24 en Connection | VEZ-400 Mini PTZ Dome |
| |
NOTICE!
The wire shield must be tied to signal at both ends, if 2-wire twisted pair is used.
NOTICE!
When the RS-485 signal is looped through, ensure that (only) the last device is terminated properly. Improper RS-485 wiring or termination may result in unreliable system operation.
Use a 2-wire (shielded), half-duplex, differential, multi-drop with the following attributes:
Wire Type | 2-wire Shielded Twisted Pair |
Distance | 1.2 Km (3937 ft) |
Gauge | 0.511 mm (24 AWG) |
Impedance | 120 Ω |
Table 6.1 RS-485 Wire Specifications
The following table shows the terminal connections for the 2- pin terminal block RS-485 connections (see Figure 6.1, item 5):
Number | | Signal | Color | |
1 | | TRX + | Sky | |
2 | | TRX - | White | |
Table 6.2 | 2-pin Terminal Block Connections |
NOTICE!
When the camera's RS-485 port is connected to a MIC-BP3 Biphase convertor, the camera's TRX+ should be connected to the convertor's RxB, and TRX- should be connected to RxA. The camera's baud rate should be set to 9600, and the protocol should be set to Bosch OSRD. Also make sure that the camera ID is configured correctly. For further details on setting up the MIC-BP3, please refer to the separate MIC-BP3 Bi-Phase Converter Card Installation and Operation Manual.