AEG Thyro-S H1 manual Tab a Thyro-A Fault, Tab b Thyro-A Status

Page 20

Tab. 14a Thyro-A Fault

Description

Bit

LEDs

Relay

Frequency measurement outside of 47Hz to 63Hz

Bit 0

Pulse Inhibit LED flashing slowly

open

SYNC error, no cero crossing within the gate

Bit 1

Pulse Inhibit LED flashing slowly

open

Temperature monitoring triggered

Bit 2

Load Fault LED flashing slowly

open

Load fault

Bit 3

Load fault LED on

open

Flash values invalid

Bit 4

Pulse Inhibit LED and Load

open

 

 

Fault LED flashing simultaneous-

 

 

 

ly qickly

 

Mains undervoltage (<AD_P_SPG_MIN)

Bit 5

Pulse Inhibit LED, Load Fault

open

 

 

LED and test LED on

 

Mains overvoltage (>AD_P_SPG_MAX) Master / slave fault (only with2A) Undervoltage limit

Overvoltage limit Undercurrent limit Overcurrent limit Low power limit High power limit

Bit 6

none

Bit 8

none

Bit 9

none

Bit 10

none

Bit 11

none

Bit 12

none

Bit 13

none

Bit 14

none

open

closed closed closed closed closed closed closed

Tab. 14b Thyro-A Status

Description

Bit

LEDs

Relay

Pulse inhib active (bridge X2.1-X2.2 open)

Bit 0

Pulse Inhibit LED on

closed

Mains frequency is 60Hz

Bit 2

none

 

closed

U-limiting

Bit 4

Pulse Inhibit LED

and Load

closed

 

 

Fault LED flashing alternately

 

 

 

slowly

 

 

I-limiting

Bit 5

Pulse Inhibit LED

and Load

closed

 

 

Fault LED flashing alternately

 

 

 

slowly

 

 

P-limiting

Bit 6

Pulse Inhibit LED

and Load

closed

 

 

Fault LED flashing alternately

 

 

 

slowly

 

 

Relay status

Bit 8

none

 

on/off

(0=relay off / 1=relay on)

Bit 8

none

 

on/off

Device switched off

Bit 9

--

 

--

Wrong device

Bit 10

--

 

--

Bus module active

Bit 11

only with Thyro-S

 

-----

(0=no bus module / 1=bus module active)

 

 

 

 

Thyristor short-circuit

Bit 14

only with Thyro-S

 

----

Failure rotating field / phase

Bit 15

none

 

closed

(only Thyro 2A or 3A)

Bit 15

Pulse Inhibit LED

and Test LED

closed

 

 

flashing simultaneously slowly

 

Overcurrent limit

Bit 12

none

 

closed

Low power limit

Bit 13

none

 

closed

High power limit

Bit 14

none

 

closed

20

Image 20
Contents Ethernet Bus Module ProfiNet Contents List of figures and tables Contact Introduction Safety Identification in the operating instructionsGeneral danger information Electric currentOperator requirements Personnel requirementsIntended use Use of the deviceTransport Prior to installation / commissioningMaintenance, service, faults Processing the setpoint Thyro-A FunctionsProcessing the setpoint Thyro-S Relais Control Processing the setpoint Thyro-Step ControllerFreely addressable digital outputs Installation Connecting a 24 V power supplyConnecting the power controller to Connecting the Ethernet bus module to the masterSettings Setting the protocolSetting the number of slots Setting the device nameOperating display of the bus module Operating display of the bus moduleOperating status of the Ethernet bus module Status LED of the Ethernet PortsStart configuration parameterization Cyclical data transmission configurationOperation Input and output data Thyro-STab b Thyro-S Faults Tab Interpretation of the master setpoint with Thyro-STab Cyclic input and output data with Thyro-S ..H1 Tab Cyclic input and output data with Thyro-S ..HRL1Input and output data Thyro-A Tab b Thyro-S StatusTab Cyclic input and output data with Thyro-A 1A...H1 Tab Cyclic input and output data with Thyro-A 1A...HRL1Tab Cyclic input and output data with Thyro-A 2A...HRL1 Tab Cyclic input and output data with Thyro-A 1A...HRLP1Tab Cyclic input and output data with Thyro-A 2A...H1 Tab Cyclic input and output data with Thyro-A 2A...HRLP1 Tab Cyclic input and output data with Thyro-A 3A...H1Tab Cyclic input and output data with Thyro-A 3A...HRL1 Tab Cyclic input and output data with Thyro-A 3A...HRLP1Tab a Thyro-A Fault Tab b Thyro-A StatusTab Cyclic input and output data with Thyro-A 1A...C03 Tab Cyclic input and output data with Thyro-A 1A...C01Tab Cyclic input and output data with Thyro-A 1A...C02 Tab Cyclic input and output data with Thyro-A 1A...C05 Tab Cyclic input and output data with Thyro-A 1A...C07Supported operating modes TPM TSC TMU Tab Supported operating modesTab Cyclic input and output data TPM manual mode Input and output data Thyro-Power ManagerTab Cyclic input and output data TPM automatic mode Tab Cyclic input and output data TSC mode Tab Cyclic input and output data TIO modeInput and output data Thyro-Step Controller Input and output data Thyro Input/Output UnitTab Cyclic input and output data TMU mode Tab b Fault TPM, TSC, TIO, TMUInput and output data Thyro-Measurement Unit Tab b Status TPM, TSC, TIO, TMUWrite data record Wrrec Acyclic data transmission parameterizationRead data record Rdrec Power supply External connectionsOperating elements and terminal blocks Ethernet interfaces InterfacesSystem interface Connection diagrams Thyro-A Connection diagram Thyro-AConnection diagrams Thyro-S Connection diagram Thyro-SConnection diagrams TSC Connection diagram TSCTechnical Data InstallationService Specific notesApprovals and conformity Dimension drawingsAccessories and options Detail Appendix a Controller parameterHRL1 Hrlp SST RLP1 U16 R309 Index R309 DAC1OF Page Type value U mains U16 …260 Measuring and cycle time …1500