1.Names and functions

„About the change of parameter settings

By default, the inverter is set with parameters to the mode in which it controls the operation of the machine via a terminal board. Moreover, the inverter is set so that the switching between forward run and reverse run cannot be performed using its operation panel.

To operate the inverter using this unit, parameter settings need to be changed, as described below.

Parameter CMOd (Command input mode)

=1

(Pane/LCD-option)

Parameter FMOd (Frequency input mode 1)=4

(Pane/LCD-option)

Parameter Fr (Panel FWD/REV selection)

=2

(Forward (switchable)),

 

3

(Reverse (switchable))

This change of parameter settings makes it possible to start operation using the [RUN] key, to stop operation using the [STOP/RESET] key, and to switch between forward run and reverse run using the [FWD/REV] key.

Furthermore, it allows you to set an operation frequency using the control dial.

Refer to “5.1 Setting a panel operation frequency.”

1-3

Image 10
Contents LCD Remote Keypad „ Explanation of model code Introduction„ Check product purchase Introduction „ Optional products Model numberSafetyprecautionsprecautions Explanation of markings „ Limitation of useSafety precautions „ Handling in general „ Transportation and installation„ Disposal Safety precautions „ Operations„ Notes on operations Contents Names. Namesand functionsand functions Names and functions „ LCD panelNames and functions „ About the change of parameter settings Installing the remote keypad to the inverter Installing the remote keypad to the board optional Installing the LCD remote keypadInverter unit Remote control optionalRemote keypad Language Selection window appears on the screen インバータ⇒パネルStatus Monitor Mode Top View ModeParameter Setup Mode 54. .標About準モニタモードavailable modes„ Explanation of the top window Operation. in Top View Modein Top View ModeSetting a panel operation frequency Functions of function keysUsing an Easy key function „ To change the frequency during operationOperation Panel and Remote When used with a VF-AS1 inverter Operation in Top View ModeAlways Quick mode parameter PSEL=2 Operation Panel and Remote When used with a VF-PS1 inverterPress the F2 Lng key Operation in Top View Mode Peak/Minimum Hold settingSelecting a language to be displayed Select/confirm the desired language with the control dialPerforming jog run Press the F4 key to carry out jog runEmergency stop/reset operation 60.0 HzSelect/confirm History function using the control dial Operation. in Parameter inSetupParameterModeSetup Mode„ When Quick mode is selected „ In this window, settings can be changedOperation in Parameter Setup Mode Setting a basic parameterSelect/confirm Basic parameters using the control dial Select/confirm Extended parameters using the control dial Setting an extended parameterChange the parameter setting Select/confirm Changed Parameters using the control dial [CMOd]Operation. in Status Monintor modeStatus Monitor Mode Items displayed Description DisplayDisplaying details of an item monitored Operation. Operationby copy functionin a copy function VFAS1 VFPS1Display of copy loading(fixed screen) Copy to LCDOperation by a copy function Display of copy finishCopy to inverter [Copy to the inverter]Confirm a memory information Function Key Display Position WarrantyList of function key functionsFunction Reference Specifications 710. 状態. モSpecificationsニタモードでの操作„ Outside dimensions unit mm Before. Beforemaking a servicemakingcall a service call Problems Possible causes RemediesBefore making a service call Warranty. Warranty