American Power Conversion DC Series user manual Major and Minor Alarms

Page 15

2.4.4Major and Minor Alarms

In an MX06 40A Shelf, 9 of the available alarms can be set to show as a “Minor” or “Major” alarm. As standard the alarm outputs are open collector transistor outputs available from the connectors as detailed in the 2 previous sections. If an alarm is selected as a Minor or Major alarm it also lights the corresponding “Major” or “Minor” front panel LED and the “Major” or “Minor” relay contacts also change over. More than one alarm can be selected at once and each alarm can be selected as both Major and Minor if required.

The relay contacts are rated as follows:

AC Rating

-

0.5A @ 125Vac

DC Rating

-

1A @ 24Vdc

Max VDC

-

0.6A @ 110Vdc

Alarm

Description

Major alarm

Minor alarm

 

 

selection

selection

Over Temperature

1 or more rectifiers tripped due to excessive

SW2-1

SW5-1

 

internal temperatures

 

 

 

(Resets itself when cooled down)

 

 

Over Volts

1 or more rectifiers tripped due to excessive

SW2-2

SW5-2

 

o/p voltage (interrupt AC input or remove

 

 

 

rectifier and refit to reset)

 

 

Over Current

1 or more rectifiers in current limit state

SW2-3

SW5-3

Fan Fail

One or more of the Rectifier fans have

SW2-4

SW5-4

 

stopped

 

 

Bus Voltage Low

System volts below 48V LVD imminent

SW2-5

SW5-5

A.C Fail

1 or more of the AC input feeds failed

SW2-6

SW5-6

Fuse Fail

1 or more fuse blown or breaker tripped

SW2-7

SW5-7

2 or more Rectifier Fail

2 or more rectifiers giving output < 31Vdc

SW2-10

SW5-10

Rectifier Fail

1 Rectifier giving output less than 31V dc

SW2-11

SW5-11

See sections 2.3 for info on SW2 and SW5 location and relay contact pin-outs.

User Manual 990-9178A

Page 15 of 44

18th FEB 02

DC MX06 40A Shelf

Image 15
Contents DC Series MX06 40A Shelf DC MX06 40A Shelf Contents Issue Record Safety Precautions General InformationIntroduction CEC Code C22.1-98 Canada Types of HazardsConcealed Damage Inspection upon Receipt of GoodsGeneral Visible External DamageAPC Worldwide Customer Support Warranty Information Limited WarrantyWarranty Limitations Specification Product Overview and Technical DescriptionRectifier Parameter per rectifier 1TWF0500H54 Display + LED’s SK11 Alarm Card LayoutController SK10Alarms Available AlarmsAccess Front Access Alarms Knockout Panels Rear Access AlarmsAlarm Description Major alarm Minor alarm Selection Major and Minor AlarmsCustomer Inputs Current Limit ProgrammingOutput Voltage Programming Enable Function Input Description Location Battery Test Function Input Description LocationSystem Controller Temperature Compensation Input Description Socket PinDimensions WeightMechanical Mounting Options Positive Earth Configured SchematicNegative Earth Configured DCM00K02W483 System ConfigurationDCM00K02W481 DCM00K02W482AC Primary Supply Installation ProcedureSingle Phase Rear Access ConnectionTerminal Block Cable Gland Front Access ConnectionSingle Phase, AB Feed Front Access Connection 3 3 Phase Star Supply Front access connection 4 3 Phase Delta Supply Front access connection DC Distribution 1 10 GMT Fuses Rear Access2 10 GMT Fuses Front Access Ambient Temperature3 4 Circuit Breakers Rear Access 4 4 Circuit Breakers Front Access 6 4 Cartridge Fuses Front Access 5 4 Cartridge Fuses Rear AccessInput cables Routing Of CablesOutput Cables External Battery Installation Battery Back-up functionLVD Function System Output Earthing Battery Connection DiagramPowering up the MX06 40A Shelf Commissioning the SystemGeneral Manual Handling Procedure PreparationMethod Fault Symptoms Fault Finding / SymptomsService, Accessories & Spares Rectifier replacementController replacement