GE BECCO2200 F204 Error x spawning A164-y-z process, F205 Error x activating A164-y-z process

Page 47

BECCO2200 DCA

 

Configuration Guide

GE Energy Services

F204: Error <x> spawning A164-<y>-<z> process

Cause:

The BECO2200 DCA failed in its attempt to spawn the A164-<y>-<z> process. The error code returned was <x>.

Remedy:

Call the Customer Service department and report this error.

F205: Error <x> activating A164-<y>-<z> process

Cause:

The BECO2200 DCA failed in its attempt to activate the A164-<y>-<z> process. The error code returned was <x>.

Remedy:

Call the Customer Service department and report this error.

F206: Process A164-<x>-<y> died while initializing

Cause:

The A164-<x>-<y> process was deleted while initializing.

Remedy:

Address any fatal or non-fatal errors preceding this message.

Call the Customer Service department and report this error.

F207: Unable to allocate buffers

Cause:

The BECO2200 DCA was unable to allocate enough memory for its internal buffers.

Effect:

The BECO2200 DCA will be unable to communicate to any device configured.

Remedy:

Reduce the amount of RAM used by this and any other application in the system. The parameters that affect the amount of RAM required by this application are noted in their associated chapters.

Upgrade the GE Energy Services product to a model with more memory.

Call the Customer Service department and report this error.

Restricted

A164-0CG-1.00-2

Full

31

 

Image 47
Contents BECCO2200 DCA Configuration GuideTrademark Notices Table of Contents Configuring the A164MODE Table Configuring the A164DTBL Configuration Table BECCO2200 DCA List of Figures Viii List of Tables BECCO2200 DCA Who Should Use this Guide About this GuidePurpose of this Guide Introduction to the Wesdac D20 RTU GEN-0003 Additional DocumentationHow this Guide is Organized Xiv Overview Xvi BECO2200 DCA Configuration Tables Configuration TablesConfiguration Sequence Wesdac Point Allocation Configuring Win for the BECO2200 DCAAnalog Inputs Binary InputsBinary Outputs CountersDescription of Fields Configuring the A164APPL TableGeneral Information SOE Buffer Overflow Option Reply Buffer Size AdjustmentSOE Buffer Size Adjustment DCA IndexDevice Event Response Time BECCO2200 DCA BECO2200 DCA A164PORT Configuration Table Configuring the A164PORT TableRTS On Time Communication Port NameCommunication Port Parity Baud RateRTS Off Time Intercharacter TimeoutRemote Reply Timeout Number of Devices on Port Line Idle TimeRetries Before Failure Failures Before Off-lineBECO2200 DCA A164UNIT Configuration Table Configuring the A164UNIT TableType 0 Read Interval Remote AddressUnit Type Type 4 Read Interval Type 1 Read IntervalType 2 Read Interval Type 3 Read IntervalTime Synchronization Interval Type 7 Read IntervalType 8 Read Interval Configuring the A164MODE Table A164MODE First DvcfNumber of Dvcf BECCO2200 DCA Configuring the A164DVCF Configuration Table Number of Data Records First UnitNumber of Units First Data RecordConfiguring the A164DTBL Configuration Table Data Value Table TypePoint Number Appendix AMessages Logged by the BECO2200 DCA Fatal Error MessagesF103 Bad Cfgdca record counts, must be F100 Bad A164APPL record counts, must beF101 Bad A164PORT record counts, must be F102 Bad A164UNIT record counts, must beF106 Total # devices exceeds Unit size F107 x WESDACy pnts configured, z requiredF105 Invalid SOE Overflow parameter F111 Bad A164DVCF record counts, must be F108 x table creation errorF110 Fatal errors exist in configuration F109 Cannot find x database tableF123 Dvcf Record x, invalid Number of Units F120 Mode Record x, invalid First DvcfF121 Mode Record x, invalid Number of Dvcf F122 Dvcf Record x, invalid First UnitF125 Dvcf Record x, invalid Number of Type-Point F200 Error x on win openF201 Error x signaling A164-D-00 process F203 Error x creating A164-y-z exchangeF207 Unable to allocate buffers F204 Error x spawning A164-y-z processF205 Error x activating A164-y-z process F206 Process A164-x-y died while initializingE302 Port rec x, num of devices exceeds Unit Non-Fatal Error MessagesE300 Port rec x, invalid baud rate E301 Port rec x, invalid failures before offlineE305 Unit rec x, invalid unit type E303 Port rec x, configuration badE307 Unit rec x, configuration bad E304 Port rec x, invalid unit addressE308 Port rec x, num of devices cannot = E399 Non-fatal errors exist in configurationE400 Error x opening port y E401 Error x setting character portE405 Error x activating A164-y-z process E402 Error x setting SIO timersE403 Error x creating A164-y-z exchange E404 Error x spawning A164-y-z processE408 Unable to allocate polling list E407 Error x signalling A164-y-z processE409 Error x, invalid start signal from Spawner E406 Process A164-x-y died while initializingPSOS Interface Warnings I702 Port rec x, invalid RTS off time Information MessagesI700 Port rec x, invalid reply time-out I701 Port rec x, invalid RTS on timeI705 Port rec x, no polling required I703 Port rec x, invalid intercharacter timeoutI704 No Configuration deleting AO Operate Failed Output Request Return CodesDemand Scan Failed Do Operate FailedAscii Glossary of TermsRAM Menu-oriented software program that operates on a personal A164-0CG-1.00-2Restricted List of Acronyms and Abbreviations