Dell K812N, 5600W, 5600R OL HV-US manual Ups

Page 69

Table 16. Typical Alarms and Conditions (continued)

Alarm or Condition

Possible Cause

Action

 

 

 

 

Battery Test Failed

A weak battery string was

This is a warning notice. Dell recommends

(Alarm 191)

detected during the last battery

that you replace the batteries soon.

 

test.

 

 

Intermittent Alarm

 

 

 

 

 

 

 

 

 

Service Battery

A faulted battery string has

Contact your service representative.

 

(Alarm 149)

been detected and as a result,

 

 

the charger is disabled.

 

 

Continuous Alarm

 

 

 

 

 

 

 

 

Utility Not Present

The utility level has fallen

Transfer to battery if supporting load. Power

(Alarm 59)

below the Utility Not Present

down if not supporting load.

 

threshold (typically <25 to

 

 

Intermittent Alarm

 

 

50V).

 

 

 

 

 

 

 

 

Bypass Not Available

The utility is outside of the

Check the bypass settings. See “Settings” on

(Alarm 105)

bypass limits defined in the

page 42.

 

UPS.

 

 

 

 

 

 

 

 

 

Input AC Over Voltage

The utility voltage exceeds the

The UPS transfers to Battery mode if

 

(Alarm 6)

maximum operating range.

supporting load.

 

 

 

 

Intermittent Alarm

 

 

 

 

 

 

 

Input AC Under Voltage

The utility voltage is below the

The UPS transfers to Battery mode if

 

(Alarm 7)

minimum operating range.

supporting load.

 

 

 

 

Intermittent Alarm

 

 

 

 

 

 

 

Input Under/Over Frequency

The utility frequency is out of

The UPS transfers to Battery mode if

 

(Alarm 8)

usable frequency range.

supporting load.

 

 

 

 

Intermittent Alarm

 

 

 

 

 

 

Site Wiring Problem

An alarm triggers when the

Have a qualified electrician correct the wiring

(Alarm 194)

difference between ground and

problem. If the UPS is not wired with a neutral

neutral voltage is >15V.

wire, Site Fault should be disabled in the

Continuous Alarm

 

Settings menu (see page 42).

 

 

 

 

 

 

 

Remote Emergency Power

The external contacts in the

The UPS de-energizes the load and enters

Off

rear of the UPS are configured

Standby mode. See “Installing Remote

 

(Alarm 12)

for REPO operation and they

Emergency Power-off” on page 25 for more

have been activated.

information.

 

Continuous Alarm

 

 

 

 

 

 

 

Output Overload

The load level is at or has

The UPS can support the load indefinitely at

(Alarm 25)

exceeded the configurable

this load level.

 

threshold limit for a Level 1

 

 

Continuous Alarm

The alarm clears when the load drops below

Overload condition.

5% of the set point.

 

 

 

 

 

 

 

 

 

 

 

 

Troubleshooting

69

Image 69
Contents Users Guide October 2009 164201888 Table of Contents UPS and Battery Care Transporting the UPS Additional UPS FeaturesUPS Status Menu Event Log Menu Testing BatteriesDell Online Rack UPS IntroductionIntroduction What are You Looking For? Find It Here Finding InformationImportant Safety Instructions Safety WarningsSafety Warnings Safety Warnings Inspecting the Equipment InstallationUnpacking the Cabinet Unpacking the CabinetLifting the Cabinet 208V Rear Panel UPS Rear PanelsDell Online Rack UPS Front Panel UPS Front PanelRemoving the Battery Retaining Bracket Rackmount SetupRemoving the Battery Trays Installing the Rails Installing the Cabinet Install the UPS battery trays see Figure Installation Snap the UPS front cover into place see Figure Installing the UPS Installing the EBMRepo Connections Installing Remote Emergency Power-offRepo Connector Hardwiring the UPS Input Circuit Breaker Diagram Backfeed Protection Devices Typical External Isolating Device InstallationTerminal Position UPS Initial Startup Operation UPS Startup and ShutdownStarting the UPS UPS Shutdown Starting the UPS on BatteryControl Button Functions Control Button Sequence Control Panel FunctionsChanging the Language Display FunctionsStartup Screen UPS Status Screen LockedBypass Mode Battery ModeBad Battery Detected or Battery Disconnected UPS General Alarms ActiveStatus Summary Screens Description Battery Test Status Normal ModeStandby Mode Event Log Battery Status Screens DescriptionMeasurements Control Screens Description Control ScreensSettings Settings Description Available Settings Default SettingIdentification Settings Description Available Settings Default Setting Settings Description Available Settings Default Setting Settings Description Available Settings Default Setting Settings Description Available Settings Default Setting Transferring from Bypass to Normal Mode Transferring from Normal to Bypass ModeTransferring the UPS Between Modes Retrieving the Event LogBehavior on Overload Controlling Load Segments Through the Display Configuring Load SegmentsConfiguring Automatic Start Delay Configuring Automatic on Battery Shutdown Configuring the UPS for an EBM Configuring Battery SettingsConfiguring Automatic Restart Running Automatic Battery TestsConfiguring Automatic Battery Tests RS-232 and USB Communication Ports Additional UPS FeaturesRS-232 Communication Port Pin Assignment Dell Network Management Card on a 5600W OL UPS Dell Network Management Card OptionalDell UPS Management Software UPS Maintenance UPS and Battery CareTransporting the UPS Remove the UPS front cover see Figure Storing the UPS and Batteries When to Replace BatteriesUpdating the UPS Firmware Testing BatteriesSpecifications Rated at Nominal Inputs Regulation Normal Mode Power LevelsRegulation Battery Mode Electrical OutputOperating Temperature Environmental and SafetyTemperature Relative Humidity Safety ConformanceBattery Type Battery ConfigurationBattery Runtimes VoltageTroubleshooting Accessing Alarms and ConditionsUPS Status Menu Event Log Menu Typical Alarms and ConditionsAction UPS Troubleshooting Troubleshooting Silencing the Alarm
Related manuals
Manual 8 pages 24.59 Kb