Siemens MCC-3298 F17 Current Unbalance, F18 Display Total Elapsed Run Time of the Motor

Page 38

3 Operating the SAMMS-LV Device

F17 - Current Unbalance

1.Press the LIST key to view the percentage current unbal- ance. When unbalance protection is disabled (F9 = OFF), OFF is displayed. The percentage unbalance is the ratio of the greatest deviation of the three phase currents from their average to the average of the three phase currents ex- pressed as a percentage.

2.The UP, DOWN, and ENTER keys are disabled for this function.

3.Press the (F)unction key to go to other functions.

F18 - Display Total Elapsed Run Time of the Motor

1.Press the LIST key to view the total elapsed running time of the motor. The run time is displayed in tens of hours as follows:

Actual Number of Hours

Displayed Time

 

 

0

0.0

 

 

9999

999.9

 

 

10000

1000

 

 

65535

6553

 

 

65536

0.0 (roll over)

 

 

The displayed value does not increment until a full hour, or for elapsed times greater than 10000 hours a full ten hours, have elapsed. Internally, however, the elapsed time is maintained to the nearest 0.1 second.

Note: The value can be reset to zero with F21.

2.The UP, DOWN, and ENTER keys are disabled for this function.

3.Press the (F)unction key to go to other functions.

F19 - Number of Motor Starts

1.Press the LIST key to view the number of motor starts. The number of starts is displayed in tens of starts as follows:

Actual Number of Starts

Displayed Number

 

 

0

0.0

 

 

9999

999.9

 

 

10000

1000

 

 

65535

6553

 

 

65536

0.0 (roll over)

 

 

Note: The value can be reset to zero with F21.

2.The UP, DOWN, and ENTER keys are disabled for this function.

3.Press the (F)unction key to go to other functions.

36

F20 - Number of Overload Trips

1.Press the LIST key to view the number of overload trips, up to 9999.

Note: The value can be reset to zero with F21.

2.The UP, DOWN, and ENTER keys are disabled for this function.

3.Press the (F)unction key to go to other functions.

F21 - Reset Motor Data

1.To reset to zero the elapsed running time, the number of starts, and the number of overload trips, press the LIST key. “CLr” is displayed.

2.Press the ENTER key. “SUrE” is displayed.

3.Press the ENTER key again to zero the motor data.

4.To return to Step 1, press the LIST key at any time.

5.The UP and DOWN keys are disabled for this function.

6.Press the (F)unction key to go to other functions.

F22 - Process Current Warning Level (SAMMS-LVX Only)

1.Press the LIST key to view the active process current level. The value represents the percentage of the full load current setting above which a motor current causes the External Trip LED to flash. The function is disabled for five times the class time after starting, or after a speed or direction change. The range of settings is in 1% increments from zero (OFF) through 100. The factory default is OFF.

2.To change the setting, you must be in program mode.

3.To change the setting, press the UP or DOWN key until the desired setting is displayed then press the ENTER key to select the setting. The display blanks while the ENTER key is pressed.

3. Return to Step 3 if you select an incorrect setting.

5.To exit the program mode, press and hold the (F)unction key for several seconds. The display will show“Prog.” Press the UP or DOWN key to change to the display mode.

6.Press the (F)unction key to go to other functions.

F23 Jam Protection (SAMMS-LVX Only)

1.Press the LIST key to view the active jam protection setting (ON or OFF). The factory default setting is ON. If jam protection is enabled (ON) and the motor running current increases to the pickup current value within 360 msec, the motor will trip off-line and the External Trip LED is steadily lit. The function is disabled for five times the class time after starting, or after a speed or direction change.

2.To change the setting, you must be in program mode.

Image 38
Contents SAMMS-LV Qualified Person Contents Qualified Person Signal WordsField Service Operation About this Manual SAMMS-LV Device Models Advanced Protection for Low-Voltage MotorsProgramming Control Circuits Using the Standardized Control PanelOverload Protection Outputs One Change settings requires password Yes Remote inputsSAMMS-LV Model Light barsInstalling the SAMMS-LV Device Full voltage non-reversing connection diagram Grounding the Device SAMMS-LV device communications connections Performing a Lamp Test Password ProtectionUsing the Reset/Test Push Button Performing an Overload Relay TestOutput Devices Input DevicesLadder Diagrams Library of Standard Ladder Diagrams Custom Ladder DiagramsSAMMS-LVX Standard control circuits RVA Incomplete Sequence Ridethrough Upon Loss of Power SAMMS-LVX OnlyMotor Ambient Temperature Intelligent Reduced-Voltage Starting SAMMS-LVX OnlyODP motor thermal signature Operating the SAMMS-LV Operating the SAMMS-LV Device 10 Motor protection graph Dual Overload Protection SAMMS-LVX Only Ultimate Trip Level and Service FactorPhase Unbalance Jam Protection SAMMS-LVX OnlyRepetitive Starts Ground Fault DetectionStator Protection Start InhibitSize Pickup Current Default Pickup Range Autoreset After a Trip SAMMS-LVX OnlyUsing the Hand Held Communicator HHC Emergency RestartingJam pickup current F24 Loss of load protection or warning Function Number5A CT primary current if used Full load current for OLR No List Key Using the Enter KeyFunction Key UP and Down KeysExternal trips Enable/disable phase unbalance CapabilityMeans warning Select ground fault pick-up current Value 2A-5AStep Size Second Default Value Iflc is the value of Iflc forSelect jam pickup current 120-400% I FLC F24 Loss of Load Using the SAMMS-LV Device Func TionsProgram Mode/Passwords 200% 50% 480013 Entering and changing passwords F1 Control Circuit Number and Incomplete Se- quence Status F0 Ambient TemperatureSAMMS-LV Functions F2 Size for Overload Relay #145A Overload Setting Step Default Relay Size Range 24.0A 36AF4 Full-Load Current for Overload Relay #1 90AF9 Phase Unbalance Protection F6 Service FactorF8 Autoreset SAMMS-LVX Only F7 Overload Trip ClassF11 Emergency Restarting F12 Ground Fault Protection or WarningF10 Display Time to Restart F14 Set Programmable Timer #2 F12A Ground Fault Pickup CurrentF13 Set Programmable Timer #1 F15 Display CurrentF18 Display Total Elapsed Run Time of the Motor F21 Reset Motor DataF17 Current Unbalance F19 Number of Motor StartsF24 Loss of Load Protection or Warning SAMMS-LVX Only F25 Percentage of Motor Winding TemperatureF23A Jam Pickup Current SAMMS-LVX Only F24A Loss of Load Pickup Current SAMMS-LVX OnlyF27 Address Troubleshooting Error Condition Troubleshooting Guide Error Condition Appendix a Technical Specifications Overload Specifications Statistical Data Dimensions Catalog Number SAM4 Switch # Function Position Samms Sensor, sizes 1C, 2A, 2B Page Siemens Energy Automation, Inc