GE BECCO2200 manual F105 Invalid SOE Overflow parameter, F106 Total # devices exceeds Unit size

Page 43

BECCO2200 DCA

 

Configuration Guide

GE Energy Services

F105: Invalid SOE Overflow parameter

Cause:

The SOE Buffer Overflow Option configuration parameter in the A164APPL table is neither Overwrite Oldest (0) nor Discard Newest (1).

Remedy:

·Review the section on configuring the A164APPL table (Chapter 3:) and verify that the SOE Buffer Overflow Option is configured correctly.

F106: Total # devices exceeds UNIT size

Cause:

The sum of all BECO2200 devices specified in all records of the A164PORT table is greater than the number of records in the A164UNIT table.

Remedy:

Address all fatal and non-fatal error messages preceding this message.

Review the section on configuring the A164PORT table (Chapter 4:) and verify that the Number of Devices on Port configuration parameter in each record is correct.

Verify the sum of all Number of Devices on Port configuration parameters is less than or equal to the number of records in the A164UNIT table.

F107: <x> WESDAC_<y> pnts configured, <z> required

Cause:

<x> number of WESDAC_<y> points were configured in the WIN CFG_DCA table for the BECO2200 DCA. <z> points are required.

Remedy:

Review the section on configuring WIN for the BECO2200 DCA (Chapter 2:) and verify that the number of WESDAC_<y> points configured for the BECO2200 DCA is greater than or equal to <z>.

WESDAC NUMBER

DATA TYPE

 

 

WESDAC_1

Binary Input

 

 

WESDAC_2

Binary Output

 

 

WESDAC_3

Counter

 

 

WESDAC_4

Analog Input

 

 

WESDAC_5

Analog Output

 

 

WESDAC_6

Device Status

 

 

 

 

Table 10 WESDAC Number Definitions

Restricted

A164-0CG-1.00-2

Full

27

 

Image 43
Contents BECCO2200 DCA Configuration GuideTrademark Notices Table of Contents Configuring the A164MODE Table Configuring the A164DTBL Configuration Table BECCO2200 DCA List of Figures Viii List of Tables BECCO2200 DCA Purpose of this Guide About this GuideWho Should Use this Guide Introduction to the Wesdac D20 RTU GEN-0003 Additional DocumentationHow this Guide is Organized Xiv Overview Xvi BECO2200 DCA Configuration Tables Configuration TablesConfiguration Sequence Wesdac Point Allocation Configuring Win for the BECO2200 DCAAnalog Inputs Binary InputsBinary Outputs CountersGeneral Information Configuring the A164APPL TableDescription of Fields SOE Buffer Overflow Option Reply Buffer Size AdjustmentSOE Buffer Size Adjustment DCA IndexDevice Event Response Time BECCO2200 DCA BECO2200 DCA A164PORT Configuration Table Configuring the A164PORT TableRTS On Time Communication Port NameCommunication Port Parity Baud RateRemote Reply Timeout Intercharacter TimeoutRTS Off Time Number of Devices on Port Line Idle TimeRetries Before Failure Failures Before Off-lineBECO2200 DCA A164UNIT Configuration Table Configuring the A164UNIT TableUnit Type Remote AddressType 0 Read Interval Type 4 Read Interval Type 1 Read IntervalType 2 Read Interval Type 3 Read IntervalType 8 Read Interval Type 7 Read IntervalTime Synchronization Interval Configuring the A164MODE Table A164MODE First DvcfNumber of Dvcf BECCO2200 DCA Configuring the A164DVCF Configuration Table Number of Data Records First UnitNumber of Units First Data RecordConfiguring the A164DTBL Configuration Table Point Number Table TypeData Value Appendix AMessages Logged by the BECO2200 DCA Fatal Error MessagesF103 Bad Cfgdca record counts, must be F100 Bad A164APPL record counts, must beF101 Bad A164PORT record counts, must be F102 Bad A164UNIT record counts, must beF105 Invalid SOE Overflow parameter F107 x WESDACy pnts configured, z requiredF106 Total # devices exceeds Unit size F111 Bad A164DVCF record counts, must be F108 x table creation errorF110 Fatal errors exist in configuration F109 Cannot find x database tableF123 Dvcf Record x, invalid Number of Units F120 Mode Record x, invalid First DvcfF121 Mode Record x, invalid Number of Dvcf F122 Dvcf Record x, invalid First UnitF125 Dvcf Record x, invalid Number of Type-Point F200 Error x on win openF201 Error x signaling A164-D-00 process F203 Error x creating A164-y-z exchangeF207 Unable to allocate buffers F204 Error x spawning A164-y-z processF205 Error x activating A164-y-z process F206 Process A164-x-y died while initializingE302 Port rec x, num of devices exceeds Unit Non-Fatal Error MessagesE300 Port rec x, invalid baud rate E301 Port rec x, invalid failures before offlineE305 Unit rec x, invalid unit type E303 Port rec x, configuration badE307 Unit rec x, configuration bad E304 Port rec x, invalid unit addressE308 Port rec x, num of devices cannot = E399 Non-fatal errors exist in configurationE400 Error x opening port y E401 Error x setting character portE405 Error x activating A164-y-z process E402 Error x setting SIO timersE403 Error x creating A164-y-z exchange E404 Error x spawning A164-y-z processE408 Unable to allocate polling list E407 Error x signalling A164-y-z processE409 Error x, invalid start signal from Spawner E406 Process A164-x-y died while initializingPSOS Interface Warnings I702 Port rec x, invalid RTS off time Information MessagesI700 Port rec x, invalid reply time-out I701 Port rec x, invalid RTS on timeI704 No Configuration deleting I703 Port rec x, invalid intercharacter timeoutI705 Port rec x, no polling required AO Operate Failed Output Request Return CodesDemand Scan Failed Do Operate FailedAscii Glossary of TermsRAM Menu-oriented software program that operates on a personal A164-0CG-1.00-2Restricted List of Acronyms and Abbreviations