Siemens MCC-3298 user manual External trips Enable/disable phase unbalance, Capability

Page 29

3 Operating the SAMMS-LV Device

Function

Function Description

Range

Step Size

Number

 

 

 

 

F0

Select ambient temperature.

0 - 70º C

5º C

 

 

 

 

F1

Display (or change for SAMMS-LVE)

0 - 9999

1

 

the control circuit number,

 

 

 

 

Enable/disable incomplete sequence

 

 

 

 

status.

 

 

 

 

 

 

 

F2

Display the size for single-speed

1A, 1B, 1C, 2A, 2B, 3,

As shown

 

controller, or the high-speed size for

4, 5, 6

 

 

two-speed motor controllers.

 

 

 

 

 

 

 

F3

Display the low-speed size for

1A, 1B, 1C, 2A, 2B, 3,

As shown

 

two-speed controller. F3 is OFF for

4, 5, 6, OFF

 

 

single-speed motor controllers.

 

 

 

F4

Select the full-load current setting (IFLC )

1A:

0.3 - 1.5A

0.1A

 

for the size for single-speed motor

1B:

1.2 - 6A

0.1A

 

controller or the high-speed size for

1C:

4.8 - 24A

0.1A

 

two-speed motor controllers.

2A:

10 - 36A

1A

 

 

2B:

10 - 45A

1A

 

 

3:

20 - 90A

1A

 

 

4:

40 - 135A

1A

 

 

5:

80 - 270A

1A

 

 

6:

160 - 540A

2A

F4A

Display the primary current if 5A

Function of size in F2

Function of size in F2

 

secondary CT's are used.

 

 

 

 

 

 

 

 

F5

Select the full-load current setting (IFLC )

1A:

0.3 - 1.5A

0.1A

 

for the low-speed size for two-speed

1B:

1.2 - 6A

0.1A

 

motor controllers. F5 is OFF for single

1C:

4.8 - 24A

0.1A

 

speed motor controllers.

2A:

10 - 36A

1A

 

 

2B:

10 - 45A

1A

 

 

3:

20 - 90A

1A

 

 

4:

40 - 135A

1A

 

 

5:

80 - 270A

1A

 

 

6:

160 - 540A

2A

 

 

 

 

F5A

Display the primary current if 5A

Function of size in F3

Function of size in F3

 

secondary CT's are used.

 

 

 

 

 

 

 

F6

Select the service factor.

1 or 1.15

N/A

 

 

 

 

 

F7

Select the overload trip class.

2-23

 

1

 

 

 

 

F8

Enable/disable autoreset of overload

ON/OFF

N/A

 

and external trips.

 

 

 

 

 

 

 

F9

Enable/disable phase unbalance

ON/OFF

N/A

 

protection.

 

 

 

 

 

 

 

F10

Display the time to wait until the motor

Real Time Value

1s

 

can be restarted. Applies after an

 

 

 

 

overload trip with the winding or

 

 

 

 

housing temperature above the

 

 

 

 

maximum allowed for restarting.

 

 

 

F11

Enable/disable the emergency restart

ON/OFF

N/A

 

capability.

 

 

 

Table 3.8 Motor control and protection functions (page 1 of 3)

Default Value

40º C

N/A

N/A

N/A

0.3A

1.2A

4.8A

10A

10A

20A

40A

80A

160A

OFF (denotes SAMMS sensors in use)

0.3A

1.2A

4.8A

10A

10A

20A

40A

80A

160A

OFF (denotes SAMMS sensors in use)

1.15

10 OFF

ON

N/A

OFF

27

Image 29
Contents SAMMS-LV Qualified Person Contents Qualified Person Signal WordsField Service Operation About this Manual Advanced Protection for Low-Voltage Motors SAMMS-LV Device ModelsProgramming Control Circuits Using the Standardized Control PanelOverload Protection SAMMS-LV Model Change settings requires password Yes Remote inputsOutputs One Light barsInstalling the SAMMS-LV Device Full voltage non-reversing connection diagram Grounding the Device SAMMS-LV device communications connections Using the Reset/Test Push Button Password ProtectionPerforming a Lamp Test Performing an Overload Relay TestInput Devices Output DevicesCustom Ladder Diagrams Ladder Diagrams Library of Standard Ladder DiagramsSAMMS-LVX Standard control circuits RVA Motor Ambient Temperature Ridethrough Upon Loss of Power SAMMS-LVX OnlyIncomplete Sequence Intelligent Reduced-Voltage Starting SAMMS-LVX OnlyODP motor thermal signature Operating the SAMMS-LV Operating the SAMMS-LV Device 10 Motor protection graph Phase Unbalance Ultimate Trip Level and Service FactorDual Overload Protection SAMMS-LVX Only Jam Protection SAMMS-LVX OnlyStator Protection Ground Fault DetectionRepetitive Starts Start Inhibit Using the Hand Held Communicator HHC Autoreset After a Trip SAMMS-LVX Only Size Pickup Current Default Pickup Range Emergency RestartingJam pickup current F24 Loss of load protection or warning Function Number5A CT primary current if used Full load current for OLR No Function Key Using the Enter KeyList Key UP and Down KeysCapability External trips Enable/disable phase unbalanceStep Size Second Default Value Select ground fault pick-up current Value 2A-5AMeans warning Iflc is the value of Iflc forProgram Mode/Passwords Using the SAMMS-LV Device Func TionsSelect jam pickup current 120-400% I FLC F24 Loss of Load 200% 50% 480013 Entering and changing passwords SAMMS-LV Functions F0 Ambient TemperatureF1 Control Circuit Number and Incomplete Se- quence Status F2 Size for Overload Relay #1F4 Full-Load Current for Overload Relay #1 Overload Setting Step Default Relay Size Range 24.0A 36A45A 90AF8 Autoreset SAMMS-LVX Only F6 Service FactorF9 Phase Unbalance Protection F7 Overload Trip ClassF11 Emergency Restarting F12 Ground Fault Protection or WarningF10 Display Time to Restart F13 Set Programmable Timer #1 F12A Ground Fault Pickup CurrentF14 Set Programmable Timer #2 F15 Display CurrentF17 Current Unbalance F21 Reset Motor DataF18 Display Total Elapsed Run Time of the Motor F19 Number of Motor StartsF23A Jam Pickup Current SAMMS-LVX Only F25 Percentage of Motor Winding TemperatureF24 Loss of Load Protection or Warning SAMMS-LVX Only F24A Loss of Load Pickup Current SAMMS-LVX OnlyF27 Address Troubleshooting Error Condition Troubleshooting Guide Error Condition Appendix a Technical Specifications Overload Specifications Statistical Data Dimensions Catalog Number SAM4 Switch # Function Position Samms Sensor, sizes 1C, 2A, 2B Page Siemens Energy Automation, Inc