American Power Conversion DC Series Product Overview and Technical Description, Specification

Page 10

2 Product Overview and Technical Description

2.1 Specification

2.1.1Rectifier

Parameter (per rectifier)

1TWF0500H54**

Approved Input Rating

115V or 230Vac

I/p Operating Range

103.5V to 264V

RMS Input Current

6.5A max @115V

3.6A max @230V

Approved Input Frequency

45 – 65Hz

 

 

range

 

 

Turn-on Surge

< 10A

 

Turn-on Time

< 2 Seconds

 

Internal Fuse

7 amp 250V time lag

 

Power Factor

99 % typical, 90 % min

Output Voltage (Nominal)

54.5V dc

O/p Current (Rated)

10.5A @ 230V, 0-50°C

 

 

 

9A @ 230V, 50-65°C

 

 

 

9A @ 115V, 0-50°C

 

 

 

8A @ 115V, 50-65°C

 

Current Limit

105 % of rated

Over Volts Protection

59.5V dc ± 0.5V

Power O/p (Rated)

500W @ 115V

 

 

 

600W @ 230V

 

 

Efficiency

83 % typical

 

 

Cooling

Fan Cooled, front to rear

 

Ambient Temp

-40 to 50°C (de-rate above 50°C)

Note :- See TWF0500 Rectifier datasheet for further or more detailed information

2.1.2

System AC Input

 

 

Input Voltage (Single phase)

90 - 264Vac (Live to Neutral)

 

(3 Phase Star)

208Vac, 380Vac, 400Vac or 415Vac (phase to phase)

 

(3 Phase Delta)

208Vac only (phase to phase)

RMS Current (max) single phase

26A @ 115V ±10%, 14.5A @ 230V ±10% (total)

RMS Current (max) 3 phase star

13A @ 208Vac, 7.2A @ 415Vac (per phase)

RMS Current (max) 3 phase delta

9.5A @ 208Vac (per phase)

 

Frequency

45 – 65 Hz

 

Efficiency

83% Typical

 

Harmonic Distortion

Complies with EN61000-3-2

User Manual 990-9178A

Page 10 of 44

18th FEB 02

DC MX06 40A Shelf

Image 10
Contents DC Series MX06 40A Shelf DC MX06 40A Shelf Contents Issue Record General Information Safety PrecautionsIntroduction Types of Hazards CEC Code C22.1-98 CanadaVisible External Damage Inspection upon Receipt of GoodsGeneral Concealed DamageAPC Worldwide Customer Support Limited Warranty Warranty InformationWarranty Limitations Product Overview and Technical Description SpecificationRectifier Parameter per rectifier 1TWF0500H54 Display + LED’s SK10 Alarm Card LayoutController SK11Available Alarms AlarmsAccess Rear Access Alarms Front Access Alarms Knockout PanelsMajor and Minor Alarms Alarm Description Major alarm Minor alarm SelectionCurrent Limit Programming Customer InputsOutput Voltage Programming Battery Test Function Input Description Location Enable Function Input Description LocationTemperature Compensation Input Description Socket Pin System ControllerWeight DimensionsMechanical Mounting Options Schematic Positive Earth ConfiguredNegative Earth Configured DCM00K02W482 System ConfigurationDCM00K02W481 DCM00K02W483Rear Access Connection Installation ProcedureSingle Phase AC Primary SupplyFront Access Connection Terminal Block Cable GlandSingle Phase, AB Feed Front Access Connection 3 3 Phase Star Supply Front access connection 4 3 Phase Delta Supply Front access connection 1 10 GMT Fuses Rear Access DC DistributionAmbient Temperature 2 10 GMT Fuses Front Access3 4 Circuit Breakers Rear Access 4 4 Circuit Breakers Front Access 5 4 Cartridge Fuses Rear Access 6 4 Cartridge Fuses Front AccessRouting Of Cables Input cablesOutput Cables Battery Back-up function External Battery InstallationLVD Function Battery Connection Diagram System Output EarthingCommissioning the System Powering up the MX06 40A ShelfGeneral Preparation Manual Handling ProcedureMethod Fault Finding / Symptoms Fault SymptomsRectifier replacement Service, Accessories & SparesController replacement