2.5 Customer Inputs

2.5.1Current Limit Programming

Input

Description

Controller

Connector

 

 

Type

 

Current Limit

Connect a DC voltage to this pin (referenced to

Rear Access

SK17-2

Program

signal common or –Ve output) to reduce the system

Front Access

SK4-20

 

output current limit point.

 

 

 

Current limit is programmed down 1A per 1.5V

 

 

 

program voltage. Max program voltage 7.5V.

 

 

5V aux

5V aux can be used to program down current limit

Rear Access

SK17-5

 

level by linking to program pin.

Front Access

SK4-15

The system output current limit can also be set to either the standard “High” (100%) level or “Low” (70%) level by using SK13.

For “High” current limit level link pins 1 and 2 (default setting)

For “Low” current limit level link pins 2 and 3

Selecting “Low” current limit level will program down each rectifiers current limit level to roughly 70% of the default level. (See section 2.1.1 for default levels). This is the same as connecting the 5V aux pin to the current limit program pin as detailed above.

Note/ using both programming methods together will not double the effect

SK13

2.5.2Output Voltage Programming

Input

 

Description

Controller

Connector

 

 

 

type

 

Voltage

 

Connect a DC voltage to this pin (referenced to

Rear Access

SK17-7

Programming

 

signal common or –Ve output) to adjust the system

Front Access

SK4-18

 

 

output voltage.

 

 

 

 

This pin floats at 2.5V nominal with respect to

 

 

 

 

negative output (O/P @ 54.5V)

 

 

 

 

Applying a DC voltage adjusts the output by –1V/V.

 

 

 

 

(For 1V swing on program pin the output voltage

 

 

 

 

changes by –1V)

 

 

 

 

The programming voltage range is 0V – 14V, giving a

 

 

 

 

max adjustment range of 57V to 43V.

 

 

 

 

Note: See section 2.4 for SK4, SK17 location photo

 

 

User Manual 990-9178A

 

18th FEB 02

DC MX06 40A Shelf

Page 16 of 44

 

Image 16
Contents DC Series MX06 40A Shelf DC MX06 40A Shelf Contents Issue Record General Information Safety PrecautionsIntroduction Types of Hazards CEC Code C22.1-98 CanadaInspection upon Receipt of Goods GeneralVisible External Damage Concealed DamageAPC Worldwide Customer Support Limited Warranty Warranty InformationWarranty Limitations Product Overview and Technical Description SpecificationRectifier Parameter per rectifier 1TWF0500H54 Display + LED’s Alarm Card Layout ControllerSK10 SK11Available Alarms AlarmsAccess Rear Access Alarms Front Access Alarms Knockout PanelsMajor and Minor Alarms Alarm Description Major alarm Minor alarm SelectionCurrent Limit Programming Customer InputsOutput Voltage Programming Battery Test Function Input Description Location Enable Function Input Description LocationTemperature Compensation Input Description Socket Pin System ControllerWeight DimensionsMechanical Mounting Options Schematic Positive Earth ConfiguredNegative Earth Configured System Configuration DCM00K02W481DCM00K02W482 DCM00K02W483Installation Procedure Single PhaseRear Access Connection AC Primary SupplyFront Access Connection Terminal Block Cable GlandSingle Phase, AB Feed Front Access Connection 3 3 Phase Star Supply Front access connection 4 3 Phase Delta Supply Front access connection 1 10 GMT Fuses Rear Access DC DistributionAmbient Temperature 2 10 GMT Fuses Front Access3 4 Circuit Breakers Rear Access 4 4 Circuit Breakers Front Access 5 4 Cartridge Fuses Rear Access 6 4 Cartridge Fuses Front AccessRouting Of Cables Input cablesOutput Cables Battery Back-up function External Battery InstallationLVD Function Battery Connection Diagram System Output EarthingCommissioning the System Powering up the MX06 40A ShelfGeneral Preparation Manual Handling ProcedureMethod Fault Finding / Symptoms Fault SymptomsRectifier replacement Service, Accessories & SparesController replacement