Siemens MCC-3298 user manual F12A Ground Fault Pickup Current, F13 Set Programmable Timer #1

Page 37

3 Operating the SAMMS-LV Device

F12A - Ground Fault Pickup Current

1.Press the LIST key to view the active ground fault pickup current in use. The range of values and default values are shown in the table below:

Size

Pickup Current

Default Pickup

 

Range

Current

 

 

 

1A

1.5A

1.5A

 

 

 

1B

2A to 5A

5A

 

 

 

1C

2A to IFLC*

5A

2A

2A to IFLC*

10A

2B

2A to IFLC*

10A

3

2A to IFLC*

10A

4

2A to IFLC*

10A

5

5A to IFLC*

10A

6

10A to I FLC*

20A

*IFLC is the value of IFLC for OLR#2 if F3 is not set to OFF. If F3 is OFF, IFLC is the value of IFLC for OLR#1.

2.To change the setting, you must be in program mode.

3.To change the setting, press the UP or DOWN key to display the setting options, then press ENTER to select the setting that is shown. The display blanks while the ENTER key is pressed.

4.Repeat Step 3 if you select an incorrect setting.

5.To exit the program mode, press and hold the (F)unction key for several seconds. The display will show “Prog.” Press the UP or DOWN key to change to the display mode.

6.Press the (F)unction key to go to other functions.

F13 - Set Programmable Timer #1

1.Press the LIST key to view the active setting for timer #1. The default setting is OFF. If the timer is not used in the control circuit, OFF is displayed and the UP, DOWN, and ENTER keys are disabled. OFF is also displayed for a setting of 0 seconds. The timer may be adjusted from 0 - 200 seconds in one second increments.

2.To change the setting, you must be in program mode.

3.To change the setting, press the UP or DOWN key until the desired value is displayed then press the ENTER key to select the setting. The display blanks while the ENTER key is pressed.

4.Repeat Step 3 if you select an incorrect setting.

5.To exit the program mode, press and hold the (F)unction key for several seconds. The display will show “Prog.” Press the UP or DOWN key to change to the display mode.

6. Press the (F)unction key to go to other functions.

F14 - Set Programmable Timer #2

1.Press the LIST key to view the active setting for timer #2. The default setting is OFF. If the timer is not used in the control circuit, OFF is displayed and the UP, DOWN, and ENTER keys are disabled. OFF is also displayed for a setting of 0 seconds. The timer may be adjusted from 0 - 200 seconds in one second increments.

2.To change the setting, you must be in program mode.

3.To change the setting, press the UP or DOWN key until the desired value is displayed then press the ENTER key to select the setting. The display blanks while the ENTER key is pressed.

4.Repeat Step 3 if you select an incorrect setting.

5.To exit the program mode, press and hold the (F)unction key for several seconds. The display will show “Prog.” Press the UP or DOWN key to change to the display mode.

6.Press the (F)unction key to go to other functions.

F15 - Display Current

1.Press the LIST key to view the instantaneous line currents or the average instantaneous line current. (The LIST key is disabled for full voltage, part-winding starters.) For instanta- neous line currents, the display shows the phase designator (A, b, or C) in the left-most character followed by three significant digits of the value of the current. For the average instantaneous line current, four digits are displayed without a phase designator.

a.Because only four characters can display at a time, individual line currents of 1000 amps and above are displayed as three dashes following the phase designa- tor, e.g., “A - - -.”

b.For sizes 1A, 1B, and 1C, the current is displayed to the nearest 0.1 amp for currents less than 100 amps; for 100 amps and above, currents are displayed to the nearest 1 amp. For sizes 2A, 2B,3, 4, and 5, the current is displayed to the nearest 1 amp. For size 6, current is displayed to the nearest 2 amps.

2.To view another line current, press the UP or DOWN key to scroll through the four selections.

3.The ENTER key is disabled for this function.

4.Press the (F)unction key to go to other functions.

F16 - Trip Current

1.Press the LIST key to view the value of the current that caused the most recent trip.

2.The UP, DOWN, and ENTER keys are disabled for this function.

3.Press the (F)unction key to go to other functions.

35

Image 37
Contents SAMMS-LV Qualified Person Contents Field Service Operation Signal WordsQualified Person About this Manual Advanced Protection for Low-Voltage Motors SAMMS-LV Device ModelsOverload Protection Using the Standardized Control PanelProgramming Control Circuits SAMMS-LV Model Change settings requires password Yes Remote inputsOutputs One Light barsInstalling the SAMMS-LV Device Full voltage non-reversing connection diagram Grounding the Device SAMMS-LV device communications connections Using the Reset/Test Push Button Password ProtectionPerforming a Lamp Test Performing an Overload Relay TestInput Devices Output DevicesCustom Ladder Diagrams Ladder Diagrams Library of Standard Ladder DiagramsSAMMS-LVX Standard control circuits RVA Motor Ambient Temperature Ridethrough Upon Loss of Power SAMMS-LVX OnlyIncomplete Sequence Intelligent Reduced-Voltage Starting SAMMS-LVX OnlyODP motor thermal signature Operating the SAMMS-LV Operating the SAMMS-LV Device 10 Motor protection graph Phase Unbalance Ultimate Trip Level and Service FactorDual Overload Protection SAMMS-LVX Only Jam Protection SAMMS-LVX OnlyStator Protection Ground Fault DetectionRepetitive Starts Start InhibitUsing the Hand Held Communicator HHC Autoreset After a Trip SAMMS-LVX OnlySize Pickup Current Default Pickup Range Emergency Restarting5A CT primary current if used Full load current for OLR No Function NumberJam pickup current F24 Loss of load protection or warning Function Key Using the Enter KeyList Key UP and Down KeysCapability External trips Enable/disable phase unbalanceStep Size Second Default Value Select ground fault pick-up current Value 2A-5AMeans warning Iflc is the value of Iflc forProgram Mode/Passwords Using the SAMMS-LV Device Func TionsSelect jam pickup current 120-400% I FLC F24 Loss of Load 200% 50% 480013 Entering and changing passwords SAMMS-LV Functions F0 Ambient TemperatureF1 Control Circuit Number and Incomplete Se- quence Status F2 Size for Overload Relay #1F4 Full-Load Current for Overload Relay #1 Overload Setting Step Default Relay Size Range 24.0A 36A45A 90AF8 Autoreset SAMMS-LVX Only F6 Service FactorF9 Phase Unbalance Protection F7 Overload Trip ClassF10 Display Time to Restart F12 Ground Fault Protection or WarningF11 Emergency Restarting F13 Set Programmable Timer #1 F12A Ground Fault Pickup CurrentF14 Set Programmable Timer #2 F15 Display CurrentF17 Current Unbalance F21 Reset Motor DataF18 Display Total Elapsed Run Time of the Motor F19 Number of Motor StartsF23A Jam Pickup Current SAMMS-LVX Only F25 Percentage of Motor Winding TemperatureF24 Loss of Load Protection or Warning SAMMS-LVX Only F24A Loss of Load Pickup Current SAMMS-LVX OnlyF27 Address Troubleshooting Error Condition Troubleshooting Guide Error Condition Appendix a Technical Specifications Overload Specifications Statistical Data Dimensions Catalog Number SAM4 Switch # Function Position Samms Sensor, sizes 1C, 2A, 2B Page Siemens Energy Automation, Inc