American Power Conversion DC Series user manual Front access connection

Page 29

4.1.3.2Front access connection

To connect the input supply to the MX06 40A Shelf proceed as follows:

The AC input current to the system should also be limited by an appropriate device in the event of a short circuit as defined in EN60950 to protect the internal wiring of the end use equipment. The device(s) should be rated accordingly.

Ensure that the AC supply intended for connection is isolated, locked off and under single operator control.

The main circuit board should have been configured for 3-phase star use by removal of LK2 and LK3. This is normally factory configured.

Strip the ends of the AC Input cables to be connected to the Input terminal block.

By unscrewing the 2 front panel screws the AC Input connection drawer can be opened as shown below. The AC Input cable is fed through the gland and screwed into the terminal block visible.

Connect as follows:

Safety earth to position marked with earth symbol (connect first)

 

Phase 1 to AC1

 

Phase 2 to AC3

 

Phase 3 to AC4

 

Neutral to AC2 (neutral is required as system is a star configuration)

Terminal Block

Cable Gland

The alarm card adjacent to the AC Input drawer may need to be removed for easier access to the terminal block screws.

Refer to section 5 entitled “Commissioning the system” before applying AC power.

User Manual 990-9178A

Page 29 of 44

18th FEB 02

DC MX06 40A Shelf

Image 29
Contents DC Series MX06 40A Shelf DC MX06 40A Shelf Contents Issue Record Introduction Safety PrecautionsGeneral Information CEC Code C22.1-98 Canada Types of HazardsGeneral Inspection upon Receipt of GoodsVisible External Damage Concealed DamageAPC Worldwide Customer Support Warranty Limitations Warranty InformationLimited Warranty Rectifier Parameter per rectifier 1TWF0500H54 SpecificationProduct Overview and Technical Description Display + LED’s Controller Alarm Card LayoutSK10 SK11Access AlarmsAvailable Alarms Front Access Alarms Knockout Panels Rear Access AlarmsAlarm Description Major alarm Minor alarm Selection Major and Minor AlarmsOutput Voltage Programming Customer InputsCurrent Limit Programming Enable Function Input Description Location Battery Test Function Input Description LocationSystem Controller Temperature Compensation Input Description Socket PinMechanical DimensionsWeight Mounting Options Positive Earth Configured SchematicNegative Earth Configured DCM00K02W481 System ConfigurationDCM00K02W482 DCM00K02W483Single Phase Installation ProcedureRear Access Connection AC Primary SupplyTerminal Block Cable Gland Front Access ConnectionSingle Phase, AB Feed Front Access Connection 3 3 Phase Star Supply Front access connection 4 3 Phase Delta Supply Front access connection DC Distribution 1 10 GMT Fuses Rear Access2 10 GMT Fuses Front Access Ambient Temperature3 4 Circuit Breakers Rear Access 4 4 Circuit Breakers Front Access 6 4 Cartridge Fuses Front Access 5 4 Cartridge Fuses Rear AccessInput cables Routing Of CablesOutput Cables LVD Function External Battery InstallationBattery Back-up function System Output Earthing Battery Connection DiagramGeneral Powering up the MX06 40A ShelfCommissioning the System Method Manual Handling ProcedurePreparation Fault Symptoms Fault Finding / SymptomsController replacement Service, Accessories & SparesRectifier replacement