BECCO2200 DCA |
|
Configuration Guide | GE Energy Services |
E303: PORT rec <x>, configuration bad
Cause:
•The BECO2200 DCA encounter
Effect:
•Communication to all BECO2200 devices configured to use this port will be unavailable.
Remedy:
•Address all
E304: PORT rec <x>, invalid unit address
Cause:
•Record <x> of the A164PORT table contains an invalid Unit Address.
Effect:
•Communication to all BECO2200 devices configured to use this port will be unavailable.
Remedy:
•Review the section on configuring the A164PORT table (Chapter 4:), and verify that the Unit Address configuration parameter is within the range of 0 through 255.
E305: UNIT rec <x>, invalid unit type
Cause:
•Record <x> of the A164UNIT table contains an invalid Unit Type.
Effect:
•Communication to this unit will be unavailable.
Remedy:
•Review the section on configuring the BECO2200 DCA A164UNIT Configuration Table (Chapter 5:), and verify that the Unit Type is
E306: Unit <x> and <y>, same address on port <z>
Cause:
•Two BECO2200 devices have been configured with the same address on port <z>.
Effect:
•Communication to the two devices will be unavailable.
Remedy:
•Review the section on configuring the A164UNIT table (Chapter 5:), and verify that the addresses of records <x> and <y>. Each unit address on a given port must be unique.
E307: UNIT rec <x>, configuration bad
Cause:
•The BECO2200 DCA encountered
Effect:
•Communication to this unit will be unavailable.
Restricted |
Full | 33 |
|