AEG Thyro-S H1 manual Tab Interpretation of the master setpoint with Thyro-S, Tab b Thyro-S Faults

Page 15

Tab. 3 Interpretation of the master setpoint with Thyro-S

Setpoint (Master)

Status (return value)

0 to 409

= OFF

410 to 1091

1/5

1092 to 1706

= 1/3

1707 to 3071

1/2

3072 to 4096

= ON

Tab. 4 Cyclic input and output data with Thyro-S ..H1

(Total setpoint)

0=

819

1365 =

2047

4096

Offset

Input data, actual values

Data type

Size

Unit

0

Load voltage L1

float

4

[V]

4

Mains voltage L1

integer

2

[V]

6

Total setpoint

integer

2

4096=100%

8

Fault (see table 5b)

integer

2

-

10

Status (see table 5b)

integer

2

-

Offset

Output data, setpoint

Data type

Size

Unit

0

Master Setpoint

integer

2

4096=100%

Tab. 5 Cyclic input and output data with Thyro-S ..HRL1

Offset

Input data, actual values

Data type

Size

Unit

0

Load voltage L1

float

4

[V]

4

Load current L1

float

4

[A]

8

Mains voltage L1

integer

2

[V]

10

Total setpoint

integer

2

4096=100%

12

Fault (see table 5b)

integer

2

-

14

Status (see table 5b)

integer

2

-

Offset

Output data, setpoint

Data type

Size

Unit

0

Master setpoint

integer

2

4096=100%

Tab. 5b Thyro-S Faults

Description

Bit

LEDs

Relay

Frequency measurement outside of 47 Hz to 63 Hz

Bit 0

Test LED flashing slowly

open

SYNC error, no zero-crossing within the gate

Bit 1

Test LED flashing slowly

open

Temperature monitoring triggered

Bit 2

Load Fault flashing slowly

open

Load fault

Bit 3

Load Fault on

open

Flash values invalid

Bit 4

Test LED and Load Fault LED

open

 

 

flashing simultaneously quickly

 

Mains undervoltage (<AD_P_SPG_MIN)

Bit 5

Load Fault LED and Test LED on

open

Mains overvoltage (>AD_P_SPG_MAX)

Bit 6

None

closed

15

Image 15
Contents Ethernet Bus Module ProfiNet Contents List of figures and tables Contact Introduction Electric current SafetyIdentification in the operating instructions General danger informationUse of the device Operator requirementsPersonnel requirements Intended usePrior to installation / commissioning Maintenance, service, faultsTransport Functions Processing the setpoint Thyro-SProcessing the setpoint Thyro-A Processing the setpoint Thyro-Step Controller Freely addressable digital outputsRelais Control Connecting the Ethernet bus module to the master InstallationConnecting a 24 V power supply Connecting the power controller toSetting the device name SettingsSetting the protocol Setting the number of slotsStatus LED of the Ethernet Ports Operating display of the bus moduleOperating display of the bus module Operating status of the Ethernet bus moduleInput and output data Thyro-S Start configuration parameterizationCyclical data transmission configuration OperationTab Cyclic input and output data with Thyro-S ..HRL1 Tab b Thyro-S FaultsTab Interpretation of the master setpoint with Thyro-S Tab Cyclic input and output data with Thyro-S ..H1Tab Cyclic input and output data with Thyro-A 1A...HRL1 Input and output data Thyro-ATab b Thyro-S Status Tab Cyclic input and output data with Thyro-A 1A...H1Tab Cyclic input and output data with Thyro-A 1A...HRLP1 Tab Cyclic input and output data with Thyro-A 2A...H1Tab Cyclic input and output data with Thyro-A 2A...HRL1 Tab Cyclic input and output data with Thyro-A 3A...H1 Tab Cyclic input and output data with Thyro-A 2A...HRLP1Tab Cyclic input and output data with Thyro-A 3A...HRLP1 Tab Cyclic input and output data with Thyro-A 3A...HRL1Tab b Thyro-A Status Tab a Thyro-A FaultTab Cyclic input and output data with Thyro-A 1A...C01 Tab Cyclic input and output data with Thyro-A 1A...C02Tab Cyclic input and output data with Thyro-A 1A...C03 Tab Supported operating modes Tab Cyclic input and output data with Thyro-A 1A...C05Tab Cyclic input and output data with Thyro-A 1A...C07 Supported operating modes TPM TSC TMUInput and output data Thyro-Power Manager Tab Cyclic input and output data TPM automatic modeTab Cyclic input and output data TPM manual mode Input and output data Thyro Input/Output Unit Tab Cyclic input and output data TSC modeTab Cyclic input and output data TIO mode Input and output data Thyro-Step ControllerTab b Status TPM, TSC, TIO, TMU Tab Cyclic input and output data TMU modeTab b Fault TPM, TSC, TIO, TMU Input and output data Thyro-Measurement UnitAcyclic data transmission parameterization Read data record RdrecWrite data record Wrrec External connections Power supplyOperating elements and terminal blocks Interfaces System interfaceEthernet interfaces Connection diagram Thyro-A Connection diagrams Thyro-AConnection diagram Thyro-S Connection diagrams Thyro-SConnection diagram TSC Connection diagrams TSCSpecific notes Technical DataInstallation ServiceDimension drawings Accessories and optionsApprovals and conformity Detail Controller parameter Appendix aHRL1 Hrlp SST RLP1 U16 R309 Index R309 DAC1OF Page Type value U mains U16 …260 Measuring and cycle time …1500