Page 19
Chapter 2: Configuring Win for the BECO2200 DCA
This chapter describes how to configure the WESDAC Interface Node (WIN) for the BECO2200 DCA. The application number for WIN is B008. Refer to the WIN User’s Configuration Guide for more information on how to configure WIN. The functionality of all points required by the BECO2200 DCA is defined in the BECO2200 DCA Functional Specification.
2.1WESDAC Point Allocation
WESDAC data point allocation is accomplished by specifying the required number of points in the WIN configuration tables. Any points allocated to the BECO2200 DCA are maintained solely by the BECO2200 DCA. This means the BECO2200 DCA is the only application that may modify the value or the status of those points. All points allocated to the BECO2200 DCA are initialized to off-line and not communicating. If the WESDAC table is in NVRAM, points are initialized to the current value (state) in NVRAM. If the WESDAC table is in RAM, the points are initialized to zero (off).
| WESDAC DATA TYPE | | | Number of points required | |
| | | BECO 2200 M-0420 | |
| | | | |
| Binary Inputs | | 42 | |
| | | | |
| Binary Outputs | | 44+MDPC | |
| | | | |
| Counters | | 38 | |
| | | | |
| Analog Input | | 281 | |
| | | | |
| Analog Outputs | | 78 | |
| | | | |
| Device Status | | 1 | |
| | | | |
| | | | | |
| Table 2 Required Points BECO2200 Device |
| | | | | |
Restricted | A164-0CG-1.00-2 |
Full | 3 |
| | | |
Contents
BECCO2200 DCA
Configuration Guide
Trademark Notices
Table of Contents
Configuring the A164MODE Table
Configuring the A164DTBL Configuration Table
BECCO2200 DCA
List of Figures
Viii
List of Tables
BECCO2200 DCA
Purpose of this Guide
About this Guide
Who Should Use this Guide
Introduction to the Wesdac D20 RTU GEN-0003
Additional Documentation
How this Guide is Organized
Xiv
Overview
Xvi
BECO2200 DCA Configuration Tables
Configuration Tables
Configuration Sequence
Wesdac Point Allocation
Configuring Win for the BECO2200 DCA
Analog Inputs
Binary Inputs
Binary Outputs
Counters
General Information
Configuring the A164APPL Table
Description of Fields
SOE Buffer Overflow Option
Reply Buffer Size Adjustment
SOE Buffer Size Adjustment
DCA Index
Device Event Response Time
BECCO2200 DCA
BECO2200 DCA A164PORT Configuration Table
Configuring the A164PORT Table
RTS On Time
Communication Port Name
Communication Port Parity
Baud Rate
Remote Reply Timeout
Intercharacter Timeout
RTS Off Time
Number of Devices on Port
Line Idle Time
Retries Before Failure
Failures Before Off-line
BECO2200 DCA A164UNIT Configuration Table
Configuring the A164UNIT Table
Unit Type
Remote Address
Type 0 Read Interval
Type 4 Read Interval
Type 1 Read Interval
Type 2 Read Interval
Type 3 Read Interval
Type 8 Read Interval
Type 7 Read Interval
Time Synchronization Interval
Configuring the A164MODE Table
A164MODE
First Dvcf
Number of Dvcf
BECCO2200 DCA
Configuring the A164DVCF Configuration Table
Number of Data Records
First Unit
Number of Units
First Data Record
Configuring the A164DTBL Configuration Table
Point Number
Table Type
Data Value
Appendix AMessages Logged by the BECO2200 DCA
Fatal Error Messages
F103 Bad Cfgdca record counts, must be
F100 Bad A164APPL record counts, must be
F101 Bad A164PORT record counts, must be
F102 Bad A164UNIT record counts, must be
F105 Invalid SOE Overflow parameter
F107 x WESDACy pnts configured, z required
F106 Total # devices exceeds Unit size
F111 Bad A164DVCF record counts, must be
F108 x table creation error
F110 Fatal errors exist in configuration
F109 Cannot find x database table
F123 Dvcf Record x, invalid Number of Units
F120 Mode Record x, invalid First Dvcf
F121 Mode Record x, invalid Number of Dvcf
F122 Dvcf Record x, invalid First Unit
F125 Dvcf Record x, invalid Number of Type-Point
F200 Error x on win open
F201 Error x signaling A164-D-00 process
F203 Error x creating A164-y-z exchange
F207 Unable to allocate buffers
F204 Error x spawning A164-y-z process
F205 Error x activating A164-y-z process
F206 Process A164-x-y died while initializing
E302 Port rec x, num of devices exceeds Unit
Non-Fatal Error Messages
E300 Port rec x, invalid baud rate
E301 Port rec x, invalid failures before offline
E305 Unit rec x, invalid unit type
E303 Port rec x, configuration bad
E307 Unit rec x, configuration bad
E304 Port rec x, invalid unit address
E308 Port rec x, num of devices cannot =
E399 Non-fatal errors exist in configuration
E400 Error x opening port y
E401 Error x setting character port
E405 Error x activating A164-y-z process
E402 Error x setting SIO timers
E403 Error x creating A164-y-z exchange
E404 Error x spawning A164-y-z process
E408 Unable to allocate polling list
E407 Error x signalling A164-y-z process
E409 Error x, invalid start signal from Spawner
E406 Process A164-x-y died while initializing
PSOS Interface Warnings
I702 Port rec x, invalid RTS off time
Information Messages
I700 Port rec x, invalid reply time-out
I701 Port rec x, invalid RTS on time
I704 No Configuration deleting
I703 Port rec x, invalid intercharacter timeout
I705 Port rec x, no polling required
AO Operate Failed
Output Request Return Codes
Demand Scan Failed
Do Operate Failed
Ascii
Glossary of Terms
RAM
Menu-oriented software program that operates on a personal
A164-0CG-1.00-2Restricted
List of Acronyms and Abbreviations