3 Operating the SAMMS-LV Device

3.4 Output Devices

You can use the following SAMMS-LV output devices:

AC Outputs

The SAMMS-LVX device provides up to three AC coil drivers capable of driving contactors up to size 6, while SAMMS-LVE provides one coil driver.

Control Relays

The device provides up to eight software-controlled relays. These relays are helpful in local two-wire and other applications requiring maintained contacts.

Timing Relays

The SAMMS-LV device contains four internal software timing relays. You can configure all four timers as on-delay timers; however, if needed, you can configure the two adjustable timers (timing relays TR1 and TR2) as either on-delay or off-delay timers. Using the Hand Held Communicator, you can program timing relays TR1 and TR2 from 0 through 200 seconds (functions F13 and F14). Timing relay TR3 has a fixed 1 second delay, and timing relay TR4 has a fixed 30 seconds delay. Table

3.1illustrates the type of timers used on the device and their ranges.

Timer

Type

Time (in seconds)

 

 

 

TR1

Programmable on-delay or

0 - 200

 

off-delay

 

 

 

 

TR2

Programmable on-delay or

0 - 200

 

off-delay

 

 

 

 

TR3

Fixed on-delay

1

 

 

 

TR4

Fixed on-delay

30

Table 3.1 Types of software timing relays

Pilot LEDs

The SAMMS-LVX device contains three light bars on the front panel, while the SAMMS-LVE contains two light bars. Light bar L1 is reserved and must be used as the STOP or OFF LED. You can configure L2 and L3 at your discretion. The Hand, Off and Auto LEDs correspond to the Hand, Off and Auto pushbuttons on the front panel as illustrated in Figure 3.4. You can use the Incomplete Sequence LED in reduced-voltage applications or to verify contactor operation. Refer to Figure 3.4 for the location of the LEDs and Table 3.2 for a description of the LED states.

Flashing Pilot LEDs

The front panel contains two or three flashing light bars that indicate various conditions such as on-delay timing. These flashing light bars, L1, L2 and L3 as defined above, indicate different output devices if they are flashing rather than if they are on constantly. Refer to Figure 3.4 for an illustration of pilot LEDs.

3.5 Input Devices

You can use the following input devices with the SAMMS-LV device.

Remote AC Inputs

For SAMMS-LVX you can use four 120 VAC or VDC inputs for remote control, or you can use two inputs for SAMMS-LVE.

Front Panel Pushbuttons

The SAMMS-LV device has six front-panel pushbuttons for local control of the device. You must use pushbutton 1 (PB1) for stopping the motor. You must use three of the pushbuttons (PB4-PB6) for the Hand, Off and Auto functions if these functions are used in your configuration. If these functions are not used, you may use PB4-PB6 for other functions. You can configure the other two pushbuttons (PB2 and PB3) at your discretion. Refer to Figure 3.4 for assignment of pushbuttons. Insert labels are used to identify the function associated with each pushbutton or light bar.

Software Auxiliary Contacts

Any number of internal (software) auxiliary contacts can be configured. These contacts show either a normally open (NO) or normally closed (NC) status. You can set up these auxiliary contacts using the SAMMS-LV software. Through the SAMMS-LV software, the pilot LEDs also have auxiliary con- tacts.

 

 

 

 

 

 

 

 

STATE

 

 

 

 

 

 

LED

 

On

Flashing

 

 

 

 

 

 

Current Unbalance

 

> 40%

20 - 40%

 

 

 

 

 

 

Impending Trip

 

> 110%

> 100% - <110%

 

 

 

 

 

 

Overload Trip

 

Trip

Start Inhibit

 

 

 

 

 

 

Incomplete

 

Trip

 

 

Sequence

 

 

 

 

 

 

 

 

 

External Trip/Alarm

 

Trip: Loss of Load or

Alarm: Loss of

 

 

 

Jam

Load or Process

 

 

 

 

Current

 

 

 

 

 

 

CPU Fault

 

Trip: CPU Failure or

 

 

 

 

Low Voltage

 

 

 

 

 

 

 

Ground Fault

 

Trip

Alarm

 

 

 

 

 

 

Light bar (L1)

 

Stop or Off

Off Delay Timer

 

 

 

 

