American Power Conversion DC Series user manual Display + LED’s

Page 11

2.1.3System Output

 

Output Voltage Nominal

54.5Vdc

 

Voltage Adjustment Range

44 V – 57 V (Below 42V LVD contact opens)

 

Current Rating

42 A @ 230Vac, 36 A @ 115Vac, 28A @ 100Vac

 

Temperature Coefficient

-76mV/°C ±10% (over range 0°C - 50°C)

 

Current Limit

100% - 110% of Rated Current

 

Reverse Quiescent Current

Less than 100mA, Typically 50mA

 

Regulation

250mV max for any line or load condition

 

Over voltage

59.5V ± 0.5V (reset by interruption of AC Input)

2.1.4

Environmental

 

 

Temperature Range -25°C to 50°C operating range

 

Humidity

85% non condensing

2.1.5

Safety Approvals

 

 

Approved to the following

CE marked to the European Low Voltage

 

 

Directive 73/23/EEC amended by 93/68/EEC

 

 

complies with BS EN60950:2000

 

 

Certified to CAN/CSA 22.2#950-00 (NRTL/C

 

 

UL1950 3rd Edition)

2.2 Display + LED’s

3½ Digit LED Display

Switchable between “Volts” and “Amps”

“Volts”

System Output Voltage

“Amps”

Total Output Load Current

 

Load Current = Rectifier Current – Batt Charge Current

4 LED Rectifier

Input Healthy

Green

 

Output Healthy

Green

 

Current Limit

Red

 

Overvoltage

Red

Single LED Rectifier

Rectifier Fail

Red

Alarm Card LED’s

Input Fail

Red

 

Distribution Trip

Red

 

Major Fault

Red

 

Minor Fault

Yellow

NB/ LED’s are lit when description is true.

User Manual 990-9178A

Page 11 of 44

18th FEB 02

DC MX06 40A Shelf

Image 11
Contents DC Series MX06 40A Shelf DC MX06 40A Shelf Contents Issue Record Introduction Safety PrecautionsGeneral Information CEC Code C22.1-98 Canada Types of HazardsConcealed Damage Inspection upon Receipt of GoodsGeneral Visible External DamageAPC Worldwide Customer Support Warranty Limitations Warranty InformationLimited Warranty Rectifier Parameter per rectifier 1TWF0500H54 SpecificationProduct Overview and Technical Description Display + LED’s SK11 Alarm Card LayoutController SK10Access AlarmsAvailable Alarms Front Access Alarms Knockout Panels Rear Access AlarmsAlarm Description Major alarm Minor alarm Selection Major and Minor AlarmsOutput Voltage Programming Customer InputsCurrent Limit Programming Enable Function Input Description Location Battery Test Function Input Description LocationSystem Controller Temperature Compensation Input Description Socket PinMechanical DimensionsWeight Mounting Options Positive Earth Configured SchematicNegative Earth Configured DCM00K02W483 System ConfigurationDCM00K02W481 DCM00K02W482AC Primary Supply Installation ProcedureSingle Phase Rear Access ConnectionTerminal Block Cable Gland Front Access ConnectionSingle Phase, AB Feed Front Access Connection 3 3 Phase Star Supply Front access connection 4 3 Phase Delta Supply Front access connection DC Distribution 1 10 GMT Fuses Rear Access2 10 GMT Fuses Front Access Ambient Temperature3 4 Circuit Breakers Rear Access 4 4 Circuit Breakers Front Access 6 4 Cartridge Fuses Front Access 5 4 Cartridge Fuses Rear AccessInput cables Routing Of CablesOutput Cables LVD Function External Battery InstallationBattery Back-up function System Output Earthing Battery Connection DiagramGeneral Powering up the MX06 40A ShelfCommissioning the System Method Manual Handling ProcedurePreparation Fault Symptoms Fault Finding / SymptomsController replacement Service, Accessories & SparesRectifier replacement