AEG Thyro-S H1 manual Appendix a, Controller parameter

Page 36

17. Appendix A

1. Acyclic parameter table Thyro-S; Thyro-A; -C01; -C02; -C03; -C05

Table A: Thyro-S.., Thyro-A.., Thyro-A-C01; -C02; -C03; -C05 controller parameters slot 1-8

Controller parameter

Index Symbol

Name

Data type Value range

Combo-opt.

1

I_TYP

Controller type current

u16

0…

 

2

U_TYP

Controller supply voltage

u16

0…1000

 

3

P_TYP

Controller type output power

u32

0…

 

6

BETR

Operating mode

u16

0…3

Reserved, TAKT, VAR, QTM

7

AN1

Phase angle of 1st half wave

u16

0…180

 

8

SST

Soft start duration (given)

u16

0…1000

 

9

SDN

Soft stop duration (given)

u16

0…1000

 

10

T0

Cycle period duration

u16

0…1000

 

11

MP

Minimum interval

u16

0…10

 

12

TSMAX

Maximum cycle turn on time

u16

1…T0

 

13

TSMIN

Minimum cycle turn on time

u16

0…T0

 

14

V_IE

Front pulse stop

u16

0…180

 

15

H_IE

Back pulse stop

u16

0…180

 

16

RE

Control (analog output value)

u16

0…8

Uload2, Uload eff, Iload2, Iload eff, reserved, real power,

 

 

 

 

 

reserved, reserved, without regulation

17

TI_1

PI controller, I part

u16

0= aus 0…65535

 

18

KP_1

PI controller, P part

u16

0= aus 0…65535

 

19

KR_1

PI controller, counter P part

u16

0…65535

 

20

V_IE_2

Front pulse stop phase 2

u16

0…180

 

21

UEMA

Effective voltage setpoint maximum

u16

0…

 

22

IEMA

Effective current setpoint maximum

u16

0…

 

23

PMA

Power setpoint maximum

u32

0…

 

24

SW_ENABLE

Setpoint activation

u16

0…3

Bit0=1 setpoint x2.4 active, Bit1=1 setpoint

 

 

 

 

 

master active

27

SW_REGLER

Setpoint x2.4

u16

0…4096

 

28

OF_1

Actual value output offset 1

u16

0…4096

 

29

FA_1

Scale end value actual value output 1

u16

0…4096

 

30

SPG_MIN

Mains voltage monitoring min.

u16

0…1000

 

31

SPG_MAX

Mains voltage monitoring max.

u16

0…1000

 

32

UN_S

Undercurrent monitoring

u16

0…1

on, off

33

RELAIS_CTRL_2

Relay configuration 2

u16

0…65535

bit coded

34

LASTBRUCH_MIN_ABS

Load fault, minimum value

u16

0…4505

 

36

SYNC_ADR

Synchro cycle address

u16

0…65535

 

37

IMAB

Pulse switch-off in case of failure

u16

0…65535

bit coded

38

STA_RE

Control start controller analog setpoint

u16

0…65535

 

39

STE_RE

Control end controller analog setpoint

u16

0…65535

 

40

 

Configuration 3A

u16

 

bit coded

41

MOSI_FA

Peak current value limit

u16

0…4096

 

42

DAC_1_CTRL

Analog output configuration 1

u16

0…10

 

44

VERS_T

Version day

u16

1…31

 

45

VERS_M

Version month

u16

1…12

 

46

VERS_J

Version year

u16

0…9999

 

48

 

Controller inhibit

u16

0…1

on, off

49

RELAIS_CTRL

Relay configuration 1

u16

0…65535

bit coded

50

 

Save

u16

0…1

off, save

56

MITTEL

Averaging analog output 1

u16

0…65535

 

84

TEMP

Temperature

u16

-50…150

 

109

MITTEL_2

Averaging analog output 2

u16

0…65535

 

110

OF_2

Actual value output offset 2

u16

0…4096

 

111

FA_2

Scale end value actual value output 2

u16

0…4096

 

