Dell 5600R OL HV-US, K812N, 5600W manual Action

Page 68

Table 16. Typical Alarms and Conditions (continued)

Alarm or Condition

Possible Cause

Action

Battery test did not run or was interrupted.

One of the conditions listed in

Resolve the condition, then restart the test.

“Running Automatic Battery

 

Tests” on page 53 was not

 

present.

 

The UPS does not transfer to Bypass mode.

The bypass utility does not qualify.

Check the bypass utility. The UPS is receiving bypass utility power that may be unstable or in brownout conditions.

Bypass mode is disabled.

Check that the Bypass settings are configured

 

correctly. See “Settings” on page 42.

UPS on Bypass

The UPS is operating from

(Notice 169)

Bypass mode.

 

Continuous Alarm

 

The equipment transferred to bypass utility power. Battery mode is not available and your equipment is not protected; however, the utility power continues to be passively filtered by the UPS. Check for one of the following alarms: overtemperature, overload, or UPS failure.

On Manual Bypass

UPS was manually commanded

None.

(Notice 143)

to transfer to Bypass mode and

 

will remain in bypass until

 

Intermittent Alarm

 

commanded.

 

 

 

 

 

 

 

 

Battery Disconnected

The UPS does not recognize the

If the condition persists, contact your service

(Alarm 199)

internal batteries.

representative.

 

 

Continuous Alarm

Battery voltage is lower than the

Verify that all batteries are properly connected.

batteries disconnected level

If the condition persists, contact your service

 

 

 

 

 

 

defined for this UPS. This may

representative.

 

 

 

be due to a blown fuse,

 

 

 

 

intermittent battery

 

 

 

 

connection, or battery cable

 

 

 

 

being disconnected.

 

 

 

 

Low Battery Warning

Battery time remaining or

This warning is approximate. The actual time to

(Alarm 56)

 

battery capacity is lower than

shutdown may vary depending on the UPS load

 

the battery low warning level

and presence of an External Battery Module

Continuous Alarm

defined for this UPS.

(EBM).

 

 

 

 

 

 

Shutdown Imminent

Communication to external

The alarm is issued when the battery time

(Alarm 55)

 

devices stops because the UPS

remaining reaches zero. All connected devices

 

has entered a state where it may

should have already shut down gracefully.

Continuous Alarm

abruptly stop operating without

 

 

 

 

 

 

 

 

further notice unless utility

 

 

 

 

returns.

 

 

 

 

 

 

68

Troubleshooting

 

 

Image 68
Contents Users Guide October 2009 164201888 Table of Contents Additional UPS Features UPS and Battery Care Transporting the UPSTesting Batteries UPS Status Menu Event Log MenuIntroduction Dell Online Rack UPSIntroduction Finding Information What are You Looking For? Find It HereSafety Warnings Important Safety InstructionsSafety Warnings Safety Warnings Installation Inspecting the EquipmentUnpacking the Cabinet Unpacking the CabinetLifting the Cabinet UPS Rear Panels 208V Rear PanelUPS Front Panel Dell Online Rack UPS Front PanelRackmount Setup Removing the Battery Retaining BracketRemoving the Battery Trays Installing the Rails Installing the Cabinet Install the UPS battery trays see Figure Installation Snap the UPS front cover into place see Figure Installing the EBM Installing the UPSInstalling Remote Emergency Power-off Repo ConnectionsRepo Connector Hardwiring the UPS Input Circuit Breaker Diagram Typical External Isolating Device Installation Backfeed Protection DevicesTerminal Position UPS Initial Startup Starting the UPS OperationUPS Startup and Shutdown Starting the UPS on Battery UPS ShutdownControl Panel Functions Control Button Functions Control Button SequenceStartup Screen Changing the LanguageDisplay Functions Screen Locked UPS StatusBattery Mode Bypass ModeBad Battery Detected or Battery Disconnected UPS General Alarms ActiveStandby Mode Status Summary Screens Description Battery Test StatusNormal Mode Battery Status Screens Description Event LogMeasurements Control Screens Control Screens DescriptionIdentification SettingsSettings Description Available Settings Default Setting Settings Description Available Settings Default Setting Settings Description Available Settings Default Setting Settings Description Available Settings Default Setting Settings Description Available Settings Default Setting Transferring from Normal to Bypass Mode Transferring from Bypass to Normal ModeTransferring the UPS Between Modes Retrieving the Event LogBehavior on Overload Configuring Load Segments Controlling Load Segments Through the DisplayConfiguring Automatic Start Delay Configuring Automatic on Battery Shutdown Configuring Battery Settings Configuring the UPS for an EBMConfiguring Automatic Battery Tests Configuring Automatic RestartRunning Automatic Battery Tests Additional UPS Features RS-232 and USB Communication PortsRS-232 Communication Port Pin Assignment Dell Network Management Card Optional Dell Network Management Card on a 5600W OL UPSDell UPS Management Software Transporting the UPS UPS MaintenanceUPS and Battery Care Remove the UPS front cover see Figure When to Replace Batteries Storing the UPS and BatteriesTesting Batteries Updating the UPS FirmwareSpecifications Power Levels Rated at Nominal Inputs Regulation Normal ModeRegulation Battery Mode Electrical OutputEnvironmental and Safety Operating TemperatureTemperature Relative Humidity Safety ConformanceBattery Configuration Battery TypeBattery Runtimes VoltageUPS Status Menu TroubleshootingAccessing Alarms and Conditions Typical Alarms and Conditions Event Log MenuAction UPS Troubleshooting Troubleshooting Silencing the Alarm