Page 34

3 Operating the SAMMS-LV Device

F4 - Full-Load Current for Overload Relay #1

1.Press the LIST key to view the active full-load current setting for overload relay #1. The setting should normally be the full load current as shown on the motor nameplate (high speed for two-speed machine). The range of possible settings and the factory default value depend on the size displayed in F2 as follows:

Overload

Setting

Step

Default

Relay Size

Range

 

 

 

 

 

 

 

1A

0.3

- 1.5A

0.1A

0.3A

 

 

 

 

 

1B

1.2

- 6.0A

0.1A

1.2A

 

 

 

 

 

1C

4.8

- 24.0A

0.1A

4.8A

 

 

 

 

 

2A

10

- 36A

1A

10A

 

 

 

 

 

2B

10

- 45A

1A

10A

 

 

 

 

 

3

20

- 90A

1A

20A

 

 

 

 

 

4

40

- 135A

1A

40A

 

 

 

 

 

5

80

- 270A

1A

80A

 

 

 

 

 

6

160

- 540A

2A

160A

2.To change the setting, you must be in program mode.

3.Press the UP or DOWN key to scroll through the range of settings until the selected setting appears.

4.Press the ENTER key to change the active setting to the selected value. The display becomes blank while you hold down the ENTER key, and the SAMMS-LV device stores the new setting. (If you make an incorrect selection, repeat steps 3 and 4).

5.To exit the program mode, press and hold the (F)unction key for several seconds. The display will show“Prog.” Press the UP or DOWN key to change to the display mode.

6.Press the (F)unction key to step through to another function.

F4A - 5A CT Primary Current Selection for Overload Relay #1

SAMMS-LV is normally used with SAMMS sensors to provide the current input signals to the device. Optionally, SAMMS-LV may be used with conventional 5A secondary current trans- formers.

1.Press the LIST key to view the sensor in use for overload relay #1. If standard SAMMS sensors are used, the display will read “OFF.” If 5A secondary CT’s are in use, the CT primary current will be displayed.

2.To change the setting, you must be in program mode.

3.Press the UP or DOWN key to scroll through the range of settings, until the selected setting appears on the display.

4.Press the ENTER key to change the active setting to the selected setting. The display becomes blank while you hold

down the ENTER key and the SAMMS-LV device stores the new setting.

5.To exit the program mode, press and hold the (F)unction key for several seconds. The display will show“Prog.” Press the UP or DOWN key to change to the display mode.

6.Press the (F)unction key to step through to another function.

F5 - Full-Load Current for Overload Relay #2 (SAMMS-LVX Only)

1.Press the LIST key to view the active full-load current setting for overload relay #2. This setting should normally be the full load current for the low speed shown on the motor name- plate. The range of possible settings and the factory default value depend on the size displayed in F3. The values are similar to those found in the table in the procedure for F4. If the control is not a two-speed control, OFF appears on the display, and UP, DOWN and ENTER keys become disabled.

2.To change the setting, you must be in program mode.

3.Press the UP or DOWN key to scroll through the range of settings until the selected setting appears.

4.Press the ENTER key to change the active setting to the selected value. The display becomes blank while you hold down the ENTER key, and the SAMMS-LVX device stores the new setting. (If you make an incorrect selection, repeat steps 3 and 4).

5.To exit the program mode, press and hold the (F)unction key for several seconds. The display will show“Prog.” Press the UP or DOWN key to change to the display mode.

6.Press the (F)unction key to step through to another function.

F5A - 5A CT Primary Current Selection for Overload Relay #2 (SAMMS-LVX Only)

SAMMS-LV is normally used with SAMMS sensors to provide the current input signals to the device. Optionally, SAMMS-LV may be used with conventional 5A secondary current trans- formers.

1.Press the LIST key to view the sensor in use for overload relay #2. If standard SAMMS sensors are used, the display will read “OFF.” If 5A secondary CT’s are in use, the CT primary current will be displayed.

2.To change the setting, you must be in program mode.

3.Press the UP or DOWN key to scroll through the range of settings, until the selected setting appears on the display.

4.Press the ENTER key to change the active setting to the selected setting. The display becomes blank while you hold down the ENTER key and the SAMMS-LVX device stores the new setting.

5.To exit the program mode, press and hold the (F)unction key for several seconds. The display will show“Prog.” Press the UP or DOWN key to change to the display mode.

32

Image 34
Contents SAMMS-LV Qualified Person Contents Field Service Operation Signal WordsQualified Person About this Manual SAMMS-LV Device Models Advanced Protection for Low-Voltage MotorsOverload Protection Using the Standardized Control PanelProgramming Control Circuits Outputs One Change settings requires password Yes Remote inputsSAMMS-LV Model Light barsInstalling the SAMMS-LV Device Full voltage non-reversing connection diagram Grounding the Device SAMMS-LV device communications connections Performing a Lamp Test Password ProtectionUsing the Reset/Test Push Button Performing an Overload Relay TestOutput Devices Input DevicesLadder Diagrams Library of Standard Ladder Diagrams Custom Ladder DiagramsSAMMS-LVX Standard control circuits RVA Incomplete Sequence Ridethrough Upon Loss of Power SAMMS-LVX OnlyMotor Ambient Temperature Intelligent Reduced-Voltage Starting SAMMS-LVX OnlyODP motor thermal signature Operating the SAMMS-LV Operating the SAMMS-LV Device 10 Motor protection graph Dual Overload Protection SAMMS-LVX Only Ultimate Trip Level and Service FactorPhase Unbalance Jam Protection SAMMS-LVX OnlyRepetitive Starts Ground Fault DetectionStator Protection Start InhibitSize Pickup Current Default Pickup Range Autoreset After a Trip SAMMS-LVX OnlyUsing the Hand Held Communicator HHC Emergency Restarting5A CT primary current if used Full load current for OLR No Function NumberJam pickup current F24 Loss of load protection or warning List Key Using the Enter KeyFunction Key UP and Down KeysExternal trips Enable/disable phase unbalance CapabilityMeans warning Select ground fault pick-up current Value 2A-5AStep Size Second Default Value Iflc is the value of Iflc forSelect jam pickup current 120-400% I FLC F24 Loss of Load Using the SAMMS-LV Device Func TionsProgram Mode/Passwords 200% 50% 480013 Entering and changing passwords F1 Control Circuit Number and Incomplete Se- quence Status F0 Ambient TemperatureSAMMS-LV Functions F2 Size for Overload Relay #145A Overload Setting Step Default Relay Size Range 24.0A 36AF4 Full-Load Current for Overload Relay #1 90AF9 Phase Unbalance Protection F6 Service FactorF8 Autoreset SAMMS-LVX Only F7 Overload Trip ClassF10 Display Time to Restart F12 Ground Fault Protection or WarningF11 Emergency Restarting F14 Set Programmable Timer #2 F12A Ground Fault Pickup CurrentF13 Set Programmable Timer #1 F15 Display CurrentF18 Display Total Elapsed Run Time of the Motor F21 Reset Motor DataF17 Current Unbalance F19 Number of Motor StartsF24 Loss of Load Protection or Warning SAMMS-LVX Only F25 Percentage of Motor Winding TemperatureF23A Jam Pickup Current SAMMS-LVX Only F24A Loss of Load Pickup Current SAMMS-LVX OnlyF27 Address Troubleshooting Error Condition Troubleshooting Guide Error Condition Appendix a Technical Specifications Overload Specifications Statistical Data Dimensions Catalog Number SAM4 Switch # Function Position Samms Sensor, sizes 1C, 2A, 2B Page Siemens Energy Automation, Inc