Foundry Networks FGS624P-POE, FGS648P-POE, FGS624XGP-POE manual Foundry Networks, Inc

Page 92

FastIron GS Compact Layer 2 Switch Hardware Installation Guide

CAUTION: For the DC input circuit to the system (DC power supply part number RPSDC-FGS), make sure there is a 30 amp circuit breaker, minimum -48Vdc, double pole, on the input to the terminal block. The input wiring for connection to the product should be copper wire, 10 AWG, marked VW-1, and rated minimum 90 degrees celcius.

VORSICHT: Für den Eingangs-Gleichstromkreis zum System (Gleichstromnetzteile mit der Teilenr. RPSDC-FGS) ist ein 30 A (Minimum), -48 V DC, doppelpolig, am Eingang zur Reihenklemme zu installieren. Bei der Eingangsverdrahtung zum Anschluss des Produkts sollte es sich um einen 10 AWG-Kupferdraht (VW-1) und einer Mindestnenntemperatur von 32° handeln.

MISE EN GARDE: Pour le circuit d’alimentation C.C du système (références du bloc d’alimentation C.C. RPSDC-FGS), assurez-vous de la présence d’un disjoncteur de 30 ampères, minimum –48 V C.C., double coupure, sur l’entrée vers le bloc d’alimentation. Les câbles d’alimentation pour le produit doivent être en fils de cuivre, 10 AWG (American Wire Gauge), marqués VW-1 et classés 90 degrés Celsius.

PRECAUCIÓN: Para el circuito de entrada de CC al sistema (suministro de corriente continua con No. de referencia RPSDC-FGS), verifique que existe un cortacircuitos catalogado de 30 amperios, como mínimo, -48 VCC, bipolar, en la entrada al bloque terminal. El cableado de entrada para la conexión al producto deberá ser de cable de cobre catalogado, 10 AWG, marcado con VW- 1, y tener una capacidad nominal mínima para 90 grados centígrados.

CAUTION: Make sure you insert the power supply right-side up. It is possible to insert the supply upside down, although the supply will not engage with the power backplane when upside down. The power supply is right-side up when the power connector is on the left and the fan vent is on the right.

VORSICHT: Sicher Sie sicher, dass Sie das Netzteil mit der richtigen Seite nach oben weisend einstecken. Man kann die Karte auch umgekehrt einstecken. Allerdings rastet das umgekehrte Netzteil nicht in die Netzstrom-Rückwandplatine ein. Die rechte Seite des Netzteils weist nach oben, wenn sich der Stromanschlussstecker links und der Ventilatorschlitz rechts befindet.

MISE EN GARDE: Assurez-vous d'insérer le bloc d'alimentation dans le bon sens. Il est possible de l'insérer " la tête en bas ", mais le bloc d'alimentation ne s'enclenchera pas dans la face arrière d'alimentation s'il est inséré à l'envers. Le bloc d'alimentation est dans le bon sens lorsque le connecteur se trouve sur le côté gauche et le ventilateur sur la droite.

PRECAUCIÓN: Verifique que inserta el suministro de corriente con la cara correcta hacia arriba. Es posible insertar el suministro hacia abajo, pese a que este no se conectará con el enchufe posterior de esta forma. El suministro de potencia estará con la cara correcta hacia arriba cuando el conector de corriente quede a la izquierda y la abertura del ventilador queda a la derecha.

CAUTION: Use the erase startup-config command only for new systems. If you enter this command on a system you have already configured, the command erases the configuration. If you accidentally do erase the configuration on a configured system, enter the write memory command to save the running configuration to the startup-config file.

VORSICHT: Verwenden Sie den Befehl "Erase startup-config" (Löschen Startup-Konfig) nur für neue Systeme. Wenn Sie diesen Befehl in ein bereits konfiguriertes System eingeben, löscht der Befehl die Konfiguration. Falls Sie aus Versehen die Konfiguration eines bereits konfigurierten Systems löschen, geben Sie den Befehl "Write Memory" (Speicher schreiben) ein, um die laufende Konfiguration in der Startup-Konfig-Datei zu speichern.

MISE EN GARDE: N'utilisez la commande erase startup-config que pour les nouveaux systèmes. Si vous entrez cette commande sur un système que vous avez déjà configuré, elle efface la configuration. Si

B - 4

© 2007 Foundry Networks, Inc.

