Running Automatic Battery Tests

The automatic discharge test, enabled by default, runs during the transition from Float to Rest mode. After the test completes, the charge cycle restarts to completely charge the batteries and then continues to Rest mode normally. The automatic test runs approximately once every three months and does not run again until after three more Float to Rest mode transitions. If a manual battery test is requested, the automatic battery test timer is reset so it will not run for the next three months.

For an automatic battery test to run:

SThe Automatic Battery Tests setting must be enabled for the automatic battery tests to run. (See the following section, “Configuring Automatic Battery Tests.”)

SThe batteries must be fully charged.

SThe UPS must be in Normal mode with no active alarms.

SThe load must be higher than 10%.

Configuring Automatic Battery Tests

To configure the automatic battery tests:

1Press the button for longer than one second to go to the main menu selection and scroll down to the Settings menu using the button.

2Press the button to enter the Settings menu.

3Use the button to scroll to the Automatic Battery Tests option and press the button. The option begins to flash.

4Select whether to enable or disable the automatic battery test using the and buttons.

5Press the button to confirm.

Configuring Automatic Restart

The UPS automatically restarts if the utility power returns after the output was shut off due to depleted batteries, a shutdown input signal, or an automatic shutdown command.

You can set the load segments for the amount of time to delay the restart when utility power returns, using the Automatic Start Delay setting. See “Configuring Load Segments” on page 49. You can also configure UPS restart to depend on the battery charge level, using the Battery Charge % to Restart setting from the Settings menu (see page 45).

Operation 53

Image 53
Contents Users Guide October 2009 164201888 Table of Contents UPS and Battery Care Transporting the UPS Additional UPS FeaturesUPS Status Menu Event Log Menu Testing BatteriesDell Online Rack UPS IntroductionIntroduction What are You Looking For? Find It Here Finding InformationImportant Safety Instructions Safety WarningsSafety Warnings Safety Warnings Inspecting the Equipment InstallationUnpacking the Cabinet Unpacking the CabinetLifting the Cabinet 208V Rear Panel UPS Rear PanelsDell Online Rack UPS Front Panel UPS Front PanelRemoving the Battery Retaining Bracket Rackmount SetupRemoving the Battery Trays Installing the Rails Installing the Cabinet Install the UPS battery trays see Figure Installation Snap the UPS front cover into place see Figure Installing the UPS Installing the EBMRepo Connections Installing Remote Emergency Power-offRepo Connector Hardwiring the UPS Input Circuit Breaker Diagram Backfeed Protection Devices Typical External Isolating Device InstallationTerminal Position UPS Initial Startup Starting the UPS OperationUPS Startup and Shutdown UPS Shutdown Starting the UPS on BatteryControl Button Functions Control Button Sequence Control Panel FunctionsStartup Screen Changing the LanguageDisplay Functions UPS Status Screen LockedBypass Mode Battery ModeBad Battery Detected or Battery Disconnected UPS General Alarms ActiveStandby Mode Status Summary Screens Description Battery Test StatusNormal Mode Event Log Battery Status Screens DescriptionMeasurements Control Screens Description Control ScreensIdentification SettingsSettings Description Available Settings Default Setting Settings Description Available Settings Default Setting Settings Description Available Settings Default Setting Settings Description Available Settings Default Setting Settings Description Available Settings Default Setting Transferring from Bypass to Normal Mode Transferring from Normal to Bypass ModeTransferring the UPS Between Modes Retrieving the Event LogBehavior on Overload Controlling Load Segments Through the Display Configuring Load SegmentsConfiguring Automatic Start Delay Configuring Automatic on Battery Shutdown Configuring the UPS for an EBM Configuring Battery SettingsConfiguring Automatic Battery Tests Configuring Automatic RestartRunning Automatic Battery Tests RS-232 and USB Communication Ports Additional UPS FeaturesRS-232 Communication Port Pin Assignment Dell Network Management Card on a 5600W OL UPS Dell Network Management Card OptionalDell UPS Management Software Transporting the UPS UPS MaintenanceUPS and Battery Care Remove the UPS front cover see Figure Storing the UPS and Batteries When to Replace BatteriesUpdating the UPS Firmware Testing BatteriesSpecifications Rated at Nominal Inputs Regulation Normal Mode Power LevelsRegulation Battery Mode Electrical OutputOperating Temperature Environmental and SafetyTemperature Relative Humidity Safety ConformanceBattery Type Battery ConfigurationBattery Runtimes VoltageUPS Status Menu TroubleshootingAccessing Alarms and Conditions Event Log Menu Typical Alarms and ConditionsAction UPS Troubleshooting Troubleshooting Silencing the Alarm