Siemens MCC-3298 user manual Ultimate Trip Level and Service Factor, Phase Unbalance

Page 24

3 Operating the SAMMS-LV Device

of 10 guarantees that a current of 600% of IFLC will cause a trip in 10 seconds or less. In the SAMMS-LV, the protection curves are designed to cause a trip in 90% to 100% of the class time for a current of 600% of IFLC.

The lowest overload class, greater than or equal to the motor’s starting time, gives the best protection. Overload classes 2 through 23 are available in SAMMS-LV. The range of protection curves are shown in Figures 3.6 through 3.9.

Important: In the unlikely event that the motor acceleration time (overload class) exceeds the motor’s stall time, use a speed switch as an input source to open the contactor if the switch senses a locked rotor or stall condition.

Note: For clarity, the time-current characteristic curves in this manual are shown with overload classes 2, 5, 10, 15 and 23 only. Use interpolation to derive values of other overload classes not shown.

3.13 Ultimate Trip Level and Service Factor

The ultimate trip level is the maximum continuous current that does not cause an overload trip. Any higher current applied indefinitely to an unprotected motor will ultimately damage it. The ultimate trip level for motors with a unity service factor is 110% of the full-load current setting. For motors with a service factor of 1.15, the ultimate trip level is 120%. You can select a service factor of 1.00 or 1.15 with HHC function F6.

3.14 Phase Unbalance

Unbalanced three-phase voltages or loss of one phase can result in unbalanced currents being supplied to the motor. Unbalanced currents include negative-sequence components that produce heat in the motor winding, decreasing the effi- ciency of the motor for a given load. The SAMMS-LV device measures the magnitude of the current unbalance as the maximum deviation from the average of the three-phase cur- rents, divided by the average of the three-phase currents. In case of loss of a phase, the unbalance is 100% in a three-wire, ungrounded system.

With phase unbalance protection enabled, current unbalances of between 20% and 40% cause the Phase Unbalance LED to flash as a warning. If the unbalance increases to above 40%, the Phase Unbalance LED illuminates solidly and overload tripping accelerates. The effect of an unbalance of greater than 40% is to shift the motor protection curve in the direction of faster tripping.

You enable the phase unbalance protection using HHC function F9.

Enabled = ON

Disabled = OFF

With phase unbalance protection enabled, HHC function F17 displays the percentage of current unbalance. Both functions display OFF if phase unbalance protection is disabled.

3.15Dual Overload Protection (SAMMS-LVX Only)

Because the high-speed and low-speed currents differ in two- speed motors, different full-load current settings are often required. In such applications, use function F5 to select the full- load current for low-speed operation.

3.16 Jam Protection (SAMMS-LVX Only)

Certain mechanical loads, especially those containing gears, are susceptible to jamming. Jam protection can prevent dam- age to the motor and the driven equipment by quickly tripping the motor off-line in the event of a jam. If you have enabled jam protection, you may adjust the jam trip level from 120-400% of IFLC. The jam trip time is 360 msec. SAMMS-LVX is normally shipped with jam protection enabled, with a trip level of 200% IFLC (See Figure 3.11). Jam protection is locked out for 5 times the overload class after a start, speed, or direction change. If the jam limits are exceeded, the motor is tripped off-line and the External Trip LED on the front panel solidly illuminates. You can enable jam protection using HHC function F23.

enabled = ON

disabled = OFF

3.17Loss of Load Protection/Warning (SAMMS-LVX Only)

If the running current of the motor suddenly drops below 20 to 95% (adjustable) of its previous reading in 360 msec, a loss of load has occurred. Such a loss of load could be due to a broken belt or loss of back pressure in a pump. Loss of load detection is locked out for five times the overload class time after a start, direction, or speed change (See Figure 3.11). You can select loss of load protection or warning using HHC function F24.

protection = ON

warning = OFF

With protection selected, detection of a loss of load trips the motor off-line and illuminates the External Trip LED. With warning selected, the motor does not trip off-line and the External Trip LED flashes until the current returns to its former steady-state level or higher. SAMMS-LVX is normally shipped with loss of load protection OFF (WARNING only), and with default setting of 50% IFLC.

