Start-Up Procedure: InfraStruXure System
Verify UPS battery operation
1. Read the messages displayed on the Symmetra PX UPS display interface: Note any alarms and verify that they are
appropriate for
2. Command the UPS to apply power to the load: a. Press the ESC key to open the
menu.
b. Select Control, and press the ENTER key.
c. Select Turn Load On/Off from the Control menu, and press the ENTER key.
d. On the next screen: select Yes, UPS Load ON, and press the ENTER key.
The interface will display the following screen:
The interface will display the following fault message:
e. Select Start up on Batt, and press the
ENTER key.
The interface will display the following screen:
54 | InfraStruXure |