EXAMPLE: If the range of the transducer is 3.5 bar abs and the atmospheric pressure is 1005 mbar.

Calculated output at atmospheric pressure:

mA @ Atm.press =

4 +

16 * (1005 800)

= 5.215 mA

 

 

3500 800

 

Calculated applied pressure for maximum output: mbarg @ 20 mA = 3500 1005 = 2495 mbarg Calculated pressure at 50% of the transducer range:

mA @ P mbarg =

4 +

16*(1005 800 + 1750)

= 15.585 mA

 

 

3500 800

 

Page 25 of 28

Image 25
Contents MAS2600 Table of contents Description and Operation MAS2600 Tank Contents TransmitterApplication Technical Specifications Transducer Ranges MAS2600 Ordering InformationGauge Transmitter TypeSelecting the Measuring Range Gauge and High Temperature Gauge TransducersSelecting the Transducer Type Transducer type 3.5 bar abs 2.0 bar absBasic Rules Absolute TransducersForepeak Tank Draft Temperature Sensor MAS2600-XXX-XX-X/XXPole Mounting drawing no. G022P011 Brackets for Internal Mounting drawing no. G022P010Flange Mounting drawing no. G022P013 Pipe End Mounting drawing no. G022P015Flexible rubber tube mounting 80 ºC drawing no. G022P001 DN25 flange with 1 ball valve drawing no. G022P019 75.0 Deck Box 165B9035 Handling Installation June XXXXXX-YYYY Intrinsically Safe InstallationEd 19UK Any 28V / 300R Testing Testing and Recalibrating= 12 mA + P Trd .range −Calculated output at atmospheric pressure Maintenance Maintenance and Trouble ShootingTrouble Shooting FAX MAS2600 Test sheetEmerson Process Management