2.4.4Major and Minor Alarms
In an MX06 40A Shelf, 9 of the available alarms can be set to show as a “Minor” or “Major” alarm. As standard the alarm outputs are open collector transistor outputs available from the connectors as detailed in the 2 previous sections. If an alarm is selected as a Minor or Major alarm it also lights the corresponding “Major” or “Minor” front panel LED and the “Major” or “Minor” relay contacts also change over. More than one alarm can be selected at once and each alarm can be selected as both Major and Minor if required.
The relay contacts are rated as follows:
AC Rating | - | 0.5A @ 125Vac |
DC Rating | - | 1A @ 24Vdc |
Max VDC | - | 0.6A @ 110Vdc |
Alarm | Description | Major alarm | Minor alarm |
|
| selection | selection |
Over Temperature | 1 or more rectifiers tripped due to excessive | ||
| internal temperatures |
|
|
| (Resets itself when cooled down) |
|
|
Over Volts | 1 or more rectifiers tripped due to excessive | ||
| o/p voltage (interrupt AC input or remove |
|
|
| rectifier and refit to reset) |
|
|
Over Current | 1 or more rectifiers in current limit state | ||
Fan Fail | One or more of the Rectifier fans have | ||
| stopped |
|
|
Bus Voltage Low | System volts below 48V LVD imminent | ||
A.C Fail | 1 or more of the AC input feeds failed | ||
Fuse Fail | 1 or more fuse blown or breaker tripped | ||
2 or more Rectifier Fail | 2 or more rectifiers giving output < 31Vdc | ||
Rectifier Fail | 1 Rectifier giving output less than 31V dc |
See sections 2.3 for info on SW2 and SW5 location and relay contact
User Manual | Page 15 of 44 | 18th FEB 02 |
DC MX06 40A Shelf |