6.8 Input and output data Thyro-Measurement Unit
Tab. 25 Cyclic input and output data TMU mode
Offset | Input data, actual values | Data type | Size | Unit |
0 | AC input 1 | float | 4 | [A],[V] |
4 | AC input 2 | float | 4 | [A],[V] |
8 | AC input 3 | float | 4 | [A],[V] |
12 | Power | float | 4 | [W] |
16 | Energy | float | 4 | [kWh] |
20 | DC input 1 | integer | 2 | 4096=100% |
22 | DC input 2 | integer | 2 | 4096=100% |
24 | DC input 3 | integer | 2 | 4096=100% |
26 | Mains voltage | integer | 2 | [V] |
28 | Period duration | integer | 2 | [μs] |
30 | Temperature | integer | 2 | [°C] |
32 | Fault (see table 25b) | integer | 2 | - |
34 | Status (see table 25b) | integer | 2 | - |
Tab. 25b Status TPM, TSC, TIO, TMU
Description | Bit | Fault LED, fault output* |
Frequency measurement outside of 47Hz to 63Hz | Bit 0 | on |
SYNC error, no cero crossing within the gate | Bit 1 | on |
Temperature max. limit has been exceeded | Bit 2 | on |
Temperature min. limit has been exceeded | Bit 3 | on |
One or more parameters outside the limits | Bit 4 | on |
Mains voltage lower than lower voltage limit | Bit 5 | on |
Tab. 25b Fault TPM, TSC, TIO, TMU
Description | Bit | Alarm LED, alarm output* |
Mains frequency is 60Hz | Bit 2 | off |
Transformer 1 fallen below min. limit | Bit 3 | on |
Transformer 1 exceeded max. limit | Bit 4 | on |
Transformer 2 fallen below min. limit | Bit 5 | on |
Transformer 2 exceeded max. limit | Bit 6 | on |
Transformer 3 fallen below min. limit | Bit 7 | on |
Transformer 3 exceeded max. limit | Bit 8 | on |
Device switched off | Bit 9 | |
Wrong device | Bit 10 | |
Bus module active (0=no bus module / 1=bus module | Bit 11 | off |
active) |
|
|
* Default setting can be parameterized. |
|
|