GE BECCO2200 manual Binary Inputs, Binary Outputs, Counters, Analog Inputs, Analog Outputs

Page 20

 

BECCO2200 DCA

GE Energy Services

Configuration Guide

NOTE: The actual number of Binary Output points required must be incremented by the number of Mode Download Pseudo Controls configured.

2.1.1 Binary Inputs

When communication is established with a device and valid data is returned for the binary input point, the point is turned on-line and communication OK. If communication between the device and the point fails, all binary input points associated with the device will be set off-line and communication failed.

2.1.2 Binary Outputs

On startup, all pseudo controls associated with a valid device and all Mode Download Pseudo Controls are placed on-line and communication OK. When communication is established with a device, the remaining binary outputs are set on-line and communication OK. If communication between the device and the points fails, all binary output points, excluding pseudo controls, will be set off-line and communication failed.

2.1.3 Counters

When communication is established with a device and valid data is returned for the counter, the point is turned on-line and communication OK. If communication between the device and the point fails, all counters associated with the device will be set off-line and communication failed.

2.1.4 Analog Inputs

When communication is established with a device and valid data is returned for the analog input point, the point is turned on-line and communication OK. If communication between the device and the point fails, all analog input points associated with the device will be set off-line and communication failed.

2.1.5 Analog Outputs

On startup, all analog outputs associated with a valid device are placed on-line and communication OK. If communication between the device and the point fails, all analog output points associated with the device will be set off-line and communication failed.

2.1.6 Device Status

When communication is established with a device, the device status point is set on-line and communication OK. If communication between the device and the point fails, the device status point will be set off-line and communication failed.

A164-0CG-1.00-2Restricted

4

Full

 

Image 20
Contents Configuration Guide BECCO2200 DCATrademark Notices Table of Contents Configuring the A164MODE Table Configuring the A164DTBL Configuration Table BECCO2200 DCA List of Figures Viii List of Tables BECCO2200 DCA Who Should Use this Guide About this GuidePurpose of this Guide Additional Documentation Introduction to the Wesdac D20 RTU GEN-0003How this Guide is Organized Xiv Overview Xvi Configuration Tables BECO2200 DCA Configuration TablesConfiguration Sequence Configuring Win for the BECO2200 DCA Wesdac Point AllocationBinary Inputs Binary OutputsCounters Analog InputsDescription of Fields Configuring the A164APPL TableGeneral Information Reply Buffer Size Adjustment SOE Buffer Size AdjustmentDCA Index SOE Buffer Overflow OptionDevice Event Response Time BECCO2200 DCA Configuring the A164PORT Table BECO2200 DCA A164PORT Configuration TableCommunication Port Name Communication Port ParityBaud Rate RTS On TimeRTS Off Time Intercharacter TimeoutRemote Reply Timeout Line Idle Time Retries Before FailureFailures Before Off-line Number of Devices on PortConfiguring the A164UNIT Table BECO2200 DCA A164UNIT Configuration TableType 0 Read Interval Remote AddressUnit Type Type 1 Read Interval Type 2 Read IntervalType 3 Read Interval Type 4 Read IntervalTime Synchronization Interval Type 7 Read IntervalType 8 Read Interval Configuring the A164MODE Table First Dvcf A164MODENumber of Dvcf BECCO2200 DCA Configuring the A164DVCF Configuration Table First Unit Number of UnitsFirst Data Record Number of Data RecordsConfiguring the A164DTBL Configuration Table Data Value Table TypePoint Number Fatal Error Messages Appendix AMessages Logged by the BECO2200 DCAF100 Bad A164APPL record counts, must be F101 Bad A164PORT record counts, must beF102 Bad A164UNIT record counts, must be F103 Bad Cfgdca record counts, must beF106 Total # devices exceeds Unit size F107 x WESDACy pnts configured, z requiredF105 Invalid SOE Overflow parameter F108 x table creation error F110 Fatal errors exist in configurationF109 Cannot find x database table F111 Bad A164DVCF record counts, must beF120 Mode Record x, invalid First Dvcf F121 Mode Record x, invalid Number of DvcfF122 Dvcf Record x, invalid First Unit F123 Dvcf Record x, invalid Number of UnitsF200 Error x on win open F201 Error x signaling A164-D-00 processF203 Error x creating A164-y-z exchange F125 Dvcf Record x, invalid Number of Type-PointF204 Error x spawning A164-y-z process F205 Error x activating A164-y-z processF206 Process A164-x-y died while initializing F207 Unable to allocate buffersNon-Fatal Error Messages E300 Port rec x, invalid baud rateE301 Port rec x, invalid failures before offline E302 Port rec x, num of devices exceeds UnitE303 Port rec x, configuration bad E307 Unit rec x, configuration badE304 Port rec x, invalid unit address E305 Unit rec x, invalid unit typeE399 Non-fatal errors exist in configuration E400 Error x opening port yE401 Error x setting character port E308 Port rec x, num of devices cannot =E402 Error x setting SIO timers E403 Error x creating A164-y-z exchangeE404 Error x spawning A164-y-z process E405 Error x activating A164-y-z processE407 Error x signalling A164-y-z process E409 Error x, invalid start signal from SpawnerE406 Process A164-x-y died while initializing E408 Unable to allocate polling listPSOS Interface Warnings Information Messages I700 Port rec x, invalid reply time-outI701 Port rec x, invalid RTS on time I702 Port rec x, invalid RTS off timeI705 Port rec x, no polling required I703 Port rec x, invalid intercharacter timeoutI704 No Configuration deleting Output Request Return Codes Demand Scan FailedDo Operate Failed AO Operate FailedGlossary of Terms AsciiRAM Menu-oriented software program that operates on a personal A164-0CG-1.00-2Restricted List of Acronyms and Abbreviations