Table 7. Settings (continued)
Description | Available Settings | Default Setting |
|
|
|
Synchronization Window | [Sync Disabled] [±0.5 Hz] [±1.0 Hz] [±1.5 Hz] | ±3.0 Hz |
| [±2.0 Hz] [±2.5 Hz] [±3.0 Hz] |
|
| If ±3.0 Hz, on inverter operation the inverter tries to |
|
| synchronize with the Bypass when the Bypass |
|
| frequency is not more than 3 Hz from the nominal |
|
| output frequency; otherwise, the inverter goes to |
|
| nominal frequency. On Bypass mode, the sync |
|
| window is always ±3 Hz. |
|
| NOTE: In Sync Disabled state, if the Bypass |
|
| operation is allowed, the UPS synchronizes only |
|
| when it is operating on Bypass mode. |
|
|
|
|
Unsynchronized Transfers | [Enabled] [Disabled] | Enabled |
| If Enabled, unsynchronized transfers to the Bypass |
|
| are allowed. |
|
| If Disabled, unsynchronized transfers to the Bypass |
|
| are not allowed. |
|
| NOTE: The Qualify Bypass setting may overrule the |
|
| Unsynchronized Transfers setting. |
|
|
|
|
External Battery Modules (EBMs) | [0] [1] | 0 |
| See “Configuring the UPS for an EBM” on page 52. |
|
|
|
|
Charger | [Enabled] [Disabled] | Enabled |
| If Enabled, batteries charge normally. |
|
| If Disabled, the battery charger is off. |
|
|
|
|
Battery Charge % to Restart | [0%] [10%] [20%] [30%]...[100%] | 0% |
| When enabled, automatic restart is made when the |
|
| battery charge state reaches the selected level. If set |
|
| to 0%, the feature is disabled. |
|
|
|
|
Battery Low Alarm | [Immediate] [2 min] [3 min] [5 min] | 3 min |
| If you select a value, the battery low alarm triggers |
|
| when the set amount of backup time |
|
| (approximately) remains in the batteries. |
|
|
|
|
Automatic Battery Tests | [Enabled] [Disabled] | Enabled |
| See “Running Automatic Battery Tests” on page 53. |
|
|
|
|
Operation 45