A.2 Non-Fatal Error Messages
This section contains a description of all these
E300: PORT rec <x>, invalid baud rate
Cause:
•Record <x> of the A164PORT table contains an invalid Baud Rate.
Effect:
•Communication to all BECO2200 devices configured to use this port will be unavailable.
Remedy:
•Review the section on configuring the A164PORT table (Chapter 4:), and verify that the Baud Rate configuration parameter is configured as either 110, 300, 600, 1200, 2400, 4800, or 9600.
E301: PORT rec <x>, invalid failures before offline
Cause:
•Record <x> of the A164PORT table contains an invalid Failures Before Offline.
Effect:
•Communication to all BECO2200 devices configured to use this port will be unavailable.
Remedy:
•Review the section on configuring the A164PORT table (Chapter 4:), and verify that the Failures Before
E302: PORT rec <x>, num of devices exceeds UNIT
Cause:
•The Number of Devices on Port parameter in record <x> of the A164PORT table is greater than the number of records in the A164UNIT table.
Effect:
•Communication to all BECO2200 devices configured to use this port will be unavailable.
Remedy:
•Review the section on configuring the A164PORT table (Chapter 4:), and verify that the Number of Devices on Port is correct.