Tab. 8 Cyclic input and output data with Thyro-A 1A...HRLP1
Offset | Input data, actual values | Data type | Size | Unit |
0 | Load voltage L1 | float | 4 | [V] |
4 | Load current L1 | float | 4 | [A] |
8 | Power L1 | float | 4 | [W] |
12 | Mains voltage L1 | integer | 2 | [V] |
14 | integer | 2 | [period] | |
16 | integer | 2 | [0.01 °el] | |
18 | Total setpoint | integer | 2 | 4096=100% |
20 | Fault (see table 14b) | integer | 2 | - |
22 | Status (see table 14b) | integer | 2 | - |
Offset | Output data, setpoint | Data type | Size | Unit |
0 | Master setpoint | integer | 2 | 4096=100% |
Tab. 9 Cyclic input and output data with Thyro-A 2A...H1
Offset | Input data, actual values | Data type | Size | Unit |
0 | Load voltage L1 | float | 4 | [V] |
4 | Load voltage L3 | float | 4 | [V] |
8 | Mains voltage L1 | integer | 2 | [V] |
10 | Mains voltage L3 | integer | 2 | [V] |
12 | integer | 2 | [period] | |
14 | Total setpoint | integer | 2 | 4096=100% |
16 | Fault (see table 14b) | integer | 2 | - |
18 | Status (see table 14b) | integer | 2 | - |
Offset | Output data, setpoint | Data type | Size | Unit |
0 | Master setpoint | integer | 2 | 4096=100% |
Tab. 10 Cyclic input and output data with Thyro-A 2A...HRL1
Offset | Input data, actual values | Data type | Size | Unit |
0 | Load voltage L1 | float | 4 | [V] |
4 | Load voltage L3 | float | 4 | [V] |
8 | Load current L1 | float | 4 | [A] |
12 | Load current L2 | float | 4 | [A] |
16 | Load current L3 | float | 4 | [A] |
20 | Mains voltage L1 | integer | 2 | [V] |
22 | Mains voltage L3 | integer | 2 | [V] |
24 | integer | 2 | [period] | |
26 | Total setpoint | integer | 2 | 4096=100% |
28 | Fault (see table 14b) | integer | 2 | - |
30 | Status (see table 14b) | integer | 2 | - |
Offset | Output data, setpoint | Data type | Size | Unit |
0 | Master setpoint | integer | 2 | 4096=100% |