| BECCO2200 DCA |
GE Energy Services | Configuration Guide |
Remedy:
•Address all
E308: PORT rec <x>, num of devices cannot = 0
Cause:
•The Number of Devices on Port parameter in record <x> of the A164PORT table is equal to zero.
Effect:
•Communication on this port will be unavailable.
Remedy:
•Review the section on configuring the A164PORT table (Chapter 4:), and verify that the Number of Devices on Port is correct.
E399: Non-fatal errors exist in configuration
Cause:
•The BECO2200 DCA encountered
Effect:
•The BECO2200 will be unable to communicate to some or all of the devices configured.
Remedy:
•Address all
E400: Error <x> opening port <y>
Cause:
•The BECO2200 DCA failed in its attempt to open the communication port <y>. The error code returned was <x>.
Effect:
•Communication to all devices configured for this port will be unavailable.
Remedy:
•Ensure that no other application is configured to use port <y>.
•Call the Customer Service department and report this error.
E401: Error <x> setting character port
Cause:
•The BECO2200 DCA failed in its attempt to set the communication port characteristics. The error code returned was <x>.
Effect:
•Communication to all devices configured for this port will be unavailable.
Remedy:
•Call the Customer Service department and report this error.
34 | Full |
|