AEG Thyro-S H1 Operation, Start configuration parameterization, Input and output data Thyro-S

Page 14

6. Operation

6.1 Start configuration (parameterization)

Via the parameterization (in step 7 – HW Config, double-click on slot 0 of the bus module, parameter tab) the following settings can be undertaken.

No connection (slot 1-8):

Here you can set what should happen with the output data of the devices if the connection to the master is interrupted.

Hold last values

The output data are not changed.

Outputs = 0

The output data are set to 0

No connection (slot 9):

Here you can set what should happen with the output data of the bus module if the connection to the master is interrupted.

Hold last value

The digital outputs are not changed.

Outputs = 0

The digital outputs are set to 0.

Averaging of the measured values:

Here you can enter the number of actual values which flow into the averaging. A new value is calculated once a second. Values from 0-20 can be entered, whereby 0 or 1 deactivates this function.

Remove device when it is switched off:

Not all devices are equipped with a 24 V supply connection. When switching off the Thyro mains supply and the control voltage supply (24V) the Thyro no longer communicates with the bus modules. A switched off device will normally be displayed as pull. This display can be suppressed here.

Deactivate

Devices which are no longer accessible (no communication) will continue to

 

be displayed as plug.

Activate

Devices which are no longer accessible will be displayed as pull.

Use output data:

The suppression of certain output data can be activated here.

Always

New output data are transferred immediately.

Only when Bit is set

New output data are only transferred, if the Bit 0 is set in the output

 

“Functions”

6.2 Cyclical data transmission (configuration)

The configuration of the cyclical data traffic is undertaken by adding modules.

The input and output data depend on the device types. The following tables show the input and output data available for each of the devices.

6.3 Input and output data Thyro-S

With the Thyro-S the setpoint is interpreted as operating mode.

14

Image 14
Contents Ethernet Bus Module ProfiNet Contents List of figures and tables Contact Introduction General danger information SafetyIdentification in the operating instructions Electric currentIntended use Operator requirementsPersonnel requirements Use of the deviceTransport Prior to installation / commissioningMaintenance, service, faults Processing the setpoint Thyro-A FunctionsProcessing the setpoint Thyro-S Relais Control Processing the setpoint Thyro-Step ControllerFreely addressable digital outputs Connecting the power controller to InstallationConnecting a 24 V power supply Connecting the Ethernet bus module to the masterSetting the number of slots SettingsSetting the protocol Setting the device nameOperating status of the Ethernet bus module Operating display of the bus moduleOperating display of the bus module Status LED of the Ethernet PortsOperation Start configuration parameterizationCyclical data transmission configuration Input and output data Thyro-STab Cyclic input and output data with Thyro-S ..H1 Tab b Thyro-S FaultsTab Interpretation of the master setpoint with Thyro-S Tab Cyclic input and output data with Thyro-S ..HRL1Tab Cyclic input and output data with Thyro-A 1A...H1 Input and output data Thyro-ATab b Thyro-S Status Tab Cyclic input and output data with Thyro-A 1A...HRL1Tab Cyclic input and output data with Thyro-A 2A...HRL1 Tab Cyclic input and output data with Thyro-A 1A...HRLP1Tab Cyclic input and output data with Thyro-A 2A...H1 Tab Cyclic input and output data with Thyro-A 2A...HRLP1 Tab Cyclic input and output data with Thyro-A 3A...H1Tab Cyclic input and output data with Thyro-A 3A...HRL1 Tab Cyclic input and output data with Thyro-A 3A...HRLP1Tab a Thyro-A Fault Tab b Thyro-A StatusTab Cyclic input and output data with Thyro-A 1A...C03 Tab Cyclic input and output data with Thyro-A 1A...C01Tab Cyclic input and output data with Thyro-A 1A...C02 Supported operating modes TPM TSC TMU Tab Cyclic input and output data with Thyro-A 1A...C05Tab Cyclic input and output data with Thyro-A 1A...C07 Tab Supported operating modesTab Cyclic input and output data TPM manual mode Input and output data Thyro-Power ManagerTab Cyclic input and output data TPM automatic mode Input and output data Thyro-Step Controller Tab Cyclic input and output data TSC modeTab Cyclic input and output data TIO mode Input and output data Thyro Input/Output UnitInput and output data Thyro-Measurement Unit Tab Cyclic input and output data TMU modeTab b Fault TPM, TSC, TIO, TMU Tab b Status TPM, TSC, TIO, TMUWrite data record Wrrec Acyclic data transmission parameterizationRead data record Rdrec Power supply External connectionsOperating elements and terminal blocks Ethernet interfaces InterfacesSystem interface Connection diagrams Thyro-A Connection diagram Thyro-AConnection diagrams Thyro-S Connection diagram Thyro-SConnection diagrams TSC Connection diagram TSCService Technical DataInstallation Specific notesApprovals and conformity Dimension drawingsAccessories and options Detail Appendix a Controller parameterHRL1 Hrlp SST RLP1 U16 R309 Index R309 DAC1OF Page Type value U mains U16 …260 Measuring and cycle time …1500