112

DAC_2_CTRL

Analog output configuration 2

u16

0…10

 

115

MITTEL_3

Averaging analog output 3

u16

0…65535

 

116

OF_3

Actual value output offset 3

u16

0…4096

 

117

FA_3

Scale end value actual value output 3

u16

0…4096

 

118

DAC_3_CTRL

Analog output configuration 3

u16

0…10

 

119

U_MIN

Voltage limit minimum

u16

0…65535

 

120

U_MAX

Voltage limit maximum

u16

0…65535

 

121

I_MIN

Current limit minimum

u16

0…65535

 

122

I_MAX

Current limit maximum

u16

0…65535

 

123

P_MIN

Power limit minimum

u32

0…

 

124

P_MAX

Power limit maximum

u32

0…

 

36

Image 36
Contents Ethernet Bus Module ProfiNet Contents List of figures and tables Contact Introduction Safety Identification in the operating instructionsGeneral danger information Electric currentOperator requirements Personnel requirementsIntended use Use of the devicePrior to installation / commissioning Maintenance, service, faultsTransport Functions Processing the setpoint Thyro-SProcessing the setpoint Thyro-A Processing the setpoint Thyro-Step Controller Freely addressable digital outputsRelais Control Installation Connecting a 24 V power supplyConnecting the power controller to Connecting the Ethernet bus module to the masterSettings Setting the protocolSetting the number of slots Setting the device nameOperating display of the bus module Operating display of the bus moduleOperating status of the Ethernet bus module Status LED of the Ethernet PortsStart configuration parameterization Cyclical data transmission configurationOperation Input and output data Thyro-STab b Thyro-S Faults Tab Interpretation of the master setpoint with Thyro-STab Cyclic input and output data with Thyro-S ..H1 Tab Cyclic input and output data with Thyro-S ..HRL1Input and output data Thyro-A Tab b Thyro-S StatusTab Cyclic input and output data with Thyro-A 1A...H1 Tab Cyclic input and output data with Thyro-A 1A...HRL1Tab Cyclic input and output data with Thyro-A 1A...HRLP1 Tab Cyclic input and output data with Thyro-A 2A...H1Tab Cyclic input and output data with Thyro-A 2A...HRL1 Tab Cyclic input and output data with Thyro-A 2A...HRLP1 Tab Cyclic input and output data with Thyro-A 3A...H1Tab Cyclic input and output data with Thyro-A 3A...HRL1 Tab Cyclic input and output data with Thyro-A 3A...HRLP1Tab a Thyro-A Fault Tab b Thyro-A StatusTab Cyclic input and output data with Thyro-A 1A...C01 Tab Cyclic input and output data with Thyro-A 1A...C02Tab Cyclic input and output data with Thyro-A 1A...C03 Tab Cyclic input and output data with Thyro-A 1A...C05 Tab Cyclic input and output data with Thyro-A 1A...C07Supported operating modes TPM TSC TMU Tab Supported operating modesInput and output data Thyro-Power Manager Tab Cyclic input and output data TPM automatic modeTab Cyclic input and output data TPM manual mode Tab Cyclic input and output data TSC mode Tab Cyclic input and output data TIO modeInput and output data Thyro-Step Controller Input and output data Thyro Input/Output UnitTab Cyclic input and output data TMU mode Tab b Fault TPM, TSC, TIO, TMUInput and output data Thyro-Measurement Unit Tab b Status TPM, TSC, TIO, TMUAcyclic data transmission parameterization Read data record RdrecWrite data record Wrrec Power supply External connectionsOperating elements and terminal blocks Interfaces System interfaceEthernet interfaces Connection diagrams Thyro-A Connection diagram Thyro-AConnection diagrams Thyro-S Connection diagram Thyro-SConnection diagrams TSC Connection diagram TSCTechnical Data InstallationService Specific notesDimension drawings Accessories and optionsApprovals and conformity Detail Appendix a Controller parameterHRL1 Hrlp SST RLP1 U16 R309 Index R309 DAC1OF Page Type value U mains U16 …260 Measuring and cycle time …1500