Siemens MCC-3298 user manual Error Condition

Page 42

4 Troubleshooting

Error Condition

Incomplete

Sequence

External Trip

CPU Fault

Troubleshooting Guide

Main Cause

 

Remedy

Indicates the SAMMS-LV unit does not

1. If the unit trips one second after start, verify that

detect current one second after a start

 

current transformer secondary input is present in the

command, or it detects current one

 

range of 100 mVAC to 3.54 VAC at terminals 1, 2,

second after a stop command.

 

and 3 with reference to 4. Verify that the coil voltage

 

 

is 115 VAC at terminals 14, 15, or 16 with reference

 

 

to 13 when the motor is started. Verify 115 VAC at

 

 

terminal 7 with reference to 13. Correct conditions if

 

 

necessary. Call Siemens if unit continues to trip.

 

2. If the unit trips one second after a stop command,

 

 

verify the contactor is open. Repair or replace the

 

 

contactor if it is not functioning properly.

 

3. Verify operation of mechanical interlock, and replace

 

 

or adjust.

 

4. Verify absence of voltage at terminals 1, 2, and 3 with

 

 

reference to 4, and at terminals 14, 15, or 16 with

 

 

reference to 13. If voltage is present, define the

 

 

source and reconnect so that the motor current only

 

 

passes through the current transformer.

 

5. To disable incomplete sequence, select F1 on the

 

 

HHC, press the ENTER key for one or more seconds

 

 

and start the motor. The incomplete sequence will

 

 

remain disabled until the above procedure is

 

 

repeated.

If the external trip LED is solidly

1. Jam conditions such as a blocked conveyor belt or

illuminated and the motor is stopped, it

 

gear train cause a sudden increase in motor current,

indicates a jam or loss of load

 

which can damage the motor’s insulation in a short

condition.

 

period of time.

 

2. Loss of load conditions, such as a broken blade of an

 

 

impeller or loss of back pressure of a pump, result in

 

 

a sudden decrease in motor current.

 

3. F16 on the HHC displays the external trip current at

 

 

the time of the trip.

 

 

In any case, determine the reason for the external trip

 

 

and correct the problem before restarting the motor.

 

 

If the external trip LED flashes and the motor

 

 

continues to run, it indicates loss of load warning or

 

 

process current warning.

Indicates a problem in the

 

Verify voltage between terminals 5 and 6 is more than

microprocessor or a low voltage

 

10 VAC. If fault persists, call Siemens.

condition.

 

 

 

 

 

40

Image 42
Contents SAMMS-LV Qualified Person Contents Signal Words Field Service OperationQualified Person About this Manual SAMMS-LV Device Models Advanced Protection for Low-Voltage MotorsUsing the Standardized Control Panel Overload ProtectionProgramming Control Circuits Outputs One Change settings requires password Yes Remote inputsSAMMS-LV Model Light barsInstalling the SAMMS-LV Device Full voltage non-reversing connection diagram Grounding the Device SAMMS-LV device communications connections Performing a Lamp Test Password ProtectionUsing the Reset/Test Push Button Performing an Overload Relay TestOutput Devices Input DevicesLadder Diagrams Library of Standard Ladder Diagrams Custom Ladder DiagramsSAMMS-LVX Standard control circuits RVA Incomplete Sequence Ridethrough Upon Loss of Power SAMMS-LVX OnlyMotor Ambient Temperature Intelligent Reduced-Voltage Starting SAMMS-LVX OnlyODP motor thermal signature Operating the SAMMS-LV Operating the SAMMS-LV Device 10 Motor protection graph Dual Overload Protection SAMMS-LVX Only Ultimate Trip Level and Service FactorPhase Unbalance Jam Protection SAMMS-LVX OnlyRepetitive Starts Ground Fault DetectionStator Protection Start InhibitSize Pickup Current Default Pickup Range Autoreset After a Trip SAMMS-LVX OnlyUsing the Hand Held Communicator HHC Emergency RestartingFunction Number 5A CT primary current if used Full load current for OLR NoJam pickup current F24 Loss of load protection or warning List Key Using the Enter KeyFunction Key UP and Down KeysExternal trips Enable/disable phase unbalance CapabilityMeans warning Select ground fault pick-up current Value 2A-5AStep Size Second Default Value Iflc is the value of Iflc forSelect jam pickup current 120-400% I FLC F24 Loss of Load Using the SAMMS-LV Device Func TionsProgram Mode/Passwords 200% 50% 480013 Entering and changing passwords F1 Control Circuit Number and Incomplete Se- quence Status F0 Ambient TemperatureSAMMS-LV Functions F2 Size for Overload Relay #145A Overload Setting Step Default Relay Size Range 24.0A 36AF4 Full-Load Current for Overload Relay #1 90AF9 Phase Unbalance Protection F6 Service FactorF8 Autoreset SAMMS-LVX Only F7 Overload Trip ClassF12 Ground Fault Protection or Warning F10 Display Time to RestartF11 Emergency Restarting F14 Set Programmable Timer #2 F12A Ground Fault Pickup CurrentF13 Set Programmable Timer #1 F15 Display CurrentF18 Display Total Elapsed Run Time of the Motor F21 Reset Motor DataF17 Current Unbalance F19 Number of Motor StartsF24 Loss of Load Protection or Warning SAMMS-LVX Only F25 Percentage of Motor Winding TemperatureF23A Jam Pickup Current SAMMS-LVX Only F24A Loss of Load Pickup Current SAMMS-LVX OnlyF27 Address Troubleshooting Error Condition Troubleshooting Guide Error Condition Appendix a Technical Specifications Overload Specifications Statistical Data Dimensions Catalog Number SAM4 Switch # Function Position Samms Sensor, sizes 1C, 2A, 2B Page Siemens Energy Automation, Inc