3. Installation
3.2.2 Mounting Holes
Refer to 2.3.3 Panel Cutout Dimensions for machining the mounting parts.
-Prepare the gasket and mounting metal hasps to install the Operator Panel.
-To ensure
-The panel thickness range should be from 1.6 to 5.0 mm. Choose a panel thickness taking
the strength of the panel into consideration.
1.6~5.0mm
-For easier maintenance, operation, and improved ventilation, make sure to install the Operator Panel at least 100 mm away from surrounding structures and other equipment.
[Unit : mm]
100
100
100 |
| 100 |
| 100 |
100
100
-Use the Operator Panel within the operating ambient temperature range of 5 to 40 degC and operating ambient humidity range of 20 to 80%. The Operator Panel may malfunction if it is used outside of these ranges. (The operating ambient temperature range applies to both inside the Controller Box and outside the Controller Box.)
Inside Outside
Controller Controller
Box Box
-Prevent the Operator Panel from overheating due to heat generated by surrounding equipment.
10 | OP1 Rev.1a |