Page 28

3 Operating the SAMMS-LV Device

3.27.1 The (F)unction Key

When you press the (F)unction key, the function mode is selected and the HHC displays the number of the selected function preceded by F. With the HHC in the function mode, use the UP and DOWN keys to step from one function to the next.

3.27.2 The LIST Key

When you press the LIST key, the display mode is selected and the HHC displays the value corresponding to the selected function. If the selected function is a set point, the HHC displays the actual setting. If the selected function is a measured quantity, the HHC displays the value of the measured quantity.

In the display mode, use the UP and DOWN keys to step through the range of possible set points for the selected function. Pressing the LIST key returns the active setting to the display.

There is one occasion when the LIST key is disabled making the corresponding functions inoperative. In a SAMMS-LV device with autoreset disabled at the factory, the LIST key has no effect for F8.

3.27.3 UP and DOWN Keys

Use the UP and DOWN keys to step through the functions while the HHC is in the function mode. When the HHC is in the display mode, use the UP and DOWN keys to step through the values for a selected function. You can use the keys in three ways:

1.Single step - press the key and release it.

2.Slow scroll - press the key and hold the key down for no longer than two or three seconds.

3.Fast scroll - press the key and hold the key down long enough for the HHC to step through more than five steps.

The following information discusses how to operate the UP and DOWN keys in the function and display modes.

1.In the function mode, the UP key increases the function number by one and the DOWN key decreases the function number by one. If F0 appears on the display, pressing the DOWN key rolls the function over to the highest-numbered function, F27. If the highest-numbered function (F27) ap- pears in the display, pressing the UP key rolls the function over to the lowest-numbered function (F0).

2.In the display mode, use the UP and DOWN keys to step through the range of settings for each set point function. You also use the UP and DOWN keys to step through the individual line currents and the average line current of F15. Just as the UP and DOWN keys cause the function numbers to roll over, they also cause the range of settings to roll over.

3.27.4 Using the ENTER Key

Use the ENTER key to change settings on the HHC display. The SAMMS-LV device disables the ENTER key under the following conditions:

1.The ENTER key is disabled while the device is in the function mode.

2.The ENTER key is disabled for non-setting functions that display a parameter.

3.The ENTER key is disabled while the motor is running to prevent settings from being changed while the motor is running.

Use the following procedure to change a setting. This example shows you how to change the full-load current setting from 112A to 67A.

1.With the HHC in the program mode (see section 3.28.1), press the (F)unction key. The display shows the number of the function most recently selected, (e.g. F9).

2.Use the UP or DOWN key (as described above) to step or scroll to the desired function. The display shows the desired function, (e.g. F4).

3.Press the LIST key. The display shows the active setting for the selected function, (e.g. 112, representing a full-load current setting of 112A for a motor controlled by a size 4 contactor.)

4.Use the UP or DOWN key (as described above) to step or scroll to the desired setting. The display shows the desired setting, (e.g. 67 for 67A).

5.To enter the desired setting (67) which is displayed, press the ENTER key. The display becomes blank while you hold down the ENTER key and the SAMMS-LV device stores the new setting.

6.Press the LIST key to show the new setting (67) on the display.

7.To move to the other functions, press the (F)unction key. The display shows, in the example, F4.

8.Press the UP and DOWN keys to step through the function numbers. The SAMMS-LV device is in the function mode.

9.To exit the program mode, press and hold the (F)unction key for several seconds. The display will show“Prog.” Press the UP or DOWN key to change to display mode.

26

Image 28
Contents SAMMS-LV Qualified Person Contents Field Service Operation Signal WordsQualified Person About this Manual SAMMS-LV Device Models Advanced Protection for Low-Voltage MotorsOverload Protection Using the Standardized Control PanelProgramming Control Circuits Change settings requires password Yes Remote inputs SAMMS-LV ModelOutputs One Light barsInstalling the SAMMS-LV Device Full voltage non-reversing connection diagram Grounding the Device SAMMS-LV device communications connections Password Protection Using the Reset/Test Push ButtonPerforming a Lamp Test Performing an Overload Relay TestOutput Devices Input DevicesLadder Diagrams Library of Standard Ladder Diagrams Custom Ladder DiagramsSAMMS-LVX Standard control circuits RVA Ridethrough Upon Loss of Power SAMMS-LVX Only Motor Ambient TemperatureIncomplete Sequence Intelligent Reduced-Voltage Starting SAMMS-LVX OnlyODP motor thermal signature Operating the SAMMS-LV Operating the SAMMS-LV Device 10 Motor protection graph Ultimate Trip Level and Service Factor Phase UnbalanceDual Overload Protection SAMMS-LVX Only Jam Protection SAMMS-LVX OnlyGround Fault Detection Stator ProtectionRepetitive Starts Start InhibitAutoreset After a Trip SAMMS-LVX Only Using the Hand Held Communicator HHCSize Pickup Current Default Pickup Range Emergency Restarting5A CT primary current if used Full load current for OLR No Function NumberJam pickup current F24 Loss of load protection or warning Using the Enter Key Function KeyList Key UP and Down KeysExternal trips Enable/disable phase unbalance CapabilitySelect ground fault pick-up current Value 2A-5A Step Size Second Default ValueMeans warning Iflc is the value of Iflc forUsing the SAMMS-LV Device Func Tions Program Mode/PasswordsSelect jam pickup current 120-400% I FLC F24 Loss of Load 200% 50% 480013 Entering and changing passwords F0 Ambient Temperature SAMMS-LV FunctionsF1 Control Circuit Number and Incomplete Se- quence Status F2 Size for Overload Relay #1Overload Setting Step Default Relay Size Range 24.0A 36A F4 Full-Load Current for Overload Relay #145A 90AF6 Service Factor F8 Autoreset SAMMS-LVX OnlyF9 Phase Unbalance Protection F7 Overload Trip ClassF10 Display Time to Restart F12 Ground Fault Protection or WarningF11 Emergency Restarting F12A Ground Fault Pickup Current F13 Set Programmable Timer #1F14 Set Programmable Timer #2 F15 Display CurrentF21 Reset Motor Data F17 Current UnbalanceF18 Display Total Elapsed Run Time of the Motor F19 Number of Motor StartsF25 Percentage of Motor Winding Temperature F23A Jam Pickup Current SAMMS-LVX OnlyF24 Loss of Load Protection or Warning SAMMS-LVX Only F24A Loss of Load Pickup Current SAMMS-LVX OnlyF27 Address Troubleshooting Error Condition Troubleshooting Guide Error Condition Appendix a Technical Specifications Overload Specifications Statistical Data Dimensions Catalog Number SAM4 Switch # Function Position Samms Sensor, sizes 1C, 2A, 2B Page Siemens Energy Automation, Inc