4 Troubleshooting
Troubleshooting Guide
Error Condition
Ground Fault
Main Cause
Indicates the ground fault current exceeded the threshold. If ground fault protection was selected, the ground fault LED illuminates solidly and the motor stops. If ground fault warning was selected, the ground fault LED flashes and the motor continues to run.
Remedy
The cause of the ground fault should be determined and removed before using the motor again. F16 on the HHC displays the ground fault trip current.
Ready Light not Illuminated
Improper Remote Operation
Improper Alarm Contact Operation
Improper Light
Operation
Improper Local Operation
Improper Contactor Operation
Cannot Change HHC Settings
Improper
SAMMS-LV
Operation
Usually indicates lack of control power. | 1. | Verify the presence of 12 VAC between terminals 5 |
|
| and 6 of the |
| 2. | If control power is not present, check the control |
|
| power fuses or the control power transformer and |
|
| replace if defective. |
| 3. | If control power is present, push the RESET button to |
|
| test lights and unit. If the Ready light does not |
|
| illuminate, call Siemens. |
Indicates connection or operator error. | 1. | Verify the |
| 2. | Verify 115 VAC input at |
|
| 11, and 12 with reference to 13, and at terminal 7 |
|
| with reference to 13. |
| 3. | If remote operation is intermittent, verify connections |
|
| are made in a manner to avoid noise interference. |
|
| Refer to Section 2 of this manual for instructions. |
Indicates connection error. |
| Verify 115 VAC at terminals 7 and 8 with reference to |
|
| 13. |
Usually indicates programming error. | 1. | Perform lamp test by pressing RESET button. |
| 2. | Verify ladder diagram. |
Operator error. |
| Verify |
Connection error. |
| Verify 115 VAC at terminal 7 with reference to 13, |
|
| and at output terminals 14, 15, or 16 with reference |
|
| to 13 when the motor is started. |
Usually indicates motor is running, or | 1. | Verify that the motor is stopped before changing |
incorrect password. |
| parameters. |
| 2. | Verify that the correct password is in use. If the |
|
| password cannot be determined, call Siemens. |
Usually indicates improper grounding |
| Refer to Section 2 of this manual for instructions. |
or noise interference. |
|
|
|
|
|
41