3. Functions

3.1 Processing the setpoint Thyro-S

Only local setpoints, no bus setpoint

Switching signal (24DC) at the control terminal X22.1 of the Thyro-S > No wiring of the terminal point X22.4 at the power controller

-The bus module is fully functional. The analog signal from the control terminal X22.1 is used as setpoint (on/off).

Setpoint from the bus module (X22.3), no local setpoint

> Connect the ground to terminal X22.4 of the power controller.

- The master setpoint of the bus module is used. For this purpose the setpoint is interpreted as the ope- rating mode.

Bus setpoint, switching over to „local“ in case of bus fault

Only use the setpoint of the bus module if there is an IO connection.

>Connect terminal X22.4 of the power controller to one of the terminals X1.1 to X8.1 of the bus module. - If there is an IO connection the master set point is used.

If not then the analog signal from the control terminal X22.1 is used as setpoint (on/off).

Switching over to bus / local setpoint switchable for each controller in operation

Individual setpoint from the bus module for each power controller.

>Connect terminal X22.4 of the power controller to one of the terminals X1.5 to X 8.5 of the bus module.

-The power controllers can be switched over individually (targeted) via the bus between master setpoint and terminal X22.1

3.2Processing the setpoint Thyro-A

Only local setpoints, no bus setpoint

Analog input at control terminal X2.4 of Thyro-A

> Do not connect anything to terminal X22.1 of the power controller.

-The bus module is fully functional. The analog signal from the control terminal X2.4 is used as setpoint (on/off).

Setpoint from the bus module (X22.3), no local setpoint

>Connect the ground to terminal X22.1 of the power controller. - The master setpoint of the bus module is used.

Bus setpoint, switching over to “local” in case of bus fault

Only use the setpoint of the bus module if there is an IO connection.

> Connect terminal X22.1 of the power controller to one of the terminals X1.1 to X8.1 of the bus module.

-If there is an IO connection the master setpoint is used. If there is no IO connection then the analog signal from the control terminal X2.4 is used as setpoint.

Switching over to bus / local setpoint switchable for each controller in operation

Individual setpoint from the bus module for each power controller.

> Connect terminal X22.1 of the power controller to one of the terminals X1.5 to X8.5 of the bus module.

-The power controllers can be switched over individually (targeted) via the bus between master setpoint and terminal X2.4.

9

Image 9
Contents Ethernet Bus Module ProfiNet Contents List of figures and tables Contact Introduction Identification in the operating instructions SafetyGeneral danger information Electric currentPersonnel requirements Operator requirementsIntended use Use of the devicePrior to installation / commissioning Maintenance, service, faultsTransport Functions Processing the setpoint Thyro-SProcessing the setpoint Thyro-A Processing the setpoint Thyro-Step Controller Freely addressable digital outputsRelais Control Connecting a 24 V power supply InstallationConnecting the power controller to Connecting the Ethernet bus module to the masterSetting the protocol SettingsSetting the number of slots Setting the device nameOperating display of the bus module Operating display of the bus moduleOperating status of the Ethernet bus module Status LED of the Ethernet PortsCyclical data transmission configuration Start configuration parameterizationOperation Input and output data Thyro-STab Interpretation of the master setpoint with Thyro-S Tab b Thyro-S FaultsTab Cyclic input and output data with Thyro-S ..H1 Tab Cyclic input and output data with Thyro-S ..HRL1Tab b Thyro-S Status Input and output data Thyro-ATab Cyclic input and output data with Thyro-A 1A...H1 Tab Cyclic input and output data with Thyro-A 1A...HRL1Tab Cyclic input and output data with Thyro-A 1A...HRLP1 Tab Cyclic input and output data with Thyro-A 2A...H1Tab Cyclic input and output data with Thyro-A 2A...HRL1 Tab Cyclic input and output data with Thyro-A 3A...H1 Tab Cyclic input and output data with Thyro-A 2A...HRLP1Tab Cyclic input and output data with Thyro-A 3A...HRLP1 Tab Cyclic input and output data with Thyro-A 3A...HRL1Tab b Thyro-A Status Tab a Thyro-A FaultTab Cyclic input and output data with Thyro-A 1A...C01 Tab Cyclic input and output data with Thyro-A 1A...C02Tab Cyclic input and output data with Thyro-A 1A...C03 Tab Cyclic input and output data with Thyro-A 1A...C07 Tab Cyclic input and output data with Thyro-A 1A...C05Supported operating modes TPM TSC TMU Tab Supported operating modesInput and output data Thyro-Power Manager Tab Cyclic input and output data TPM automatic modeTab Cyclic input and output data TPM manual mode Tab Cyclic input and output data TIO mode Tab Cyclic input and output data TSC modeInput and output data Thyro-Step Controller Input and output data Thyro Input/Output UnitTab b Fault TPM, TSC, TIO, TMU Tab Cyclic input and output data TMU modeInput and output data Thyro-Measurement Unit Tab b Status TPM, TSC, TIO, TMUAcyclic data transmission parameterization Read data record RdrecWrite data record Wrrec External connections Power supplyOperating elements and terminal blocks Interfaces System interfaceEthernet interfaces Connection diagram Thyro-A Connection diagrams Thyro-AConnection diagram Thyro-S Connection diagrams Thyro-SConnection diagram TSC Connection diagrams TSCInstallation Technical DataService Specific notesDimension drawings Accessories and optionsApprovals and conformity Detail Controller parameter Appendix aHRL1 Hrlp SST RLP1 U16 R309 Index R309 DAC1OF Page Type value U mains U16 …260 Measuring and cycle time …1500