Dell K812N, 5600W, 5600R OL HV-US manual Terminal Position

Page 30

6Connect the input and ground wires to the terminal block according to Figure 20 and Table 2.

Terminal Position

1 2 3

Figure 20. UPS Input Terminal Block

Table 2. UPS Wiring Specifications

Wire Function

Terminal

UPS Wire Function

Terminal Wire

Tightening Torque

Position

Size Rating*

 

 

 

 

 

 

 

 

Input

1

Input Ground

 

 

 

 

 

5.26–16 mm2

 

 

2

L2/Neutral In

2.49 Nm (22 lb in)

 

(10–6 AWG)

 

 

 

 

 

3

L1 In

 

 

 

 

 

 

 

 

 

* Use a minimum:

S10 AWG for equipment grounding wire, 75_C copper wire minimum

S8 AWG for input line and neutral wires, 75_C copper wire minimum

7Replace the terminal block cover.

8Continue to the following section, “UPS Initial Startup.”

30 Installation

Image 30
Contents Users Guide October 2009 164201888 Table of Contents Additional UPS Features UPS and Battery Care Transporting the UPSTesting Batteries UPS Status Menu Event Log MenuIntroduction Dell Online Rack UPSIntroduction Finding Information What are You Looking For? Find It HereSafety Warnings Important Safety InstructionsSafety Warnings Safety Warnings Installation Inspecting the EquipmentUnpacking the Cabinet Unpacking the CabinetLifting the Cabinet UPS Rear Panels 208V Rear PanelUPS Front Panel Dell Online Rack UPS Front PanelRackmount Setup Removing the Battery Retaining BracketRemoving the Battery Trays Installing the Rails Installing the Cabinet Install the UPS battery trays see Figure Installation Snap the UPS front cover into place see Figure Installing the EBM Installing the UPSInstalling Remote Emergency Power-off Repo ConnectionsRepo Connector Hardwiring the UPS Input Circuit Breaker Diagram Typical External Isolating Device Installation Backfeed Protection DevicesTerminal Position UPS Initial Startup Operation UPS Startup and ShutdownStarting the UPS Starting the UPS on Battery UPS ShutdownControl Panel Functions Control Button Functions Control Button SequenceChanging the Language Display FunctionsStartup Screen Screen Locked UPS StatusBad Battery Detected or Battery Disconnected Battery ModeBypass Mode UPS General Alarms ActiveStatus Summary Screens Description Battery Test Status Normal ModeStandby Mode Battery Status Screens Description Event LogMeasurements Control Screens Control Screens DescriptionSettings Settings Description Available Settings Default SettingIdentification Settings Description Available Settings Default Setting Settings Description Available Settings Default Setting Settings Description Available Settings Default Setting Settings Description Available Settings Default Setting Transferring the UPS Between Modes Transferring from Normal to Bypass ModeTransferring from Bypass to Normal Mode Retrieving the Event LogBehavior on Overload Configuring Load Segments Controlling Load Segments Through the DisplayConfiguring Automatic Start Delay Configuring Automatic on Battery Shutdown Configuring Battery Settings Configuring the UPS for an EBMConfiguring Automatic Restart Running Automatic Battery TestsConfiguring Automatic Battery Tests Additional UPS Features RS-232 and USB Communication PortsRS-232 Communication Port Pin Assignment Dell Network Management Card Optional Dell Network Management Card on a 5600W OL UPSDell UPS Management Software UPS Maintenance UPS and Battery CareTransporting the UPS Remove the UPS front cover see Figure When to Replace Batteries Storing the UPS and BatteriesTesting Batteries Updating the UPS FirmwareSpecifications Regulation Battery Mode Power LevelsRated at Nominal Inputs Regulation Normal Mode Electrical OutputTemperature Relative Humidity Environmental and SafetyOperating Temperature Safety ConformanceBattery Runtimes Battery ConfigurationBattery Type VoltageTroubleshooting Accessing Alarms and ConditionsUPS Status Menu Typical Alarms and Conditions Event Log MenuAction UPS Troubleshooting Troubleshooting Silencing the Alarm
Related manuals
Manual 8 pages 24.59 Kb