Emerson MAS 2600 user manual = 12 mA

Page 23

 

Installation & User Manual

June 2013

Ed 19UK

 

 

Recalibrating Gauge Transmitter using Vacuum (for gauge transmitters only)

An internally mounted transducer can also be recalibrated by using vacuum.

1.Check that the tank is empty.

2.Check that the range select switch on the amplifier is correctly set.

3.Set the calibrator to vacuum mode.

4.Connect the hose from the calibrator to the breather tube from the transducer cable.

5.In conditions of no pressure the output signal should be adjusted to 4.00 mA on the zero potentiometer.

6.Increase the vacuum equal to the maximum height of the fluid (water gauge) and adjust the output signal to 20.00 mA on the span potentiometer.

7.Remove the vacuum and check the zero point.

8.Check the linearity at 0-25-50-75 and 100% of the measuring range.

9.If necessary, repeat the steps 5 to 8.

NOTE:

If the calibrated maximum water gauge is greater than the maximum water gauge

 

that can be generated by the vacuum calibrator, the proportional mA output signal

 

equal to the maximum vacuum signal should be calculated.

EXAMPLE: If the full-scale of the transmitter is 15 mH2O, and the maximum capacity of the vacuum calibrator is 7.5 mH2O, the mA output signal at 7.5 mH2O is calculated as:

15 mH2O = 20 mA and 0 mH2O = 4 mA

7.5 mH2O = 4 +

(20 4) * 7.5

= 12 mA

15

 

 

 

 

The span potentiometer is adjusted so that the output signal shows 12 mA at 7.5 mH2O.

Page 23 of 28

Image 23
Contents MAS2600 Table of contents Application MAS2600 Tank Contents TransmitterDescription and Operation Technical Specifications Transducer Ranges MAS2600 Ordering InformationGauge Transmitter TypeTransducer type 3.5 bar abs 2.0 bar abs Gauge and High Temperature Gauge TransducersSelecting the Measuring Range Selecting the Transducer TypeForepeak Tank Absolute TransducersBasic Rules Draft Temperature Sensor MAS2600-XXX-XX-X/XXPole Mounting drawing no. G022P011 Brackets for Internal Mounting drawing no. G022P010Flange Mounting drawing no. G022P013 Pipe End Mounting drawing no. G022P015Flexible rubber tube mounting 80 ºC drawing no. G022P001 DN25 flange with 1 ball valve drawing no. G022P019 75.0 Deck Box 165B9035 Handling Installation June XXXXXX-YYYY Intrinsically Safe InstallationEd 19UK Any 28V / 300R Testing Testing and Recalibrating= 12 mA + P Trd .range −Calculated output at atmospheric pressure Trouble Shooting Maintenance and Trouble ShootingMaintenance FAX MAS2600 Test sheetEmerson Process Management