2.5.3Battery Test Function
Input | Description | Location |
Battery Test | Front panel momentary push button. Push and hold drops | Push button mounted on |
| output volts to 45Vdc. This is below battery float voltage and | controller front panel. |
| is used to check the batteries can supply the system load. |
|
2.5.4Enable Function
Input | Description | Location |
Enable | SK22 (mounted on back- | |
| pins 1 and 2 with supplied link for “local” enable of rectifier | plane board). |
| outputs. Link pins 2 and 3 for “remote” enable. |
|
| If “remote” enable |
|
| enable rectifier outputs. |
|
| System is set to “Local Enable” as standard |
|
SK17
SK22
Note: Prior to accessing and making connections ensure batteries are disconnected from the system by setting battery connection switch to “OFF” via controller / alarm card front panel (see section 2.3) and by turning the external battery breaker off.
The AC input supply must then be turned off by operating the local isolator or disconnection device.
User Manual | Page 17 of 44 | 18th FEB 02 |
DC MX06 40A Shelf |