American Power Conversion DC Series user manual Ambient Temperature, 2 10 GMT Fuses Front Access

Page 33

4.2.210 GMT Fuses Front Access

No. of Outputs :

10

Output Rating :

10A max per output

Fuses :

(42A total)

GMT-** (Bussmann)

Trip Alarm :

YES

To connect the cables to the system proceed as follows:

Cables should be rated to at least the same current rating as the corresponding output fuse and be colour coded as to meet all the local installation regulations

Remove the distribution front panel to give easier access to terminal block if required. To attach the cables simply strip the ends and screw into output terminal block

Ensure stray wires do not contact the front panel metalwork.

Output 1

Top Connector :

Common (0V Rtn) / Earth (if earth link fitted)

Output 10

Output 1

Bottom Connector :

- 54Vdc, +Ve earth

Output 10

GMT Fuse ratings

DISTRIBUTION

FUSES

INPUTCONTROLLER

1

2

3

4

5

6

7

8

9

10

GMT Fuse 1

GMT Fuse 10

Continuous

Current Rating

Ambient Temperature

20oC 50oC 65oC

10A

7A

6A

5A

12A

8A

7A

6A

15A

10A

9A

8A

This table shows that the continuous current rating of a GMT fuse is less than the specified current rating. It also shows that it is affected by ambient temperature.

Lower value fuses follow the same pattern.

User Manual 990-9178A

Page 33 of 44

18th FEB 02

DC MX06 40A Shelf

Image 33
Contents DC Series MX06 40A Shelf DC MX06 40A Shelf Contents Issue Record Safety Precautions General InformationIntroduction CEC Code C22.1-98 Canada Types of HazardsGeneral Inspection upon Receipt of GoodsVisible External Damage Concealed DamageAPC Worldwide Customer Support Warranty Information Limited WarrantyWarranty Limitations Specification Product Overview and Technical DescriptionRectifier Parameter per rectifier 1TWF0500H54 Display + LED’s Controller Alarm Card LayoutSK10 SK11Alarms Available AlarmsAccess Front Access Alarms Knockout Panels Rear Access AlarmsAlarm Description Major alarm Minor alarm Selection Major and Minor AlarmsCustomer Inputs Current Limit ProgrammingOutput Voltage Programming Enable Function Input Description Location Battery Test Function Input Description LocationSystem Controller Temperature Compensation Input Description Socket PinDimensions WeightMechanical Mounting Options Positive Earth Configured SchematicNegative Earth Configured DCM00K02W481 System ConfigurationDCM00K02W482 DCM00K02W483Single Phase Installation ProcedureRear Access Connection AC Primary SupplyTerminal Block Cable Gland Front Access ConnectionSingle Phase, AB Feed Front Access Connection 3 3 Phase Star Supply Front access connection 4 3 Phase Delta Supply Front access connection DC Distribution 1 10 GMT Fuses Rear Access2 10 GMT Fuses Front Access Ambient Temperature3 4 Circuit Breakers Rear Access 4 4 Circuit Breakers Front Access 6 4 Cartridge Fuses Front Access 5 4 Cartridge Fuses Rear AccessInput cables Routing Of CablesOutput Cables External Battery Installation Battery Back-up functionLVD Function System Output Earthing Battery Connection DiagramPowering up the MX06 40A Shelf Commissioning the SystemGeneral Manual Handling Procedure PreparationMethod Fault Symptoms Fault Finding / SymptomsService, Accessories & Spares Rectifier replacementController replacement