American Power Conversion DC Series user manual Front access connection

Page 31

4.1.4.2Front access connection

To connect the input supply to the MX06 40A Shelf proceed as follows:

The AC input current to the system should also be limited by an appropriate device in the event of a short circuit as defined in EN60950 to protect the internal wiring of the end use equipment. The device(s) should be rated accordingly.

Ensure that the AC supply intended for connection is isolated, locked off and under single operator control.

The main circuit board should have been factory configured for 3-phase delta prior to sale. LK2 and LK4 should have been fitted but LK1 and LK3 should be removed. Also an external link should connect AC2 to AC5. This is normally factory configured.

Strip the ends of the AC Input cables to be connected to the Input terminal block.

By unscrewing the 2 front panel screws the AC Input connection draw can be opened as shown below. The AC Input cable is fed through the gland and screwed into the terminal block visible.

Connect as follows:

Safety earth to position marked with earth symbol (connect first)

 

Phase 1 to AC1

 

Phase 2 to AC2

 

Phase 3 to AC4

Terminal Block

Cable Gland

The alarm card adjacent to the AC Input drawer may need to be removed for easier access to the terminal block screws

Refer to section 5 entitled “Commissioning the system” before applying AC power.

User Manual 990-9178A

Page 31 of 44

18th FEB 02

DC MX06 40A Shelf

Image 31
Contents DC Series MX06 40A Shelf DC MX06 40A Shelf Contents Issue Record General Information Safety PrecautionsIntroduction CEC Code C22.1-98 Canada Types of HazardsConcealed Damage Inspection upon Receipt of GoodsGeneral Visible External DamageAPC Worldwide Customer Support Limited Warranty Warranty InformationWarranty Limitations Product Overview and Technical Description SpecificationRectifier Parameter per rectifier 1TWF0500H54 Display + LED’s SK11 Alarm Card LayoutController SK10Available Alarms AlarmsAccess Front Access Alarms Knockout Panels Rear Access AlarmsAlarm Description Major alarm Minor alarm Selection Major and Minor AlarmsCurrent Limit Programming Customer InputsOutput Voltage Programming Enable Function Input Description Location Battery Test Function Input Description LocationSystem Controller Temperature Compensation Input Description Socket PinWeight DimensionsMechanical Mounting Options Positive Earth Configured SchematicNegative Earth Configured DCM00K02W483 System ConfigurationDCM00K02W481 DCM00K02W482AC Primary Supply Installation ProcedureSingle Phase Rear Access ConnectionTerminal Block Cable Gland Front Access ConnectionSingle Phase, AB Feed Front Access Connection 3 3 Phase Star Supply Front access connection 4 3 Phase Delta Supply Front access connection DC Distribution 1 10 GMT Fuses Rear Access2 10 GMT Fuses Front Access Ambient Temperature3 4 Circuit Breakers Rear Access 4 4 Circuit Breakers Front Access 6 4 Cartridge Fuses Front Access 5 4 Cartridge Fuses Rear AccessInput cables Routing Of CablesOutput Cables Battery Back-up function External Battery InstallationLVD Function System Output Earthing Battery Connection DiagramCommissioning the System Powering up the MX06 40A ShelfGeneral Preparation Manual Handling ProcedureMethod Fault Symptoms Fault Finding / SymptomsRectifier replacement Service, Accessories & SparesController replacement