Siemens MCC-3298 F6 Service Factor, F7 Overload Trip Class, F8 Autoreset SAMMS-LVX Only

Page 35

3 Operating the SAMMS-LV Device

6. Press the (F)unction key to step through to another function.

F6 - Service Factor

1.Press the LIST key to view the active service factor, 1.0 or 1.15. The factory default is 1.15. A service factor of 1.15 adjusts the overload trip thresholds up by 15% over their values for a service factor of 1.0. This results in more margin before tripping.

2.To change the setting, you must be in program mode.

3.To change the setting, press the UP or DOWN key to alternate between the two choices until the selected value is displayed.

4.Press the ENTER key to change the active setting to the selected value. The display becomes blank while you hold down the ENTER key, and the SAMMS-LV device stores the new setting. (If you make an incorrect selection, repeat steps 3 and 4.)

5.To exit the program mode, press and hold the (F)unction key for several seconds. The display will show“Prog.” Press the UP or DOWN key to change to the display mode.

6.Press the (F)unction key to step through to another function.

F7 - Overload Trip Class

The trip class is the time in seconds that it takes the overload relay to trip for a starting current of 600% of the full-load current setting. The range of possible values is 2-23.

1.Press the LIST key to view the active trip class.

2.To change the setting, you must be in program mode.

3.To change the setting, press the UP or DOWN key to scroll through the range of settings until the selected setting appears.

4.Press the ENTER key to change the active setting to the selected value. The display becomes blank while you hold down the ENTER key, and the SAMMS-LV device stores the new setting. (If you make an incorrect selection, repeat steps 3 and 4.)

5.To exit the program mode, press and hold the (F)unction key for several seconds. The display will show “Prog.”Press the UP or DOWN key to change to the display mode.

6.Press the (F)unction key to step through to another function.

F8 - Autoreset (SAMMS-LVX Only)

1.Press the LIST key to view the active autoreset setting, either ON or OFF. If autoreset is ON, the SAMMS-LV device automatically resets 30 seconds after an overload or exter- nal trip. At this time the motor can start. If autoreset is OFF, you must manually reset the overload relay with the Reset/ Test button before restarting the motor. The factory default is OFF.

2.To change the setting, you must be in program mode.

3.To change the setting, press the UP or DOWN key to select the new setting.

4.Press and hold the ENTER key. If the displayed setting is ON, go to step 6. If the displayed setting is OFF go to step 5.

5.Release the ENTER key while the display appears blank. When you release the key, the setting changes to OFF. Go to step 6.

6.Release the ENTER key. “SUrE” appears on the display.

7.Press the ENTER key to make the change to ON.

Note: The reason for displaying “SUrE” and requiring you to press the ENTER key a second time is because the motor can restart immediately after an overload trip if autoreset is ON.

8.If you made an incorrect selection, repeat steps 3 through 7.

9.To exit the program mode, press and hold the (F)unction key for several seconds. The display will show“Prog.” Press the UP or DOWN key to change to the display mode.

10.Press the (F)unction key to step through other functions.

F9 - Phase Unbalance Protection

1.Press the LIST key to view the active phase unbalance protection setting (ON or OFF). The factory default setting is ON.

a.When phase unbalance protection is enabled (ON), cur- rent unbalances of greater than 40% accelerate overload tripping. The Phase Unbalance LED flashes for unbal- ances between 20% and 40%. It remains steadily illumi- nated for unbalances greater than 40%.

33

Image 35
Contents SAMMS-LV Qualified Person Contents Qualified Person Signal WordsField Service Operation About this Manual Advanced Protection for Low-Voltage Motors SAMMS-LV Device ModelsProgramming Control Circuits Using the Standardized Control PanelOverload Protection Light bars Change settings requires password Yes Remote inputsSAMMS-LV Model Outputs OneInstalling the SAMMS-LV Device Full voltage non-reversing connection diagram Grounding the Device SAMMS-LV device communications connections Performing an Overload Relay Test Password ProtectionUsing the Reset/Test Push Button Performing a Lamp TestInput Devices Output DevicesCustom Ladder Diagrams Ladder Diagrams Library of Standard Ladder DiagramsSAMMS-LVX Standard control circuits RVA Intelligent Reduced-Voltage Starting SAMMS-LVX Only Ridethrough Upon Loss of Power SAMMS-LVX OnlyMotor Ambient Temperature Incomplete SequenceODP motor thermal signature Operating the SAMMS-LV Operating the SAMMS-LV Device 10 Motor protection graph Jam Protection SAMMS-LVX Only Ultimate Trip Level and Service FactorPhase Unbalance Dual Overload Protection SAMMS-LVX OnlyStart Inhibit Ground Fault DetectionStator Protection Repetitive StartsEmergency Restarting Autoreset After a Trip SAMMS-LVX OnlyUsing the Hand Held Communicator HHC Size Pickup Current Default Pickup RangeJam pickup current F24 Loss of load protection or warning Function Number5A CT primary current if used Full load current for OLR No UP and Down Keys Using the Enter KeyFunction Key List KeyCapability External trips Enable/disable phase unbalanceIflc is the value of Iflc for Select ground fault pick-up current Value 2A-5AStep Size Second Default Value Means warning200% 50% 4800 Using the SAMMS-LV Device Func TionsProgram Mode/Passwords Select jam pickup current 120-400% I FLC F24 Loss of Load13 Entering and changing passwords F2 Size for Overload Relay #1 F0 Ambient TemperatureSAMMS-LV Functions F1 Control Circuit Number and Incomplete Se- quence Status90A Overload Setting Step Default Relay Size Range 24.0A 36AF4 Full-Load Current for Overload Relay #1 45AF7 Overload Trip Class F6 Service FactorF8 Autoreset SAMMS-LVX Only F9 Phase Unbalance ProtectionF11 Emergency Restarting F12 Ground Fault Protection or WarningF10 Display Time to Restart F15 Display Current F12A Ground Fault Pickup CurrentF13 Set Programmable Timer #1 F14 Set Programmable Timer #2F19 Number of Motor Starts F21 Reset Motor DataF17 Current Unbalance F18 Display Total Elapsed Run Time of the MotorF24A Loss of Load Pickup Current SAMMS-LVX Only F25 Percentage of Motor Winding TemperatureF23A Jam Pickup Current SAMMS-LVX Only F24 Loss of Load Protection or Warning SAMMS-LVX OnlyF27 Address Troubleshooting Error Condition Troubleshooting Guide Error Condition Appendix a Technical Specifications Overload Specifications Statistical Data Dimensions Catalog Number SAM4 Switch # Function Position Samms Sensor, sizes 1C, 2A, 2B Page Siemens Energy Automation, Inc