5 Commissioning the System

5.1 General

All site preparation and equipment installation in the previous chapters must be completed before commissioning.

Ensure that the AC power source isolator is switched OFF.

Switch all MX06 40A Shelf and any external battery circuit breakers to the OFF position.

5.2Powering up the MX06 40A Shelf

Set the required alarms to show a “Major” or “Minor” alarm. To do this remove the alarm card from the shelf and operate switches SW2 and SW5 (see section 2.3.4)

Switch on the external ac power supply to the MX06 40A Shelf.

Check the Rectifier module LED’s:

Check that each rectifier module has 2 green LED’s lit (if fitted), representing Input Healthy and Output Healthy. There should be no red LED’s lit.

Check the alarm card LED’s:

The alarm card has 4 LED’s (3 red and 1 yellow) the only LED that may be lit is the red “Dist Trip” which will be lit if the system has output circuit breakers that are turned off. The other LED’s should be off unless “Major” or “Minor” have been allocated to “Dist Trip”.

Set alarm card meter to read “Volts” and check that the output volts are set to the desired level. If the voltage is slightly higher or lower than required simply adjust using the alarm card front panel potentiometer (see section 2.3.1). If the output voltage is outside the specified range this may indicate a fault.

Switch on the Distribution Breakers (1, 2, 3 and 4 as required) if fitted.

Ensure the correct polarity of any connected battery strings (see section 4.4.4) then switch on any external battery breakers as required.

Switch the “Battery Connection” switch to the desired setting “ON”, “AUTO” or “OFF” (see section 4.4.2)

User Manual 990-9178A

Page 41 of 44

18th FEB 02

DC MX06 40A Shelf

Image 41
Contents DC Series MX06 40A Shelf DC MX06 40A Shelf Contents Issue Record Introduction Safety PrecautionsGeneral Information CEC Code C22.1-98 Canada Types of HazardsGeneral Inspection upon Receipt of GoodsVisible External Damage Concealed DamageAPC Worldwide Customer Support Warranty Limitations Warranty InformationLimited Warranty Rectifier Parameter per rectifier 1TWF0500H54 SpecificationProduct Overview and Technical Description Display + LED’s Controller Alarm Card LayoutSK10 SK11Access AlarmsAvailable Alarms Front Access Alarms Knockout Panels Rear Access AlarmsAlarm Description Major alarm Minor alarm Selection Major and Minor AlarmsOutput Voltage Programming Customer InputsCurrent Limit Programming Enable Function Input Description Location Battery Test Function Input Description LocationSystem Controller Temperature Compensation Input Description Socket PinMechanical DimensionsWeight Mounting Options Positive Earth Configured SchematicNegative Earth Configured DCM00K02W481 System ConfigurationDCM00K02W482 DCM00K02W483Single Phase Installation ProcedureRear Access Connection AC Primary SupplyTerminal Block Cable Gland Front Access ConnectionSingle Phase, AB Feed Front Access Connection 3 3 Phase Star Supply Front access connection 4 3 Phase Delta Supply Front access connection DC Distribution 1 10 GMT Fuses Rear Access2 10 GMT Fuses Front Access Ambient Temperature3 4 Circuit Breakers Rear Access 4 4 Circuit Breakers Front Access 6 4 Cartridge Fuses Front Access 5 4 Cartridge Fuses Rear AccessInput cables Routing Of CablesOutput Cables LVD Function External Battery InstallationBattery Back-up function System Output Earthing Battery Connection DiagramGeneral Powering up the MX06 40A ShelfCommissioning the System Method Manual Handling ProcedurePreparation Fault Symptoms Fault Finding / SymptomsController replacement Service, Accessories & SparesRectifier replacement