Siemens MCC-3298 user manual Overload Specifications

Page 45

Appendix A Technical Specifications

Overload Specifications

 

 

 

 

 

 

Overload classes

Overload classes 2 through 23 with one second increments.

Trip Characteristics

Tripping time at 6 x I FLC

= 95% of the overload class (±5%).

 

Tripping time at 1.5 x I FLC within two minutes for warm conditions for all classes.

Tripping threshold

(1.1 ± 0.05) x I FLC for motors with 1.00 service factor, and

 

(1.2 ± 0.05) x I FLC for motors with 1.15 service factor.

Tripping time

20 minutes @1.15 x I FLC

for motors with service factor 1.

Mechanical jam protection

Sudden increase of the motor running current. Pick-up current adjustable from 120 to

SAMMS-LVX only

400% in increments of 5% of I FLC . Pick-up time 360 msec.

 

Default value: 200% I FLC.

 

 

Loss of load protection

Sudden decrease of motor running current. Pick-up current adjustable from 20 to 95% in

SAMMS-LVX only

increments of 5% of I FLC . Pick-up time 360 msec.

 

Default value: 50% I FLC .

 

 

Process current warning

Settings from 0 to 100% of I FLC .

 

SAMMS-LVX only

 

 

 

 

Accuracy

± 5% of overload trip curve values.

 

 

± 2% repeat accuracy.

 

 

Phase unbalance protection

Response time after 1 second

 

 

Shifted trip threshold value to 0.9 x I FLC

at 40% phase unbalance.

Equipment ground fault protection

Response time after overload class in seconds.

 

Pick-up time: 360 msec.

 

 

 

Pick-up current:

 

 

 

Overload Relay Size Pick-up Current

Default

 

1A

1.5A

1.5A

 

1B

2A- 5A

5A

 

1C

2A- I FLC

5A

 

2A

2A- I FLC

10A

 

2B

2A- I FLC

10A

 

3

2A- I FLC

10A

 

4

2A- I FLC

10A

 

5

5A- I FLC

10A

 

6

10A- I FLC

20A

 

I FLC

is the value of I FLC for OLR#2 if F# is not set to OFF. If F3 is OFF, I FLC is the value of

 

I FLC

for OLR#1.

 

 

Ambient temperature

Motor ambient temperature adjustable 0 - 70°C in increments of 5°C.

 

Default value: 40°C.

 

 

 

 

 

 

 

43

Image 45
Contents SAMMS-LV Qualified Person Contents Signal Words Field Service OperationQualified Person About this Manual Advanced Protection for Low-Voltage Motors SAMMS-LV Device ModelsUsing the Standardized Control Panel Overload ProtectionProgramming Control Circuits SAMMS-LV Model Change settings requires password Yes Remote inputsOutputs One Light barsInstalling the SAMMS-LV Device Full voltage non-reversing connection diagram Grounding the Device SAMMS-LV device communications connections Using the Reset/Test Push Button Password ProtectionPerforming a Lamp Test Performing an Overload Relay TestInput Devices Output DevicesCustom Ladder Diagrams Ladder Diagrams Library of Standard Ladder DiagramsSAMMS-LVX Standard control circuits RVA Motor Ambient Temperature Ridethrough Upon Loss of Power SAMMS-LVX OnlyIncomplete Sequence Intelligent Reduced-Voltage Starting SAMMS-LVX OnlyODP motor thermal signature Operating the SAMMS-LV Operating the SAMMS-LV Device 10 Motor protection graph Phase Unbalance Ultimate Trip Level and Service FactorDual Overload Protection SAMMS-LVX Only Jam Protection SAMMS-LVX OnlyStator Protection Ground Fault DetectionRepetitive Starts Start InhibitUsing the Hand Held Communicator HHC Autoreset After a Trip SAMMS-LVX OnlySize Pickup Current Default Pickup Range Emergency RestartingFunction Number 5A CT primary current if used Full load current for OLR NoJam pickup current F24 Loss of load protection or warning Function Key Using the Enter KeyList Key UP and Down KeysCapability External trips Enable/disable phase unbalanceStep Size Second Default Value Select ground fault pick-up current Value 2A-5AMeans warning Iflc is the value of Iflc forProgram Mode/Passwords Using the SAMMS-LV Device Func TionsSelect jam pickup current 120-400% I FLC F24 Loss of Load 200% 50% 480013 Entering and changing passwords SAMMS-LV Functions F0 Ambient TemperatureF1 Control Circuit Number and Incomplete Se- quence Status F2 Size for Overload Relay #1F4 Full-Load Current for Overload Relay #1 Overload Setting Step Default Relay Size Range 24.0A 36A45A 90AF8 Autoreset SAMMS-LVX Only F6 Service FactorF9 Phase Unbalance Protection F7 Overload Trip ClassF12 Ground Fault Protection or Warning F10 Display Time to RestartF11 Emergency Restarting F13 Set Programmable Timer #1 F12A Ground Fault Pickup CurrentF14 Set Programmable Timer #2 F15 Display CurrentF17 Current Unbalance F21 Reset Motor DataF18 Display Total Elapsed Run Time of the Motor F19 Number of Motor StartsF23A Jam Pickup Current SAMMS-LVX Only F25 Percentage of Motor Winding TemperatureF24 Loss of Load Protection or Warning SAMMS-LVX Only F24A Loss of Load Pickup Current SAMMS-LVX OnlyF27 Address Troubleshooting Error Condition Troubleshooting Guide Error Condition Appendix a Technical Specifications Overload Specifications Statistical Data Dimensions Catalog Number SAM4 Switch # Function Position Samms Sensor, sizes 1C, 2A, 2B Page Siemens Energy Automation, Inc