Siemens MCC-3298 Stator Protection, Repetitive Starts, Start Inhibit, Cooling Time Constants

Page 25

3 Operating the SAMMS-LV Device

3.19 Stator Protection

By selecting the overload class slightly greater than or equal to the motor’s starting time, the motor model defines an energy I2t value. In this value, I equals 600% of the motor’s full load current and t equals the overload class selected.

If the amount of energy exerted by the motor during start, stall or under locked rotor condition exceeds the amount of energy defined by the overload class selected, the SAMMS-LV device will trip. This protects the motor’s winding against excessive heat build up. For example, a typical motor starts within 3 to 4 seconds. By selecting an overload class 4 or 5, you can safely start the motor hot or cold and without nuisance tripping. This also provides protection against stall time exceeding 4 or 5 seconds; assuming the locked rotor current equals 600% of the motor’s full-load current (See Figure 3.10).

3.20 Repetitive Starts

The motor model allows repetitive starts without nuisance tripping while protecting the motor against overload and stall conditions. Repetitive starts can occur as long as the following conditions are met:

1.The energy exerted by the motor during start does not exceed the energy defined by the overload class selected.

2.The motor winding temperature does not exceed the maxi- mum temperature allowed.

3.The SAMMS-LV is not in start inhibit (See Section 3.21).

For example, a motor starting from cold condition could have 4 or more typical starts of 5 seconds without nuisance tripping and without damaging the motor insulation. Figure 3.11 shows a multi-start scenario for an open drip-proof motor.

Figure 3.11 Multi-start scenario for an open drip-proof motor

3.21 Start Inhibit

When the motor temperature reaches the maximum values allowed, the SAMMS-LV device trips. If you attempt a restart, the overload LED flashes and the motor will not start until the motor winding and rotor temperatures cool down to the full load temperature. HHC function F25 displays the motor winding temperature as a percentage of the full-load temperature. HHC function F10 displays the time to enable restart in seconds.

3.22 Cooling Time Constants

The motor time constants vary based on whether the motor is running idle or is stopped. The values listed in Table 3.4 are used in the motor model.

Motor

Delta

 

Motor FLC

Cond.

Temp.

 

 

 

0.3-9.0A

9.1-65A

65.1-540A

 

 

 

 

 

 

 

Stopped

80º C to

1750 s

5500 s

9100 s

 

29º C

 

 

 

 

 

 

 

 

Running

80º C to

600 s

1800 s

2800 s

Idle

39.4º C

 

 

 

Table 3.4 Motor time constants

3.23Normalized Temperature Rise for Class B and Class F Insulation

Steady state and maximum winding temperature are functions of the motor’s insulation class. In this motor model, normalized temperature rise for both Class B and Class F insulation are used. The motor winding temperature is displayed as a per- centage of the steady-state full-load temperature rise as shown in Table 3.5.

Boundary

Class B

Class F

% Full Load

Parameters

Insulation

Insulation

Temperature

 

 

 

Rise

 

 

 

 

Steady State

80º C

105º C

100

Temperature

 

 

 

rise at

 

 

 

full-load

 

 

 

current

 

 

 

 

 

 

 

Maximum

140º C

185º C

175

allowed

 

 

 

winding

 

 

 

temperature

 

 

 

Table 3.5 Steady state and maximum winding temperature rise

3.24 Ground Fault Detection

In SAMMS-LV devices, HHC function F12 selects ground fault protection or warning.

protection = ON

warning = OFF

The device detects a ground fault if the fault current exceeds the pickup level for 360 msec. If you have selected protection (ON),

23

Image 25
Contents SAMMS-LV Qualified Person Contents Field Service Operation Signal WordsQualified Person About this Manual Advanced Protection for Low-Voltage Motors SAMMS-LV Device ModelsOverload Protection Using the Standardized Control PanelProgramming Control Circuits SAMMS-LV Model Change settings requires password Yes Remote inputsOutputs One Light barsInstalling the SAMMS-LV Device Full voltage non-reversing connection diagram Grounding the Device SAMMS-LV device communications connections Using the Reset/Test Push Button Password ProtectionPerforming a Lamp Test Performing an Overload Relay TestInput Devices Output DevicesCustom Ladder Diagrams Ladder Diagrams Library of Standard Ladder DiagramsSAMMS-LVX Standard control circuits RVA Motor Ambient Temperature Ridethrough Upon Loss of Power SAMMS-LVX OnlyIncomplete Sequence Intelligent Reduced-Voltage Starting SAMMS-LVX OnlyODP motor thermal signature Operating the SAMMS-LV Operating the SAMMS-LV Device 10 Motor protection graph Phase Unbalance Ultimate Trip Level and Service FactorDual Overload Protection SAMMS-LVX Only Jam Protection SAMMS-LVX OnlyStator Protection Ground Fault DetectionRepetitive Starts Start InhibitUsing the Hand Held Communicator HHC Autoreset After a Trip SAMMS-LVX OnlySize Pickup Current Default Pickup Range Emergency Restarting5A CT primary current if used Full load current for OLR No Function NumberJam pickup current F24 Loss of load protection or warning Function Key Using the Enter KeyList Key UP and Down KeysCapability External trips Enable/disable phase unbalanceStep Size Second Default Value Select ground fault pick-up current Value 2A-5AMeans warning Iflc is the value of Iflc forProgram Mode/Passwords Using the SAMMS-LV Device Func TionsSelect jam pickup current 120-400% I FLC F24 Loss of Load 200% 50% 480013 Entering and changing passwords SAMMS-LV Functions F0 Ambient TemperatureF1 Control Circuit Number and Incomplete Se- quence Status F2 Size for Overload Relay #1F4 Full-Load Current for Overload Relay #1 Overload Setting Step Default Relay Size Range 24.0A 36A45A 90AF8 Autoreset SAMMS-LVX Only F6 Service FactorF9 Phase Unbalance Protection F7 Overload Trip ClassF10 Display Time to Restart F12 Ground Fault Protection or WarningF11 Emergency Restarting F13 Set Programmable Timer #1 F12A Ground Fault Pickup CurrentF14 Set Programmable Timer #2 F15 Display CurrentF17 Current Unbalance F21 Reset Motor DataF18 Display Total Elapsed Run Time of the Motor F19 Number of Motor StartsF23A Jam Pickup Current SAMMS-LVX Only F25 Percentage of Motor Winding TemperatureF24 Loss of Load Protection or Warning SAMMS-LVX Only F24A Loss of Load Pickup Current SAMMS-LVX OnlyF27 Address Troubleshooting Error Condition Troubleshooting Guide Error Condition Appendix a Technical Specifications Overload Specifications Statistical Data Dimensions Catalog Number SAM4 Switch # Function Position Samms Sensor, sizes 1C, 2A, 2B Page Siemens Energy Automation, Inc