Timing

 

 

 

 

 

 

Light bar (L2)

 

Start, On, Forward,

On Delay Timer

 

 

 

Low Speed, Right

Timing

 

 

 

 

 

 

Light bar (L3)

 

Reverse, High Speed,

On Delay Timer

 

 

 

Left

Timing

 

Table 3.2 Description

 

of pilot LEDs

 

 

 

 

Software Timer Inputs

Each timer has an unlimited number of normally open (NO) and normally closed (NC) contacts. Timers configured as on-delay timers have an unlimited supply of normally open timed-closed (NOTC), and normally closed timed-open (NCTO) contacts. Timers configured as off-delay timers have an unlimited supply of normally open timed-open (NOTO), and normally closed timed-closed (NCTC) contacts.

Communications Inputs

A serial, RS-485 communications port is located on the back of the device for external communications.

The communications inputs must be included in the ladder logic (control circuit).

12

Image 14
Contents SAMMS-LV Qualified Person Contents Qualified Person Signal WordsField Service Operation About this Manual SAMMS-LV Device Models Advanced Protection for Low-Voltage MotorsProgramming Control Circuits Using the Standardized Control PanelOverload Protection Outputs One Change settings requires password Yes Remote inputsSAMMS-LV Model Light barsInstalling the SAMMS-LV Device Full voltage non-reversing connection diagram Grounding the Device SAMMS-LV device communications connections Performing a Lamp Test Password ProtectionUsing the Reset/Test Push Button Performing an Overload Relay TestOutput Devices Input DevicesLadder Diagrams Library of Standard Ladder Diagrams Custom Ladder DiagramsSAMMS-LVX Standard control circuits RVA Incomplete Sequence Ridethrough Upon Loss of Power SAMMS-LVX OnlyMotor Ambient Temperature Intelligent Reduced-Voltage Starting SAMMS-LVX OnlyODP motor thermal signature Operating the SAMMS-LV Operating the SAMMS-LV Device 10 Motor protection graph Dual Overload Protection SAMMS-LVX Only Ultimate Trip Level and Service FactorPhase Unbalance Jam Protection SAMMS-LVX OnlyRepetitive Starts Ground Fault DetectionStator Protection Start InhibitSize Pickup Current Default Pickup Range Autoreset After a Trip SAMMS-LVX OnlyUsing the Hand Held Communicator HHC Emergency RestartingJam pickup current F24 Loss of load protection or warning Function Number5A CT primary current if used Full load current for OLR No List Key Using the Enter KeyFunction Key UP and Down KeysExternal trips Enable/disable phase unbalance CapabilityMeans warning Select ground fault pick-up current Value 2A-5AStep Size Second Default Value Iflc is the value of Iflc forSelect jam pickup current 120-400% I FLC F24 Loss of Load Using the SAMMS-LV Device Func TionsProgram Mode/Passwords 200% 50% 480013 Entering and changing passwords F1 Control Circuit Number and Incomplete Se- quence Status F0 Ambient TemperatureSAMMS-LV Functions F2 Size for Overload Relay #145A Overload Setting Step Default Relay Size Range 24.0A 36AF4 Full-Load Current for Overload Relay #1 90AF9 Phase Unbalance Protection F6 Service FactorF8 Autoreset SAMMS-LVX Only F7 Overload Trip ClassF11 Emergency Restarting F12 Ground Fault Protection or WarningF10 Display Time to Restart F14 Set Programmable Timer #2 F12A Ground Fault Pickup CurrentF13 Set Programmable Timer #1 F15 Display CurrentF18 Display Total Elapsed Run Time of the Motor F21 Reset Motor DataF17 Current Unbalance F19 Number of Motor StartsF24 Loss of Load Protection or Warning SAMMS-LVX Only F25 Percentage of Motor Winding TemperatureF23A Jam Pickup Current SAMMS-LVX Only F24A Loss of Load Pickup Current SAMMS-LVX OnlyF27 Address Troubleshooting Error Condition Troubleshooting Guide Error Condition Appendix a Technical Specifications Overload Specifications Statistical Data Dimensions Catalog Number SAM4 Switch # Function Position Samms Sensor, sizes 1C, 2A, 2B Page Siemens Energy Automation, Inc