3.18Process Current Warning (SAMMS-LVX Only)

It is often convenient to have an indication that the load current is above its normal operating level so that the process can be checked and, if necessary, adjusted. You can set the process current warning from 0% (displayed as “OFF”) to 100% of the full-load current with HHC function F22. As long as the motor running current exceeds the process current warning level, the External Trip LED flashes. Process current warning is locked out for five times the class time after a start or a direction or speed change.

22

Image 24
Contents SAMMS-LV Qualified Person Contents Signal Words Field Service OperationQualified Person About this Manual SAMMS-LV Device Models Advanced Protection for Low-Voltage MotorsUsing the Standardized Control Panel Overload ProtectionProgramming Control Circuits Change settings requires password Yes Remote inputs SAMMS-LV ModelOutputs One Light barsInstalling the SAMMS-LV Device Full voltage non-reversing connection diagram Grounding the Device SAMMS-LV device communications connections Password Protection Using the Reset/Test Push ButtonPerforming a Lamp Test Performing an Overload Relay TestOutput Devices Input DevicesLadder Diagrams Library of Standard Ladder Diagrams Custom Ladder DiagramsSAMMS-LVX Standard control circuits RVA Ridethrough Upon Loss of Power SAMMS-LVX Only Motor Ambient TemperatureIncomplete Sequence Intelligent Reduced-Voltage Starting SAMMS-LVX OnlyODP motor thermal signature Operating the SAMMS-LV Operating the SAMMS-LV Device 10 Motor protection graph Ultimate Trip Level and Service Factor Phase UnbalanceDual Overload Protection SAMMS-LVX Only Jam Protection SAMMS-LVX OnlyGround Fault Detection Stator ProtectionRepetitive Starts Start InhibitAutoreset After a Trip SAMMS-LVX Only Using the Hand Held Communicator HHCSize Pickup Current Default Pickup Range Emergency RestartingFunction Number 5A CT primary current if used Full load current for OLR NoJam pickup current F24 Loss of load protection or warning Using the Enter Key Function KeyList Key UP and Down KeysExternal trips Enable/disable phase unbalance CapabilitySelect ground fault pick-up current Value 2A-5A Step Size Second Default ValueMeans warning Iflc is the value of Iflc forUsing the SAMMS-LV Device Func Tions Program Mode/PasswordsSelect jam pickup current 120-400% I FLC F24 Loss of Load 200% 50% 480013 Entering and changing passwords F0 Ambient Temperature SAMMS-LV FunctionsF1 Control Circuit Number and Incomplete Se- quence Status F2 Size for Overload Relay #1Overload Setting Step Default Relay Size Range 24.0A 36A F4 Full-Load Current for Overload Relay #145A 90AF6 Service Factor F8 Autoreset SAMMS-LVX OnlyF9 Phase Unbalance Protection F7 Overload Trip ClassF12 Ground Fault Protection or Warning F10 Display Time to RestartF11 Emergency Restarting F12A Ground Fault Pickup Current F13 Set Programmable Timer #1F14 Set Programmable Timer #2 F15 Display CurrentF21 Reset Motor Data F17 Current UnbalanceF18 Display Total Elapsed Run Time of the Motor F19 Number of Motor StartsF25 Percentage of Motor Winding Temperature F23A Jam Pickup Current SAMMS-LVX OnlyF24 Loss of Load Protection or Warning SAMMS-LVX Only F24A Loss of Load Pickup Current SAMMS-LVX OnlyF27 Address Troubleshooting Error Condition Troubleshooting Guide Error Condition Appendix a Technical Specifications Overload Specifications Statistical Data Dimensions Catalog Number SAM4 Switch # Function Position Samms Sensor, sizes 1C, 2A, 2B Page Siemens Energy Automation, Inc