| BECCO2200 DCA |
GE Energy Services | Configuration Guide |
E406: Process A164-<x>-<y> died while initializing
Cause:
•Process
Effect:
•If <y> equals C: Communication to all devices configured for this port will be unavailable.
•If <y> equals P: No polling of devices will occur for this port. Demand scanning is available.
Remedy:
•Address any fatal or
•Call the Customer Service Department and report this error.
E407: Error <x> signalling A164-<y>-<z> process
Cause:
•The BECO2200 DCA was unable to signal the
Effect:
•If <y> equals C: Communication to all devices configured for this port will be unavailable.
•If <y> equals P: No polling of devices will occur for this port. Demand scanning is available.
Remedy:
•Call the Customer Service Department and report this error.
E408: Unable to allocate polling list
Cause:
•The BECO2200 DCA was unable to allocate enough memory for is polling lists.
Effect:
•The BECO2200 DCA will be unable to poll any of the devices configured. Demand scanning is available.
Remedy:
•Reduce the amount of RAM used by this and any other application in the system. The parameters that affect the amount of RAM required by this application are noted in their associated chapters.
•Upgrade the GE Energy Services product to a model with more memory.
•Call the Customer Service department and report this error.
E409: Error <x>, invalid start signal from Spawner
Cause:
•This process failed to receive the start signal from the BECO2200 DCA spawner. The error code returned was <x>.
36 | Full |
|