September 2007

Image 92
Contents FGS Release Page Contents Hecking C Onnectivity Hardware Specifications Egulatory S Tatements Chapter About This Guide IntroductionWhat’s Included in This Edition? AudienceRelated Publications How to Get HelpWarranty Coverage Chapter Product Overview Product OverviewFGS624P and FGS624P-POE Software FeaturesHardware Features FGS624XGP and FGS624XGP-POE FGS648P and FGS648P-POEControl Features Shows the FGS648P and FGS648P-POESerial Management Interface Console Port Optional 2-port 10-GbE Module port 49Network Interfaces Show Media Description Reset ButtonNetwork Interfaces 10/100/1000 Mbps Ports Port 10-GbE Module10GbE XFP Transceiver FGS624XGP Models Only Port CX4 Module ReleasePort 10-GbE Hybrid Interface Module Release 10GbE XG and CX4 Module CX4 10Gbps XFP TransceiverLEDs for Network Interfaces and Power Supplies LEDsPosition State Meaning 10/100/1000 Copper Port LEDs 100/1000 Fiber Port LEDsPower Supply LEDs Position State MeaningGbps Port LEDs POE Port LEDsPosition State Meaning Stacking LEDs Power SuppliesFiber Optic Modules Power Specifications for POE Cooling System and FansSeptember Chapter Installing the FastIron GS Chassis Package ContentsUnpacking a System General RequirementsSummary of Installation Tasks Summary of Installation Tasks Where to Find More InformationInstallation Precautions General PrecautionsLifting Precautions Summary of Installation TasksPower Supply Precautions Cabling Infrastructure Installation Location Preparing the Installation SiteInstalling an Additional Power Supply Installing an AC Power Supply Power supply locking screw LatchesRetaining Bale AC Power Cord Installing a DC Power Supply Ground screw Negative terminal screw Ground Rack Mount Installation Installing the DeviceDesktop Installation Attaching the Short Mounting Brackets Wall Mount Installation Installing the Brackets and Mounting the DevicePowering On the System Install top screws Install devicePowering Off the System Verifying Proper OperationAttaching a PC or Terminal Observing the Power Status LEDsLEDs for Power FastIron FastIron-PREM DB-9 to DB-9 Chapter Connecting Network Devices Checking Connectivity Assigning Permanent PasswordsRecovering from a Lost Password Configuring IP Addresses Devices Running Layer 2 SoftwareConnecting to Ethernet or Fast Ethernet Hubs Connecting Network DevicesCable Specifications Connecting to Workstations, Servers, or Routers Connecting a Network Device to a Fiber PortInstalling a Fiber Optic Module Automatic MDI/MDIX DetectionTesting Connectivity Cleaning the Fiber-Optic ConnectorsPinging an IP Address Cabling a Fiber Optic ModuleDesired Meaning Abnormal Meaning/Action State Observing LEDsNetwork Connection-Related LED States Troubleshooting Network Connections Using Virtual Cable Testing to Diagnose a CableConfiguration Notes Command SyntaxCable Statistics Displays Viewing the Results of the Cable AnalysisThis Line September Managing Temperature Settings Using the Temperature SensorDisplaying the Temperature Chapter Managing the FastIron GS ChassisDisplaying Temperature Messages Changing the Temperature Warning LevelRemoving MAC Address Entries Changing the Chassis Temperature Polling IntervalDisplaying Management Module CPU Usage September Power Supply Specifications Chapter Hardware SpecificationsChassis Specifications Chassis Specifications Physical Dimensions and WeightEnvironmental Considerations Storage EnvironmentChassis Regulatory Compliance Description Certifications CoolingRegulatory Compliance Power Source Interruptions Mean Time Between FailurePower Draw Specifications Power Supply Draw Specifications Model Typical MaximumPinouts and Signalling Serial Console Port PinoutsLists the pin assignment and signalling for 10/100/100 ports 10/100 and Gigabit Port PinoutsLC connector 62.5/125 200 For SFP module Power Supply Specifications Power CordsWarranty LC connector 1530.33 Up to For XFP module 1561.42 nm 80 kmKey features FGS648 Power Supply Consumption10 Maximum Power Supply Consumption for FGS Models FGS624 Power Supply Input Connector Properties Input Connector and Plug11 Input Connector for Power Supplies Safety Warnings 13 Safety Warning Labels on Power SuppliesElectrical Specifications Output SpecificationsChapter Maintaining the FastIron GS Hardware Hardware Maintenance ScheduleReplacing a Power Supply AC Power Supplies Installation Precautions and WarningsDetermining Which Power Supply Failed Removing an AC Power Supply Locking screwInstalling an AC Power Supply DC Power Supplies Removing a DC Power Supply Shows a front view of the DC power supplyInstalling a DC Power Supply Ground Removing a 2-port 10-GbE Module Installing or Replacing a 2-port 10-GbE ModuleInstalling a 2-port 10-GbE Module Installing or Replacing a POE Daughter Card Installing a 2-port 10-GbE ModuleDisassembling the Chassis Removing the Screws for the Top CoverInstalling a POE Daughter Card Removing the Top CoverPOE Daughter Card Re-assembling the Chassis POE Daughter CardsReplacing a Fiber Optic Module Removing a Fiber Optic ModuleCabling a Fiber Optic Module Cleaning the Fiber-Optic ConnectorsInstalling a New Fiber Optic Module Digital Optical Monitoring Status Value DescriptionCLI Commands No optical-monitor alarm intervalSupported Media Show optic port/slotnumberAppendix a Regulatory Statements Industry Canada StatementEurope and Australia JapanEnglish Translation of above statement Appendix B Foundry Networks, Inc Page Foundry Networks, Inc Page September Page September