4.1.2.2Front Access Connection

To connect the input supply to the MX06 40A Shelf proceed as follows:

Ensure that the AC supply intended for connection is isolated, locked off and under single operator control.

The main circuit board should have been configured for an AB Feed by removing LK3 and LK4. This is normally factory configured.

Strip the ends of the AC Input cables to be connected to the input terminal block.

By unscrewing the 2 front panel screws the AC Input connection drawer can be opened as shown below. The AC Input cable is fed through the gland and screwed into the terminal block visible.

Connect as follows:

Safety earth to position marked with earth symbol (connect first)

 

Feed A

Live

to AC1

 

Feed A Neutral to AC2

 

Feed B

Live

to AC3

 

Feed B

Neutral to AC4

Terminal Block

Cable Gland

The alarm card adjacent to the AC Input drawer may need to be removed for easier access to the terminal block screws.

A strain relief bush can be fitted instead of the standard cable gland shown. Contact factory for details.

User Manual 990-9178A

Page 27 of 44

18th FEB 02

DC MX06 40A Shelf

Image 27
Contents DC Series MX06 40A Shelf DC MX06 40A Shelf Contents Issue Record Safety Precautions General InformationIntroduction CEC Code C22.1-98 Canada Types of HazardsConcealed Damage Inspection upon Receipt of GoodsGeneral Visible External DamageAPC Worldwide Customer Support Warranty Information Limited WarrantyWarranty Limitations Specification Product Overview and Technical DescriptionRectifier Parameter per rectifier 1TWF0500H54 Display + LED’s SK11 Alarm Card LayoutController SK10Alarms Available AlarmsAccess Front Access Alarms Knockout Panels Rear Access AlarmsAlarm Description Major alarm Minor alarm Selection Major and Minor AlarmsCustomer Inputs Current Limit ProgrammingOutput Voltage Programming Enable Function Input Description Location Battery Test Function Input Description LocationSystem Controller Temperature Compensation Input Description Socket PinDimensions WeightMechanical Mounting Options Positive Earth Configured SchematicNegative Earth Configured DCM00K02W483 System ConfigurationDCM00K02W481 DCM00K02W482AC Primary Supply Installation ProcedureSingle Phase Rear Access ConnectionTerminal Block Cable Gland Front Access ConnectionSingle Phase, AB Feed Front Access Connection 3 3 Phase Star Supply Front access connection 4 3 Phase Delta Supply Front access connection DC Distribution 1 10 GMT Fuses Rear Access2 10 GMT Fuses Front Access Ambient Temperature3 4 Circuit Breakers Rear Access 4 4 Circuit Breakers Front Access 6 4 Cartridge Fuses Front Access 5 4 Cartridge Fuses Rear AccessInput cables Routing Of CablesOutput Cables External Battery Installation Battery Back-up functionLVD Function System Output Earthing Battery Connection DiagramPowering up the MX06 40A Shelf Commissioning the SystemGeneral Manual Handling Procedure PreparationMethod Fault Symptoms Fault Finding / SymptomsService, Accessories & Spares Rectifier replacementController replacement