BECCO2200 DCA |
|
Configuration Guide | GE Energy Services |
F105: Invalid SOE Overflow parameter
Cause:
•The SOE Buffer Overflow Option configuration parameter in the A164APPL table is neither Overwrite Oldest (0) nor Discard Newest (1).
Remedy:
•·Review the section on configuring the A164APPL table (Chapter 3:) and verify that the SOE Buffer Overflow Option is configured correctly.
F106: Total # devices exceeds UNIT size
Cause:
•The sum of all BECO2200 devices specified in all records of the A164PORT table is greater than the number of records in the A164UNIT table.
Remedy:
•Address all fatal and
•Review the section on configuring the A164PORT table (Chapter 4:) and verify that the Number of Devices on Port configuration parameter in each record is correct.
•Verify the sum of all Number of Devices on Port configuration parameters is less than or equal to the number of records in the A164UNIT table.
F107: <x> WESDAC_<y> pnts configured, <z> required
Cause:
•<x> number of WESDAC_<y> points were configured in the WIN CFG_DCA table for the BECO2200 DCA. <z> points are required.
Remedy:
•Review the section on configuring WIN for the BECO2200 DCA (Chapter 2:) and verify that the number of WESDAC_<y> points configured for the BECO2200 DCA is greater than or equal to <z>.
WESDAC NUMBER | DATA TYPE |
|
|
WESDAC_1 | Binary Input |
|
|
WESDAC_2 | Binary Output |
|
|
WESDAC_3 | Counter |
|
|
WESDAC_4 | Analog Input |
|
|
WESDAC_5 | Analog Output |
|
|
WESDAC_6 | Device Status |
|
|
|
|
Table 10 WESDAC Number Definitions