Dell K812N, 5600W, 5600R OL HV-US manual Behavior on Overload

Page 48

Behavior on Overload

See Table 8 for an explanation of how the UPS responds to an overload condition.

Table 8. Behavior on Overload

Overload

Load Level

On Utility Power

On Bypass

On Battery

Severity

 

 

 

 

 

 

 

 

 

 

Level 1

100% to 101%

Overload alarm and

Overload alarm

Overload alarm and supports

 

 

supports load

and supports load

load until low battery

 

 

indefinitely

indefinitely

shutdown level is reached

 

 

 

 

 

Level 2

102% to 110%

Transfers to Bypass

Transfers to Fault

Transfers to Fault mode in

 

 

mode in 12 sec (±1 sec).

mode in 2 min

12 sec (±1 sec) or when low

 

 

If Bypass mode is not

(±1 sec)

battery shutdown level is

 

 

available, transfers to

 

reached

 

 

Fault mode after 12 sec

 

 

 

 

(±1 sec).

 

 

Level 3

> 110%

Transfers to Bypass

 

 

mode immediately. If

 

 

Bypass mode is not

 

 

available, transfers to

 

 

Fault mode after 300 ms

 

 

to 1 sec.

Transfers to Fault mode in 300 ms to 1 sec

Transfers to Fault mode in 300 ms to 1 sec

48 Operation

Image 48
Contents Users Guide October 2009 164201888 Table of Contents Additional UPS Features UPS and Battery Care Transporting the UPSTesting Batteries UPS Status Menu Event Log MenuIntroduction Dell Online Rack UPSIntroduction Finding Information What are You Looking For? Find It HereSafety Warnings Important Safety InstructionsSafety Warnings Safety Warnings Installation Inspecting the EquipmentUnpacking the Cabinet Unpacking the CabinetLifting the Cabinet UPS Rear Panels 208V Rear PanelUPS Front Panel Dell Online Rack UPS Front PanelRackmount Setup Removing the Battery Retaining BracketRemoving the Battery Trays Installing the Rails Installing the Cabinet Install the UPS battery trays see Figure Installation Snap the UPS front cover into place see Figure Installing the EBM Installing the UPSInstalling Remote Emergency Power-off Repo ConnectionsRepo Connector Hardwiring the UPS Input Circuit Breaker Diagram Typical External Isolating Device Installation Backfeed Protection DevicesTerminal Position UPS Initial Startup Operation UPS Startup and ShutdownStarting the UPS Starting the UPS on Battery UPS ShutdownControl Panel Functions Control Button Functions Control Button SequenceChanging the Language Display FunctionsStartup Screen Screen Locked UPS StatusBattery Mode Bypass ModeBad Battery Detected or Battery Disconnected UPS General Alarms ActiveStatus Summary Screens Description Battery Test Status Normal ModeStandby Mode Battery Status Screens Description Event LogMeasurements Control Screens Control Screens DescriptionSettings Settings Description Available Settings Default SettingIdentification Settings Description Available Settings Default Setting Settings Description Available Settings Default Setting Settings Description Available Settings Default Setting Settings Description Available Settings Default Setting Transferring from Normal to Bypass Mode Transferring from Bypass to Normal ModeTransferring the UPS Between Modes Retrieving the Event LogBehavior on Overload Configuring Load Segments Controlling Load Segments Through the DisplayConfiguring Automatic Start Delay Configuring Automatic on Battery Shutdown Configuring Battery Settings Configuring the UPS for an EBMConfiguring Automatic Restart Running Automatic Battery TestsConfiguring Automatic Battery Tests Additional UPS Features RS-232 and USB Communication PortsRS-232 Communication Port Pin Assignment Dell Network Management Card Optional Dell Network Management Card on a 5600W OL UPSDell UPS Management Software UPS Maintenance UPS and Battery CareTransporting the UPS Remove the UPS front cover see Figure When to Replace Batteries Storing the UPS and BatteriesTesting Batteries Updating the UPS FirmwareSpecifications Power Levels Rated at Nominal Inputs Regulation Normal ModeRegulation Battery Mode Electrical OutputEnvironmental and Safety Operating TemperatureTemperature Relative Humidity Safety ConformanceBattery Configuration Battery TypeBattery Runtimes VoltageTroubleshooting Accessing Alarms and ConditionsUPS Status Menu Typical Alarms and Conditions Event Log MenuAction UPS Troubleshooting Troubleshooting Silencing the Alarm