Recalibrating Gauge Transmitter using Vacuum (for gauge transmitters only)
An internally mounted transducer can also be recalibrated by using vacuum.
1.Check that the tank is empty.
2.Check that the range select switch on the amplifier is correctly set.
3.Set the calibrator to vacuum mode.
4.Connect the hose from the calibrator to the breather tube from the transducer cable.
5.In conditions of no pressure the output signal should be adjusted to 4.00 mA on the zero potentiometer.
6.Increase the vacuum equal to the maximum height of the fluid (water gauge) and adjust the output signal to 20.00 mA on the span potentiometer.
7.Remove the vacuum and check the zero point.
8.Check the linearity at
9.If necessary, repeat the steps 5 to 8.
NOTE: | If the calibrated maximum water gauge is greater than the maximum water gauge |
| that can be generated by the vacuum calibrator, the proportional mA output signal |
| equal to the maximum vacuum signal should be calculated. |
EXAMPLE: If the
15 mH2O = 20 mA and 0 mH2O = 4 mA
7.5 mH2O = 4 + | (20 − 4) * 7.5 | = 12 mA | |
15 |
| ||
|
|
|
The span potentiometer is adjusted so that the output signal shows 12 mA at 7.5 mH2O.